EEVblog 1500 - Automatic Transfer Switch REVERSE ENGINEERED

  Рет қаралды 85,693

EEVblog

EEVblog

Күн бұрын

Automatic AC transfer switches are pretty cool devices. A look at what they do, a practical demo, teardown, and then reverse engineering to explain how it does it with a direct one-to-one schematic-physical mapping.
Bonus look at how my automated home battery backup system will work.
00:00 - Automatic AC Transfer switch
02:05 - How I'm powering my home fridges from a battery
06:30 - What does an AC Transfer switch do?
09:27 - Huh? How do you do the automated battery power backup?
12:36 - Practical AC Transfer switch demo
15:57 - Teardown
18:44 - Reverse Engineering Schematic
25:46 - BONUS 2nd design teardown!
Forum: www.eevblog.com/forum/blog/ee...
Support the EEVblog on:
Patreon: / eevblog
Odysee: odysee.com/@eevblog:7
Web Site: www.eevblog.com
EEVblog2: / eevblog2
EEVdiscover: / eevdiscover
AliExpress Affiliate: s.click.aliexpress.com/e/c2LRpe8g
Buy anything through that link and Dave gets a commission at no cost to you.
Donate With Bitcoin & Other Crypto Currencies!
www.eevblog.com/crypto-currency/
T-Shirts: teespring.com/stores/eevblog
#ElectronicsCreators #Teardown #reverseengineering

Пікірлер: 359
@SeanBZA
@SeanBZA Жыл бұрын
Bars on top are arc catch plates, you will have a big arc on breaking under current, and closing on current. Contacts are large to handle the inrush current, which can be 2kA, and the flexible copper braid has to be rated to handle this inrush current. Common parts in all AC contactors and all AC breakers, to quench the arc and connect the moving contact to the terminal. Ideally you want a separate delay relay in the feed to the incoming supply, so that power has to be applied for 30 seconds before it is reconnected, so that all the transients on the line can die down, and also the massive inrush load can subside from all the other loads being turned on cold.
@EEVblog
@EEVblog Жыл бұрын
Yes, some of these transfer switches have 30sec delay built in.
@stevewalston7089
@stevewalston7089 Жыл бұрын
I used to work for a company that manufactured very large backup power units (our largest at the time was 1 MVA). The contacts and bus bars used were massive as were the arc extinguishing plates. Any large switchgear manufacturers will have similar (Siemens, Square-D, Eaton, etc.) devices. I could not find any other test videos of contacts up close but this give the general idea of just how violent it can be for large gear and high currents: kzfaq.info/get/bejne/erlgabRn1LO2iY0.html
@DjResR
@DjResR Жыл бұрын
@Pharisee Spotter Even 500W load can cause arc over if switched between different potentials without the arc chambers, ask how I know this._
@mikefochtman7164
@mikefochtman7164 Жыл бұрын
Agree with all you've said. Came here to comment those plates are 'arc chutes' to quench the opening arc. Now, when you get into entire switchgear being transferred, you even get into 'load-shedding'. Some rotary loads with high moments of inertia have to be stripped before allowing second power source to close in (otherwise the sudden reenergizing of those loads will create massive torque transients). 'Fast transfer', vs. 'slow transfer' versus 'dead transfer'. With BIG loads, it's a lot of careful study.
@MCBatty80
@MCBatty80 Жыл бұрын
I agree, you can see the gaps also in the plastic cover on the back right of the DaveCAD segment.
@Smidge204
@Smidge204 Жыл бұрын
When you get into larger transfer switches they of course get a lot more sophisticated. Automatic delays to ensure the grid is actually stable before switching over, voltage/frequency checks, and feedback to modulate the generator speed to match phases and frequency before switching.
@brad885
@brad885 Жыл бұрын
Right. Scada tech here. Grid size and it involves multiple switches, load switching, and feedback from the ECC before it is allowed to click back on.
@jayjay6804
@jayjay6804 Жыл бұрын
That would be a concern of mine. Voltage sag with a battery source could produce a rapid on off condition as would an overloaded generator. There should be a delay circuit on the line in if used in this configuration.
@EEVblog
@EEVblog Жыл бұрын
Yes, more complex models have a 30sec delay and brown out detection etc.
@Rx7man
@Rx7man Жыл бұрын
I was thinking that's really missing on here, when the power here comes back on it's often very dirty and often has to "try" more than once before it's reliable
@PraxZimmerman
@PraxZimmerman Жыл бұрын
None of the 2,000A switches I work on ever bother with generator synchronization. They just do a 1s break before make. If the load is critical, you slap a UPS on it.
@mattmoreira210
@mattmoreira210 Жыл бұрын
Let's take a moment to appreciate how strong those solenoids are. Incredible!
@aliveli8650
@aliveli8650 Жыл бұрын
Hi Dave, Imagine this scenario: Your freezers are powered by battery in the night and the battery is empty. Then the ATS switches to mains. However, since the battery is not under load anymore, the voltage increases back again. Then the ATS switches back to battery. Then because of not having enough power, ATS switches back to mains...then loop.... I am sure that your BMS is smart enough to cut entire battery output off (high Z) after the battery depleted and not enable it again until it is charged. But anyway keep this problem in mind ;) Cheers.
