COMPRESSOR HIGH DISCHARGE TEMPERATURE, REFRIGERATION SYSTEM | MARINE ELECTRICIAN

  Рет қаралды 32,886

leckyjake

leckyjake

2 жыл бұрын

We had a unit having a high discharge temperature which stops the unit and go out of range.
here is the troubleshooting video I did in fixing this unit
• REFRIGERATED CONTAINER...
• TROUBLE WITH DAIKIN RE...

Пікірлер: 51
@user-hd7nj9bp4q
@user-hd7nj9bp4q 3 ай бұрын
Thank you sharing the reefers stories that couldn't teach in school😊😊😊
@ChandanaPriyantha-pq3uv
@ChandanaPriyantha-pq3uv 2 күн бұрын
Thank you sir for the technology of new generation,I am interested
@digitald5851
@digitald5851 2 жыл бұрын
The old pump and dump lol. Love the videos.
@thamizhselvan7181
@thamizhselvan7181 2 жыл бұрын
Very useful 👍
@michellewu001964
@michellewu001964 2 жыл бұрын
Thank you for your help, it's really helpful, thanks again
@svyat8710
@svyat8710 2 жыл бұрын
Thanks a lot for this video
@6Diego1Diego9
@6Diego1Diego9 2 жыл бұрын
this guy is so good. so smart.
@kevincalonia5495
@kevincalonia5495 Жыл бұрын
Salamat sir Lecky marami akong natutunan sa inyu i hope sunod maging isa ako sa maging Cadet Electrician nyu po at assistant po😊
@calbear1503
@calbear1503 2 жыл бұрын
Thank brotha for the videos
@kyryl5673
@kyryl5673 Жыл бұрын
Hi, Jake! Safety First! For everybody: from the begining do not forget to check Freon type. Sime times we do simple mistake, and later on we do double job! Best regards and good luck!
@garywebb4244
@garywebb4244 2 жыл бұрын
Finding leaks can be painful to find when your on board ship. A lot of times I’ve found that the nut at the base of the high pressure valve or the low pressure valve is loose and leaking refrigerant. It’s important to check that nut anytime you’ve opened the valve.
@derrickenbuenosaires
@derrickenbuenosaires 2 жыл бұрын
Hi leckyjake, I always admired marine refrigeration. If I was contracted to do some work on a ship I would go just to try it out for once. I've worked on a couple of the transicold 69NT40 models and always wondered about the sight glass. There are two sight glasses on the receiver. A proper charge is around 5kg I think but the ball always remains pretty low on the visor. I see yours here went up pretty high. I assume the ball on the top visor should not float unless you are pumping down
@habagatbrown9842
@habagatbrown9842 2 жыл бұрын
Goodjob sir
@fazlul2930
@fazlul2930 2 жыл бұрын
Nice video
@syedbasheer8210
@syedbasheer8210 2 жыл бұрын
👍👍👍
@roelanddejonghe4694
@roelanddejonghe4694 2 жыл бұрын
Nice stagging 😉 did you find a leak or oil?
@syedbasheer8210
@syedbasheer8210 2 жыл бұрын
👍👍👍✅
@sailorlifeisbeautiful6180
@sailorlifeisbeautiful6180 2 жыл бұрын
Sir ,please make video about megger testing
@Vivek04581
@Vivek04581 2 жыл бұрын
Hi, do you have any video for msb breaker under voltage trip.
@JohnFlanagan-hs1fv
@JohnFlanagan-hs1fv 6 ай бұрын
Frontseat the discharge service valve and jump out the high pressure switch. Start unit and run
@toyinorodare4072
@toyinorodare4072 2 жыл бұрын
I love you training kudos Why was the leakage not fixed instead of recharging new Freon gas?
@rashad4333
@rashad4333 2 жыл бұрын
If he could use a pump to pull a vacuum there’s no leak. Air could have gotten into the system from someone not clearing gauges.
@moksmekanikongpandagat5256
@moksmekanikongpandagat5256 Жыл бұрын
elek id like to ask you if you have experienced high temperature alarm then the oil seems to disappear. this on a chiller for an inert gas generator.
@domalexus1991
@domalexus1991 2 жыл бұрын
I encountered that trouble sir, found out that freon leaked in the condenser coil
@danishmomin8102
@danishmomin8102 10 ай бұрын
Reefer Compressor, Bitzer Type VI. Head temperature going very high, Compressor disch temp almost 95. Checked cooling water flow, passages in head cleaned , condenser cleaned. Valve plate renewed
@danishmomin8102
@danishmomin8102 10 ай бұрын
But still temperature is very high. Kindly suggest what else to check
@TITUSITHOKA-ts9jl
@TITUSITHOKA-ts9jl 4 ай бұрын
​@@danishmomin8102Check if the compressor has enough oil and if the discharge pressure sensor is okay
@TARUNAKARYA1994
@TARUNAKARYA1994 10 ай бұрын
what triggers the low pressure temperature alarm? to -30°C, compressor pumpdown at -25°C 🙏🙏 Thanks sir...
@aripediaproject1113
@aripediaproject1113 2 жыл бұрын
How many person as an electrician or assistant electrician on your vessel ?
@NivagSwerdna
@NivagSwerdna 2 жыл бұрын
So there is a leak? Does this get recorded for testing when the container is offloaded?
@ChoroTesla
@ChoroTesla 2 жыл бұрын
I dont think if they are recorded it but its going to inspected well when the cargo is distuffed and the unit PTIed again and doing more leakage testing.
