@xnavyro
@xnavyro 2 жыл бұрын
One important thing to note is that the difference between the upper bench value & the regulator pressure determines your seat load on an air-to-close valve assembly, so the limit on the upper bench value should be +0/-(the tolerance value) ensuring there will be adequate Force to seat the plug. Also the regulator should be set with a -0/+(tolerance value) again to assure necessary seat load. To increase seat load, decrease the bench set or increase the regulator pressure setting; conversely, to lower seat load, increase the bench set or decrease the regulator value, or a combination of both.
@jimdiggins101
@jimdiggins101 2 жыл бұрын
Yes, seat loading is what makes the bench set so critical. On a direct acting actuator the seat loading is supplied by the amount of pressure available over the upper bench. For a class III and IV shutoff there must be 40lbs of available force for every inch of circumference. That force requirement is divided by the effective diaphragm area to come up with a pressure value. This value represents the amount of air pressure in excess of the upper bench value you need to achieve the total force requirement.
@xnavyro
@xnavyro 2 жыл бұрын
@@jimdiggins101 i agree, good video & great to talk to someone who understands actuators, valves & specifications. Look forward to seeing more of your videos? I wrote a lessonplan on AOVs for I&C that I’d like to send you, just provide me an email address and I’ll be happy to send it your way, Ok?
@jimdiggins101
@jimdiggins101 2 жыл бұрын
Sounds good. My contact info is available on my KZfaq page.
@sam.castaneda22
@sam.castaneda22 4 ай бұрын
Need some videos of repairs out in the field
@AashishBharat
@AashishBharat 3 жыл бұрын
Good video. Once everything is coupled and let's say the valve starts closing at 8 psi instead of 6 psi (stem friction etc). Do you readjust the spring tension while coupled to match the bench set stated on the nameplate or do you leave it as is?
@jimdiggins101
@jimdiggins101 3 жыл бұрын
Leave it as is. The bench set represents the preloading of the spring and ensures proper operation and adequate seat loading. You can, however, repeat the bench set test with the valve coupled to the actuator for the purpose of gathering friction data. This data can be used to drive preventative maintenance and diagnose the root cause of loop oscillations. A good valve positioner unit will perform this test automatically.
@sam.castaneda22
@sam.castaneda22 4 ай бұрын
Im having issues with a valve currently for leaking by. Hard to find the right kits or someone is not getting the right info for them. Is there a website or something to find the right kits? Based in west texas.
@jimdiggins101
@jimdiggins101 4 ай бұрын
Emerson owns Fisher Valves. From the Emerson website you can find the local business partner as well as drawings.
@michaelmorgan9536
@michaelmorgan9536 Жыл бұрын
How tight should the jams be tightened. What are the risks of not setting the jam nuts?
@jimdiggins101
@jimdiggins101 Жыл бұрын
The jams keep the connection block in place In most applications, the feedback arm connects to the block. In some cases, even a slight rotation can create feedback error or loss of position indication.
@epb0394
@epb0394 2 жыл бұрын
Jim, is there any way to contact you outside of KZfaq? I have an issue with one of our diaphragm actuators I would like to discuss with you.
@jimdiggins101
@jimdiggins101 2 жыл бұрын
My contact info is listed on my KZfaq home page.
@epb0394
@epb0394 2 жыл бұрын
@@jimdiggins101 Thanks. I just sent you an email.
@ducbinhhdu
@ducbinhhdu 2 жыл бұрын
Thanks bro!
@jimdiggins101
@jimdiggins101 2 жыл бұрын
You betcha!
@vinaysane5435
@vinaysane5435 6 ай бұрын
Like Video.
Reverse Action Control Valve Bench Set Test
4:01
Jim Diggins
Рет қаралды 18 М.
Кадр сыртындағы қызықтар | Келінжан
00:16
مسبح السرير #قصير
00:19
سكتشات وحركات
Рет қаралды 2,1 МЛН
白天使选错惹黑天使生气。#天使 #小丑女
00:31
天使夫妇
Рет қаралды 15 МЛН
How Is Bench Set Adjusted?
3:05
Fisher Valves & Instruments
Рет қаралды 55 М.
Inside a Central Heating Zone Valve Actuator
12:53
John Ward
Рет қаралды 167 М.
how to assembly actuator for forbes marshall
12:12
Leesonmech Engineering
Рет қаралды 1,2 М.
Mounting an Emerson Fisher 667i Actuator
4:11
Spartan Controls
Рет қаралды 34 М.
Ajuste de banco (Bench Set) valvulas de control
3:53
CADISAC
Рет қаралды 14 М.
6 Steps How To Adjust Bench Set on Control Valve
8:04
Technical Knowledge Channel
Рет қаралды 6 М.
Кадр сыртындағы қызықтар | Келінжан
00:16