@FrankGennari
@FrankGennari Жыл бұрын
My guess is that the switching time varies depending on where in the sine wave the switch happens. If it's near a zero crossing it will take longer because the solenoids may not pull the rod until closer to peak power. So you would get some ~10ms (half cycle) variation in the timing.
@frogz
@frogz Жыл бұрын
congratz on 1500 videos(+ or - a few not in the main series) dave! i've found a few pieces of industrial kit like this before, some beefy switches and motor contactors from some pumps, amazingly simple and yet surprisingly complex for what they do
@PaulSteMarie
@PaulSteMarie Жыл бұрын
Cute little baby transfer switch.😁 The data center at the bank I used to work for was more the size of a refrigerator, and had a huge lever, not a tiny knob. Those microswitches are effectively the negative feedback side of the circuit. Typical sort of a limit switch setup: apply power until you're in the right position and then stop.
@MadeinSA658
@MadeinSA658 Жыл бұрын
LOL as I sit and watch this video in South Africa 🇿🇦, we currently have whats called "load shedding" stage 4. Power off for 2 hours at a time, 3 times a day minimum. In stark contrast to experiencing only a couple of hours in a lifetime in Sydney.🙈 Great video as always! Thanks Dave!
@marcfruchtman9473
@marcfruchtman9473 Жыл бұрын
This was a really great tear down and explanation. I really like the simplicity of the design for this device. Thank you for making this video.
@Da9eI
@Da9eI Жыл бұрын
I have a similar setup at home to use battery power when electricity is expensive. I have found that switching while a fridge is running and the voltages are too far out of phase between inverter and grid the fridge kompressors will stop abruptly. I am aware double positive (or negative) ac pulse essentially is DC and acts as a brake on induction motors when using vfd's, I suspect my fridge compressor have a very low rotating mass as well and out of phase power upsets it. However measuring voltages with a multimeter and transfering between sorces when both are near 0 volts betwheen line 1's keeps the fridge happy and it continoues to run. Inverter fridges dont care, but I recommend testing this in your setup.
@gd2329j
@gd2329j Жыл бұрын
Heads up with refrigeration ! Watch out for locked rotors on switchover . A off delay of ten minutes is advised .
@Rekless70
@Rekless70 2 ай бұрын
Great content. I have learned so much, Bob is now my uncle.
@AJMansfield1
@AJMansfield1 Жыл бұрын
18:30 Those metal fins are there to help quench any arc that's formed as the contacts separate, I'd imagine -- same as for the fins you find in protective circuit breakers.
@johndelano279
@johndelano279 Жыл бұрын
The quality of the first unit you tore down is much better than that of the second with the green selector switch. The one with the green switch is a "stacked" design used to add more switch sets. I have some of these I used for my generator transfer switch with 4 contacts (I only needed 3) and the outer most switch fails spectacularly when there is a surge. I already lost 2 during power outages. Always the outer most switch assembly. It seems since these are stacked and each one "plugs" into the adjacent switch plastic lever pivot, the strength holding the contacts closed gets weaker the more poles are added due to poor tolerances! The original one you tore down is not stacked and should not suffer from this defect.
@TheRich464
@TheRich464 Жыл бұрын
Happy 1500!
@dtvking
@dtvking 4 ай бұрын
Brilliant tear down and explanation. Thanks
@WizardTim
@WizardTim Жыл бұрын
I wonder if the plastic in those transfer switches meets the necessary flammability requirements? I have a feeling it doesn't. But I at least like how the slightly crooked "QC PASS 08" stamp in the manual is actually just an image in the pdf :) The metal sheets at 18:38 look like arc splitters to cool and extinguish any arcs from breaking loads (particularly inductive ones), not sure if I'd trust them at 400 VAC 63 A but probably good enough at 240 V 10 A. However one thing I don't understand is that both units have speed holes on the front plastic cover presumably either to ensure the impending explosion is vented forwards towards the user to cause maximum damage or maybe they had issues with the low quality contacts overheating and their solution was just to add ventilation slots, but seems like it's just begging for contamination issues. I also assume this change over switch and battery inverter will not be considered a 'fixed installation'?
@EEVblog
@EEVblog Жыл бұрын
It's not a "fixed installation", as it's not physically permanenty connected at all.
@Ressy66
@Ressy66 Жыл бұрын
I'm betting not, I do not see any real separation between Gen and Out, I'd expect that thing to be a fire hazard, and your screwed as insurance wont pay out. I do not see any Aussie Compliance "RCM" markings, just the fakish "C"hina "E"lectrics mark (note the non existence of the spacing between C and E which exists on the real European thing)
@jaro6985
@jaro6985 Жыл бұрын
yeah, not that I care (because we do it at work all the time), but I'm certain this wouldn't pass AUS electrical code. I doubt DIN rail is certified for use anywhere inside the home. Sadly, as its really useful stuff.. wish my breaker panel was all DIN.
@0xbenedikt
@0xbenedikt Жыл бұрын
@@Ressy66 Agreed, except for the whole "China Electrics" thing, which isn't real (and wouldn't make sense anyhow). CE markings are self-issued so if it's on there, the manufacturer/importer claims it meets the required standards.
@fromtheflightdeck252
@fromtheflightdeck252 Жыл бұрын
Good informative video. I bought similar from same manufacturer and now I learned how to wire it up thanks. $25 here in Thailand off Lazada. Same project, running guest house off solar and a Bluetti AC200MAX with mains grid as backup.