@hakhakuuba5073
@hakhakuuba5073 2 жыл бұрын
Our Daikin reefer compressor is not working. In Mongolia nobody can fix it..
@mlenstra
@mlenstra 2 жыл бұрын
Any idea where the refrigerant from the system went? Was there a leak you found and fixed?
@Gin-toki
@Gin-toki 2 жыл бұрын
Yeah, a leak seems highly possible, which means the problem will just return after some time. Could perhaps also be that it got air trapped during its previous maintenance.
@mlenstra
@mlenstra 2 жыл бұрын
@@Gin-toki at least here in the Netherlands (I think all EU countries) I’ve come to understand it’s actually illegal to refill a suspected leaking system with fluorinated refrigerant as it’s extremely bad for the environment to get these gases into the atmosphere. Not sure what type of refrigerant this reefer is using though, might be plain CO2 these days for all we know.
@Gin-toki
@Gin-toki 2 жыл бұрын
@@mlenstra it was stated in the video that it's freon.
@nunez23j1
@nunez23j1 2 жыл бұрын
It was R134a a refrigerant not a Freon, if you go by bottle color (orange) it’s R404 a refrigerant not a Freon.
@xrpengr.574
@xrpengr.574 2 жыл бұрын
is it allowed in your company to purge out the refrigerant nto the atmosphere..
@rajatawasthi4769
@rajatawasthi4769 Жыл бұрын
Nobody seen in middle of the sea .
@Venom-iz4de
@Venom-iz4de 2 жыл бұрын
Hi,i have additional question ,have mail or something similarly where can i contact You?
@navadaspencer7252
@navadaspencer7252 Жыл бұрын
Hi really need your help having trouble clearing a alarm cord Al 58 Compressor High Pressure Safety (HPS)
@leckyjake
@leckyjake Жыл бұрын
how much os your discharge pressure?
@rajatawasthi4769
@rajatawasthi4769 Жыл бұрын
We are doing everything but unit running 4-5 hr good and again it will give high dicarge pressure may be it's TXV give advice plz?
@geronocampo7630
@geronocampo7630 Жыл бұрын
Sir paano po nagwowork ang accumulator sa compressor ?
@danharoldsebastian7504
@danharoldsebastian7504 2 жыл бұрын
Good morning sir leckyjake. BSEE student po ako at graduating na po. after po mag board exam nagbabalak po ako maging katulad nyo po na eto. bale naaral ko na po mga dapat ko gawin para maging eto. tanong ko lang po ano po ang mga training or tesda courses na dapat kong pasukin para po ngayon palang magkaron na ako ng knowledge sa pag troubleshoot ng ibat ibang machines na ginagamit sa barko. maraming salamat po
@LeckyKenTv
@LeckyKenTv Жыл бұрын
Refrigeration and Aircondition (RAC). Pag may budget ka. Marine refrigiration. 10k atah yun sa MERALCO😊
@wickedxe
@wickedxe 2 жыл бұрын
My guess would be a dirty condenser or a failed condenser fan
@rightconditions2789
@rightconditions2789 2 жыл бұрын
Yes, that was what I was thinking. It is very uncommon to have "air" or noncondensables in the system even when the sysntoms are similar. The refrigeration troubleshooting was not that good. I had never seen low side pressures and high side pressures unless it is a restriction. (Constructive critc here)
@derrickenbuenosaires
@derrickenbuenosaires 2 жыл бұрын
​@@rightconditions2789 the containers run at a really low pressure using 134A. Depending on your temp conditions they can range from 5 to down below 0 psi which would be vacuum. (more prone to air infiltration) His high side was definitely high for 134A. That's like a 65+ C / 150+ F coil. Discharge temps directly from the compressor would be way higher. Usually a high discharge would reflect back onto the suction slightly but he was in range on the suction pressure. My first thought would be to look at the coil too but we didn't get to see it. The fan is easy to test since it cycles on and off due to pressure control
@natureraj928
@natureraj928 2 жыл бұрын
Sir I want job has a assistant electrician in your under
@romiecer19bhongbhong96
@romiecer19bhongbhong96 9 ай бұрын
Pwede ba tgalog sir😅
Was ist im Eis versteckt? 🧊 Coole Winter-Gadgets von Amazon
00:37
SMOL German
Рет қаралды 34 МЛН
When You Get Ran Over By A Car...
00:15
Jojo Sim
Рет қаралды 17 МЛН
I Can't Believe We Did This...
00:38
Stokes Twins
Рет қаралды 80 МЛН
3M❤️ #thankyou #shorts
00:16
ウエスP -Mr Uekusa- Wes-P
Рет қаралды 13 МЛН
Burnt VFD, Why?????
8:45
leckyjake
Рет қаралды 21 М.
ETO REEFER CONTAINER TROUBLESHOOTING | SHIP’s ELECTRICIAN
7:43
REFRIGERATION PUMP DOWN AND HOW TO CHANGEOVER COMPRESSOR?
9:27
How does the air conditioner work?
7:26
Mscope
Рет қаралды 2,8 МЛН
40' High Cube Thermo King Refrigerator Container - How it Works
15:10
The Container Guy
Рет қаралды 39 М.
REFRIGERATION SYSTEM | Toping's World
6:01
Toping's World
Рет қаралды 26 М.
Was ist im Eis versteckt? 🧊 Coole Winter-Gadgets von Amazon
00:37
SMOL German
Рет қаралды 34 МЛН