@McTroyd
@McTroyd Жыл бұрын
Simplicity is the ultimate sophistication! Even with a 5,000-cycle rating, that thing will probably last forever.
@KeritechElectronics
@KeritechElectronics Жыл бұрын
I like this switch, it's so simple, not over-engineered and should be reliable. Automatic transfer switches make sense 1) when you have two separate utility connections (primary and backup), or 2) you've got a generator that can be remotely started. I wonder if the relay uses its auxiliary contacts for controlling the generator startup; it would make sense since as the mains dies and the relay turns off, the aux contact gets toggled, starts the generator, and when the generator is up and running and supplying power, the solenoid in the ATS gets energized and the changeover happens. Fridges won't care, but for any servers, computers etc. get yourself a UPS that can keep them powered through the changeover process. You got a lot of distortion in your mains. All that SMPS rubbish - forget about clear radio transmissions... It's sad.
@mysterious_czrs
@mysterious_czrs Жыл бұрын
U are on like every electronics video comment section LOOL
@KeritechElectronics
@KeritechElectronics Жыл бұрын
@@mysterious_czrs well, kinda. Some science stuff too.
@berndeckenfels
@berndeckenfels Жыл бұрын
It does not look safe or useable for your main household - not to mention code
@holysirsalad
@holysirsalad Жыл бұрын
It indeed seems that the relay contacts on the primary (A) side are intended for a generator start signal - C and NO at the top of the device. The manual for these can be found if you look up Geya Electrical, model W2R
@OlympusHeavyCavalry
@OlympusHeavyCavalry Жыл бұрын
I've seen these used within the water industry along with other sine wave normalizers, delays, soft starts - soft stops, VFD switches and current shunts for very high voltage electric motors.
@gnif
@gnif Жыл бұрын
I'm actually doing the same thing but my continual load is a rack of servers so the changeover needs to be smooth and phase synced. Instead of a timer though and a commercial battery/inverter, I picked up an old 3000VA UPS and modified it so it can't charge the batteries attached to it. I gutted the batteries from it and connected a 14.4KWh LiFePO4 array to it's "extended runtime" input and built a little circuit with a STM32F103C8T6 at it's heart that measures current consumption, battery charge state, among other things. When the charge state is high and solar input is high it disconnects the UPS from grid power making use of it's internal switchover function. The batteries are just connected as per normal to a MPPT via a BMS to charge from solar. Because I am using a high grade UPS that is designed for 100% duty, it has the added benefit of locking it's AC output phase with the grid phase, and when it takes over the phase is in sync with the grid, and when it goes back to mains power again it takes about 3 seconds while it re-syncs it's output to match the grid phase before switching back over.
@brendan3603
@brendan3603 Жыл бұрын
Transfer switches are an extremely important part of backup generators
@HAM-CU7BE
@HAM-CU7BE 2 ай бұрын
I have Tested with Timer, and it works fantastic. The Timer just have to be connected to the green poles AR and AN or BR and N. And it work with the Time you want. :)
@maxxxhEdroom
@maxxxhEdroom 19 күн бұрын
“It is rated for 5000 cycles” *click *click *click *click* Maybe 4000 by the end of the video. Thanks for another informative and useful video!
@isojed
@isojed Жыл бұрын
These ATS are not for rotating devices as one cannot ensure that both power supplies are (were) in-phase. The worse case scenario is opposed phase which would surely stall an rotating device.
@animarkzero
@animarkzero Жыл бұрын
...it would destroy the Device😱 it would.....Explode
@annaplojharova1400
@annaplojharova1400 Жыл бұрын
For some smaller appliance it may get away with it...
@mikefochtman7164
@mikefochtman7164 Жыл бұрын
Small motors will survive. But really large equipment, you're absolutely right. Our system would check and if drifted out of phase, strip the motors before closing the alternate source feeder.
@fransdebruijn6763
@fransdebruijn6763 Жыл бұрын
@@animarkzero it would trip any upstream breakers. The battery inverter would likely cop it too. The mechanical delay should be sufficient at 180° however the waveform is going to look like the McDonald's M. It will cause massive inrush currents on any connected transformers and the harmonic will take several cycles to dissapate.
@rogergreenwood1536
@rogergreenwood1536 Жыл бұрын
These are very simple, very crude, but also very effective for small single phase loads. As pointed out by many others, the strengthening bars are intended to break/split/dissipate the arc when switching loads. For small single phase it obviously works, I doubt they would come anywhere near the rating claimed (50kA) or the full load for the no. of operations claimed. As also pointed out by others, professional units will have multiple time delays built in to prevent hunting in the event of voltage fluctuations, and also run-on timers for generators. But they also cost accordingly :-) Great video, thanks.
@linuxguy1199
@linuxguy1199 Жыл бұрын
Thats a pretty nifty setup, my grid here in the rural US sucks. During the winter we routinely loose power for week's/month's. Ive been wanting to build a system to automatically switch my homelab server rack (with UPS) to a generator.
@davidmcdonald3314
@davidmcdonald3314 Жыл бұрын
Just a thought Dave... Do you really want to switch your fridges (essentially single phase motors under load) from one source to another almost instantaneously??? Will the solar inverter power source be synchronised to mains frequency? If so, no wukkas But I'd think you might get into difficult territory if the two sources are not in synch When I was responsible for a data centre, we were always in synch (courtesy of a UPS on the output side of the transfer switch) for most things, but we still enforced a minute or two gap between power sources (so we didn't damage the HVAC)
@CliveTrezona
@CliveTrezona Жыл бұрын
I have one of these, they work great. Dave, whats involved with replacing the contactor side of it with solid state switching? Is it worth it?
@jimthvac100
@jimthvac100 2 ай бұрын
Very good useful video I just ordered one of these (Jotta Brand same thing off Ebay) Thank you! cant beat the price of these $35.26. Of course I am sure they are not UL rated, but reviews are all good.
@alklapaxida850
@alklapaxida850 Жыл бұрын
brilliantly simple ..
@AndyMcBlane
@AndyMcBlane Жыл бұрын
Hi Dave, very interesting. I wanted to use this but was concerned about safety, so built a servo to a manual transfer switch (video on channel!). But this looks great - and now I can see inside I'm happy to spend the $50. Cheers!
@AndyMcBlane
@AndyMcBlane Жыл бұрын
Ah yes, I want to be able to switch grid off programmatically... maybe a smart plug will do.
@EEVblog
@EEVblog Жыл бұрын
There are also much more expensive versions that I'm sure are certified to meet various local standards etc.
@AndyMcBlane
@AndyMcBlane Жыл бұрын
@@EEVblog Yep. I am doing this to save money not spend it :D
@animarkzero
@animarkzero Жыл бұрын
@@AndyMcBlane These are chinesium devices and at the pricepoint I would not take the current rating seriously! When you pay up to 10x as much for brand ATS at the same current rating(63A) you know something is fishy.
@AndyMcBlane
@AndyMcBlane Жыл бұрын
@@animarkzero only switching
@aususer415
@aususer415 Жыл бұрын
Thanks Dave! Just about to put one in my caravan to switch between mains (aka “shore”) power, and my inverter.. allows me to use my microwave and coffee machine (and any other 240vac) when travelling
@ME1D
@ME1D Жыл бұрын
How’s there people commented 8 hours ago while the video just been uploaded 20 seconds ago? 😅 Btw, this subject is literally important for any beginner electrical engineer, thanks in advance ❤️
@EEVblog
@EEVblog Жыл бұрын
Patreon supporters got to see it last night.
@frogz
@frogz Жыл бұрын
@@EEVblog dont lie to us! we know you opened a time portal in your yard and have been allowing patreons to play with the course of history! if this wasnt true, WHY IS MY COPY OF BERNSTEIN BEARS CALLED BEARSTAIN BEARS?????
@imark7777777
@imark7777777 Жыл бұрын
Time travelers of course. Now you really don't know what the answer is do you? Oh and I'm trying to find an IBM 5100 so I can fix the future and my time machine.
@imark7777777
@imark7777777 Жыл бұрын
@@frogz LOL
@ME1D
@ME1D Жыл бұрын
@@imark7777777 🙈😂
@jtveg
@jtveg Жыл бұрын
Thanks for sharing. 😉👌🏻
@AJMansfield1
@AJMansfield1 Жыл бұрын
Does that circuit have sufficient isolation between the grid and backup sides? The distance between the relay's pads is awfully small. With the right fault condition it seems like there would be a possibility of back-feeding power into the grid through the control circuitry (creating a hazard for linemen etc.).
@stevenbliss989
@stevenbliss989 Жыл бұрын
Yep I have a couple, different style and brand, but the same! thanks for the reversEE :). I do wish they x'fered faster though. But considerring the likely mismatch in phase at the time, then maybe you do need some 5ms+ delay. Any thoughts on that?
@slypig24
@slypig24 Жыл бұрын
I found that very interesting, to see how it works. Hope to see the whole system working soon. Will you have an under voltage output alarm, from your battery inverter?
@pjtruslow
@pjtruslow Жыл бұрын
I'm guessing the solenoids are so powerful that it can't run them continuously, so the microswitch turns off the solenoid as soon as it has done its job.
@DanielFSmith
@DanielFSmith Жыл бұрын
My house was prone to brownouts. If the power went out then the generator kicked on, and the switch transferred power: great. But if the powercame back in brownout mode, the generator would turn off, and leave the main solenoid on brownout power (i.e., not enough to switch back). Yup: melted solenoid!
@zaprodk
@zaprodk Жыл бұрын
18:34, those "bars" are not for strenghtening, they are spark arrestors.
@DrFiero
@DrFiero Жыл бұрын
Used to work on megawatt backup gen's - when the xfer switch on those kick over, you better be paying attention and plug your ears! Some sounded like a car crash!
@imark7777777
@imark7777777 Жыл бұрын
Yeah a lot bigger possibility for arcing, it's gotta be quick and fast.
@DrFiero
@DrFiero Жыл бұрын
Not to mention the size of the contacts. Was like a bunch of small frying pans all going BANG at the same time - at about 200mph. Hahaha
@nigozeroichi2501
@nigozeroichi2501 Жыл бұрын
Big Clive took a similar unit to bits a while back, but it used a motor, much smother but the transfer time is longer
@joe72205
@joe72205 Жыл бұрын
The “strengthening bars” are probably arc extinguishers
@EEVblog
@EEVblog Жыл бұрын
Yes, that seems to be what they do.
@genome692002
@genome692002 9 ай бұрын
is there a posibility that one of those switches gets stuck and you have 2 supply connected at the same time to the load... or is there something that prevents that...
@Max-kc2rc
@Max-kc2rc Жыл бұрын
Nice Video!!! Some risk could be when your battery inverter (connected to your A input) goes into a "brownout. ---> (i) Battery "empty" - turns off the power - (ii) Relay swaps to B (grid in your case) - Battery has no load at that time (iii) battery and inveter recovers - since there is no load - (iv) relay swaps back to source A ---> we are back at the start.
@thisnthat3530
@thisnthat3530 Жыл бұрын
Did I miss them or does that unit lack the required compliance markings for use in Australia?
@azpcox
@azpcox Жыл бұрын
Was very impressed with the portrait DaveCAD. Indeed rare and it looks like you have plenty of portrait cycles left based on the thickness of the DaveCAD Pad. DCP
@derofromdown-under2832
@derofromdown-under2832 Жыл бұрын
The first box internally it looks real cheap-arsed. The way the solenoids are positioned seem a tad wrong. The later switch box looks a bit better... 10/10 for the vid
@jimmybrad156
@jimmybrad156 Жыл бұрын
Has anyone looked into what a typical blackout looks like over ~1 second? I'm wondering if there's normally behaviour that would make a 240v relay across it "chatter". Do UPS's normally have a minimum time to run off battery before re-connecting to the mains once it's back up?
@Satoshi_1980
@Satoshi_1980 8 ай бұрын
Can i use this to my PC and not restart when main power is off, it is about switching speed from main power to backup power?
@UpLateGeek
@UpLateGeek Жыл бұрын
Our CBD office has independent connections to two separate grids because it's in a bank building, which is great because it basically meant we didn't have to have a UPS for our data centre. It's practically impossible for both grids to be down at the same time, because that would mean the head offices for most of the major banks and financial institutions in the country would go down. Well, one day there was a major power outage in the CBD, it took out one of our grid feeds, but when our automatic transfer switch switched over, it decided half way through that it was too much work and exploded, taking out the second power feed and our entire office and data centre. Everyone was basically left standing around twiddling their thumbs for a couple of hours until they could get an electrician to bypass the transfer switch and reconnect the one good power feed. Unfortunately the disruption probably cost the business about half a million Aussie dollary doos. But that's not the end of the story. Do you think this convinced them to install a UPS? Nope! Instead they decided that in the event of losing one grid feed, they'd have an enormous generator on the back of a truck, which someone would drive into the CBD and park on the street outside the loading dock. Then they'd roll out a huge cable up the ramp, through the loading dock, and into a panel to feed another transfer switch that they could use to power up the missing feed. Yep, a flawless plan. Thankfully we haven't yet needed to implement it, since the grids have been stable since then. Unfortunately the UPS in our head office wasn't as reliable ... but that's a story for another time.
@sennheiser1986
@sennheiser1986 Жыл бұрын
Can't you switch off the power to the batteries, based on the current provided by the solar panels?
@buckybuckyking
@buckybuckyking Жыл бұрын
Hi Dave, Great video but i was wondering how this arrangement is grounded? Thanks
@ulwur
@ulwur Жыл бұрын
One of the first bigclive videos i watched was about a transfer switch like this.
@larrydillon4841
@larrydillon4841 Жыл бұрын
I'd be curious if you could just run the fridges when the sun is shining and turn them off at night. It would depend on now well insulated they are and thermal mass. Not sure this would work for a fridge, but I think it would with a deep freezer.
@fr6885
@fr6885 Жыл бұрын
The vents on the stationary contacts are for arc flash suppression.
@steve479976
@steve479976 11 ай бұрын
Bridge rectifiers and associated circuitry are possibly only protected by the 100A main fuse. The control circuits need their own low amp protection device.
@kheavmady8780
@kheavmady8780 Жыл бұрын
Doest it turn off the light during switching?
@bascomnextion5639
@bascomnextion5639 Жыл бұрын
Your going to need to think about RCD protection when running off the battery.
@eliotmansfield
@eliotmansfield Жыл бұрын
Came here for that comment - lots of people seem to ignore rcd protection of downstream devices after genny or battery system
@kissingfrogs
@kissingfrogs Жыл бұрын
Nice video. Didn't quite follow the trigger setup. Curious if a rigol 1054Z is capable,
@EEVblog
@EEVblog Жыл бұрын
The Keysight doesn't have a fancy dropout trigger, so I just bodged the pulse trigger low trigger.
@danielreid6823
@danielreid6823 10 ай бұрын
Would love to see Dave explaine the PEN and MEN connections, when using a transfer switch. There's a good article from WorkSafe QLD on the dangers of switching Neutral
@rickarmstrong4704
@rickarmstrong4704 Жыл бұрын
Hi Dave ! futher to the SeanBZA comment below, there is the problem also fixed by the timer, the compressors having a power cut and reapplication with the compressor still under head pressure usually that time is around five or ten minutes otherwise the compressor just keeps cycling till that pressure reduces hard on the overload and the motor, Cheers!!! Rick Armstrong from Canada
@stazeII
@stazeII Жыл бұрын
Hopefully you can tell your battery inverter to not re-energize until it reaches a certain SoC, otherwise this might chatter as the inverter energizes, then quickly browns out. Nicer ones have time delays to prevent that (wait 30+ seconds to make sure grid is actually back on), and also zero crossing switching. Funny timing on this video. My campus is doing ATS testing today and switching to “island mode” (local power generation) off the grid and making sure everything works.
@thinklist
@thinklist Жыл бұрын
Just make sure you're installing to AS3000 and AS3010. You might also want to use a PE cell instead of your manual switch.
@djnmv
@djnmv Жыл бұрын
I wonder if you could use a UPS to do this exact same setup, depending if the UPS had certain features that you could utilise? I'm thinking something like a self test feature that you can set on a time schedule, and that will allow the battery to drain down almost completely, then switch back to AC power afterwards. So you could make it at a certain time every day, it disconnects AC power and uses it's batteries until their depleted, or until a certain timeout is reached perhaps.
@CraigThomas1983
@CraigThomas1983 Жыл бұрын
Could you replace the timer with a external adjustable photocell?
@camius1
@camius1 Жыл бұрын
SCRs and IGBTs are awesome
@bartowl
@bartowl Жыл бұрын
You might consider using one of the easun/powland cheap Chinese inverters with automatic bypass and built in charger when you have direct 24/48v battery connection. 5kW are around $400 and unlike typical ATS when battery is low it switches like ups without circuit disruption to grid power. Your ats is here really very fast! You may also configure safe buffer, to reserve a bit capacity should grid fail. those inverters are really good and configurable as for that price.
@tmd63
@tmd63 Жыл бұрын
So how do you monitor and direct the solar power into your EV or Battery bank? My Solar has an inverter that shuts down if the mains is shutdown, but If I run a backup battery off the grid, it cannot detect if the solar is providing the power or the grid. Do you have a method for detecting when the solar is providing the power so that all the power generated is used by the battery charging. It would help to charge local batteries during the day when I am at work and then allow me to high voltage charge an EV during the night.
@chiliphil64
@chiliphil64 Жыл бұрын
Would it be possible to have the unit control an EV charger to change over to the cheep Tarif.
@pepethefrog7193
@pepethefrog7193 Жыл бұрын
Here in europe where power is expensive i do measure actual power into/from the grid and switch extra consumers according to solar surplus. Measuring is done with 3-phase shelly-3em over WiFi, switching load is done with sonoff-basic over WiFi.
@sebmadgwick2789
@sebmadgwick2789 Жыл бұрын
Seems like a design flaw to me. Shouldn't the tamper switches be arranged so that the solenoid circuit is broken at the end of the throw, not the beginning? Breaking the circuit at the beginning of the throw could result in oscillations if the initial force of the solenoid is not sufficient - perhaps due to increased friction after years of use and accumulation of dirt.
@NeverTalkToCops1
@NeverTalkToCops1 Жыл бұрын
Daiyve, Daiyve, Daiyve, this lash up may be frowned upon by Aussie government. Your refrigerators must never disconnect from the grid, even for 20 milliseconds. It's all on page 278 of the International Internet of Things Treaty, IIoTT.
@SylwerDragon
@SylwerDragon Жыл бұрын
Nice video Dave. Those U shaped metal lets call them bars are actually for ark reduction or reduction of the arc that will start ot end in that place..so they are there only for that.. btw. I created similar circuit.. you need two main relays and then one smaller relay... and also two extra contacts..exactly how it is in that package.. I will add one small thing..they should add small capacitors parallel with coils to reduce voltage spike and it would good design
@johndododoe1411
@johndododoe1411 Жыл бұрын
Your optimal cost timer should be set to a random time offset from exact hours, to avoid grid impact from other people running similar clocks. This smoothes out the load discontinuity for the grid backbone system, giving them time to startup power sources.
@mikefochtman7164
@mikefochtman7164 Жыл бұрын
In theory, maybe. But those refrigerators are intermittent loads anyway. They cycle on/off somewhat randomly throughout the day. If you have a load big enough to seriously impact the grid, the grid operator already knows about you and your staff have discussed such issues with them.
@Islandwaterjet
@Islandwaterjet Жыл бұрын
Why are coils DC ?
@MisterTalkingMachine
@MisterTalkingMachine Жыл бұрын
Barring aside the manual switching, would it be feasible to use a DPDT contactor with the coil wired to your priority source to do a job like this?
@mattmoreira210
@mattmoreira210 Жыл бұрын
Absolutely! You do lose the ability of controlling it manually, but there should not be any major harm in doing so.
@EEVblog
@EEVblog Жыл бұрын
I think that would work.
@SeanBZA
@SeanBZA Жыл бұрын
Disadvantage of around 20VA constant power consumption, as opposed to the small relay only being around 1VA coil current.
@jimmybrad156
@jimmybrad156 Жыл бұрын
Element14 part 2787143 seems to switch pretty fast. I'm thinking of using it for an always-on inverter ready to replace mains 240v in a blackout for PC & display & external hard drive. I'm considering options to include a timer so that when the mains does come back up, it waits a few minutes before switching back over to it.
@sandy1653
@sandy1653 Жыл бұрын
In my experience anyway, those contacts on the Source B/Generator are used to trigger the generator's start sequence.
@Herr_Bone
@Herr_Bone Жыл бұрын
Clive, I think you know that all this can be done much easier with some available home automation thingies. They measure the consumption and control without steps the output of your batteries as well as the charging. But well, your oldschool solution might not be too bad.
@pocoapoco2
@pocoapoco2 Жыл бұрын
Is there some hysteresis to the micro switches that control the main switch solenoids, or are they relying on momentum to complete the switch change?
@eDoc2020
@eDoc2020 Жыл бұрын
Dave drew the diagram backwards "for simplicity" but they're actually normally closed switches mounted on the destination side. The power isn't cut until the movement is complete.
@slypig24
@slypig24 Жыл бұрын
For your 3 fridges, I have seen someone make a 3 relay box, to prevent all 3 loads starting at the same time. It's a very low chance of this happening, but with thermostats opening & closing, it can happen.
@Philip8888888
@Philip8888888 Жыл бұрын
How does that work?
@slypig24
@slypig24 Жыл бұрын
They used an arduino for sequential control of power outlets, to avoid heavy start up loads.
@Philip8888888
@Philip8888888 Жыл бұрын
@@slypig24 but the compressor will turn off after a time, so how do they detect when it would turn on again and prevent 2 from turning on at the same time?
@pfeerick
@pfeerick Жыл бұрын
@@Philip8888888 it is most likely just for the initial switch on, when all three compressors would kick in at the same instant... I. E. Turn them on in sequence with a 10 second delay or such, and then whatever happens happens. Yes, you could get fancy with power and even temperature monitoring, but more risk of something failing then.
@dh2032
@dh2032 Жыл бұрын
it doesn't seem to be very concerned about run with no working earth connect at any of the contacts?
@fransdebruijn6763
@fransdebruijn6763 Жыл бұрын
You don't need an earth for this switch. It has no metal that can become live and zap you.
@joshuaanhalt3180
@joshuaanhalt3180 Жыл бұрын
Do your refrigerator/freezers have protection against short cycling? I don't know if the 20-50ms glitch is enough to get the compressor motors to lock up.
@EEVblog
@EEVblog Жыл бұрын
No idea, but it's rare this would actually switch.
@DLSDKING
@DLSDKING Жыл бұрын
@@EEVblog If the battery pack starts to fail or underperform, You will observe shortcycling of the automatic changeover switch when the compressors are called in by refridgerator control system which will kill the refridgerators for sure (got to know about that after watching several videos from ​ @HVACR VIDEOS channel). My suggestion is to use a delay line(delay setting of 5 minutes) between the battery pack and the change over switch for additional protection,
@theoneandonlyyoko
@theoneandonlyyoko Жыл бұрын
dont know if I got lost in the sauce, but I assume the battery its only being charged when solar is working? from the diagram it seems that battery is charged from mains (which it may be) but I assume there is some configuration to make work only on sunlight time, right?
@theoneandonlyyoko
@theoneandonlyyoko Жыл бұрын
nevermind, I continued washing the video and he immediately explained the timer switch, lol
@tomhillpot1473
@tomhillpot1473 Жыл бұрын
Have you considered all fridges starting at the same time?
@ianbottom7396
@ianbottom7396 Жыл бұрын
Be worth using an ON DELAY circuit on the output, domestic refrigeration equipment usually needs the pressure generated by the compressor to have equalised off cycle for the compressor to start equalised and therefore unloaded, short breaks in supply don’t allow this to happen and the compressor will generally trip on over current and it’s not a good thing to do frequently. What you described as strengthening bars on the first unit are most likely arc chutes to break the arc current during switching
@t4796
@t4796 4 ай бұрын
What happens if the control wires aren't connected. Can it still be used manually as a mechanical switch? It's too late to get my head around the circuit.
@Roacheification
@Roacheification 3 ай бұрын
Yes
@jdennee
@jdennee Жыл бұрын
Forgot the most important rule of the EEVBlog! Don't turn it on take it APAAAT!
@jlucasound
@jlucasound Жыл бұрын
I know you are running freezers through this but I would think the delay of it switching over wouldn't even cause your digital clocks to go to "12:00" and blink. (If you were using it as a backup for grid failure). Hey! Try that, Dave! "Plug" a digital clock into it and see if the toggle action is fast enough to keep it going. I would try that before seeing if it crashes a desktop computer (or not)! 😱
@EEVblog
@EEVblog Жыл бұрын
Our fridges don't have clocks.
@2loco
@2loco Жыл бұрын
18:27 - these are for absorbing and quenching the arc produced when making and breaking the current.
@strehlow
@strehlow Жыл бұрын
Heat pumps generally can't immediately restart. If there's a power failure, it should stay off for a minute or two before applying power again. They have a soft-start accumulator tank which fills when first turned on. Applying power while that is full may stall the compressor. I suspect inverter-driven units take care of this electronically, but I'm not certain.
@Alexander-qz6px
@Alexander-qz6px Жыл бұрын
Is the degeneration of the 3000$+ battery and the inverter running every night, or 24/7 actually, (caps?) actually worth the lower energy intake?
@jimmybrad156
@jimmybrad156 Жыл бұрын
lithium titanites seem to've come down in price. claim to do something like 20k+ cycles.
@PETMK
@PETMK Жыл бұрын
Looks like Dave is going to build overcomplicated nuclear power station from it :D What I didn't understand are these points: 1. How can help these mechanical contacts help with glitches caused by another mechanical contacts of built-in relays ofthe battery? 2. Why the fridge must be powered permanently? We have two days with eight hours power outages here per year due to maintenance and it is not absolutely problem - the freezer goes from -18 degC to -12 degC at this time. I don't understand why can 5 to 10 minutes cause a probelm, it would be below scale of the thermosat hysteresis. If the internal temperature rises so fast it is not problem for electrician but for the fire department. 3. The fridge is a compressor. The compressor is a motor with hard start. It means 10 to 15 times normal current. It is stupid idea to connect three of them in paralell and conect at the same moment, even if it runs form a convertor. This will activate the overcurrent protection. And my recommendations: 1. If there is no extra reason, NEVER switch the neutral line in mains circuits. Really, NEVER. And if you need it be sure the neutral is connected the first and disconnected the last. I know you are not familiar wit it but imagine a board powered by +24V and +5V with cutted off the ground. This is similar. 2. This switch is nice to be a bistable relay on the output. The sensing inputs A and B are good to realize separate control circuits with delay etc. in that. 3. If it is possible to connect N without switching the N contact can switch on and off charging of the battery (the charge time will be shotrer by few minutes but you won't need the extra relay for it). 4. If the invertor has power indication contact it should be used to control this crazy invention. 5. You can also use current sensing relays and switch the output when there is no power consummed from the battery ouput. In this case you have no inrush current...
@tzisorey
@tzisorey Жыл бұрын
"I'm not going to take it apart further "
@Sven_Dongle
@Sven_Dongle Жыл бұрын
Wouldnt the solenoids have opposite polarity?
@zxspectum
@zxspectum Жыл бұрын
Hi regarding the fridge circuit, will you pull a new circuit through your house just for this setup? As I could imagine the complexity of putting this in line to an existing circuit may cause confusion down the track. How will you identify this in the mains board and on your GPO outlets. There could be other devices plugged into that circuit in the future or more GPO added? (PS I am not a qualified sparky so take my comment with a pinch of salt)
@EEVblog
@EEVblog Жыл бұрын
Yes, new cables pulled, totally independent to the other fixed house wiring.
@TheSpud2233
@TheSpud2233 Жыл бұрын
@@EEVblog If you have a dedicated circuit for you backup supply you should consider using red socket outlets, these are the industry standard for dedicated UPS / Emergency circuits.
@InssiAjaton
@InssiAjaton Жыл бұрын
At about 18:45, the two perforated bars may be arc extinguishing means? You see such on higher voltage and power switches or any breakers capable for over 10 kA breaking. The idea is to let the arc extend by its own magnetic effekt and push it to multiple gaps that also cool the arc.
@cOsMiCTr
@cOsMiCTr Жыл бұрын
I have a question, my ATS switches nicely but sometimes my house fuses flip during the transfer switching from battery to main. What could be the reason?
@greyMDA
@greyMDA 2 ай бұрын
have you found the issue?
@cOsMiCTr
@cOsMiCTr 2 ай бұрын
Kind of. We have fuse type B installed. I will change it to fuse type C which is made to hold for initial load longer. I presume that should do the trick…
@greyMDA
@greyMDA 2 ай бұрын
@@cOsMiCTr thanks for getting back to me so promptly. hope you solve this.
@TheEmbeddedHobbyist
@TheEmbeddedHobbyist Жыл бұрын
The problem with AC is if you want zero switching time, you need to phase lock the supply's. Or convert both to DC then invert back to AC the same way a lot of high power UPS do.
Automatic generator changeover switch (with schematic).
27:06
bigclivedotcom
Рет қаралды 847 М.
Me: Don't cross there's cars coming
00:16
LOL
Рет қаралды 14 МЛН
孩子多的烦恼?#火影忍者 #家庭 #佐助
00:31
火影忍者一家
Рет қаралды 48 МЛН
1❤️
00:17
Nonomen ノノメン
Рет қаралды 13 МЛН
I wish I could change THIS fast! 🤣
00:33
America's Got Talent
Рет қаралды 118 МЛН
Generator ATS (Automatic Transfer Switch)
11:25
Gavin’s Garage
Рет қаралды 15 М.
EEVblog 1473 - How Your LCR Meter Works
19:43
EEVblog
Рет қаралды 73 М.
EEVblog 1622 - The BIG BEGINNER MISTAKE with Multimeters
12:25
GEYA W2R Automatic Transfer Switch
1:52
GEYA Electric
Рет қаралды 16 М.
EEVblog 1482 - Mains Capacitor Zener Regulator Circuit
18:52
Automatic transfer switch setup and quick look at 3 types
11:24
DIY Tech & Repairs
Рет қаралды 366 М.
Simple maintenance. #leddisplay #ledscreen #ledwall #ledmodule #ledinstallation
0:19
LED Screen Factory-EagerLED
Рет қаралды 26 МЛН
Игровой Комп с Авито за 4500р
1:00
ЖЕЛЕЗНЫЙ КОРОЛЬ
Рет қаралды 2 МЛН
Blue Mobile 📲 Best For Long Audio Call 📞 💙
0:41
Tech Official
Рет қаралды 1 МЛН
Hisense Official Flagship Store Hisense is the champion What is going on?
0:11
Special Effects Funny 44
Рет қаралды 2,8 МЛН
⚡️Супер БЫСТРАЯ Зарядка | Проверка
1:00