Gas Pipe Bonding Requirements, NEC 2020 - [250.4(A)(4)], (12min:16sec)

  Рет қаралды 48,754

MikeHoltNEC

MikeHoltNEC

2 жыл бұрын

What are the NEC requirements for bonding of gas piping systems? What other than NEC requirements are involved in bonding metal gas piping? Metal gas piping must be bonded to the circuit equipment grounding conductor if there likely to become energized. However, many AHJ’s throughout the country enforce the metal gas piping to be bonded with an additional bonding jumper in accordance with the National Fuel Gas Code.
For over 40 years, Mike Holt Enterprises has been providing quality electrical code training to help electrical professionals learn the code, prepare for exams, and improve their electrical knowledge. Visit www.MikeHolt.com for exam preparation tips and training, instructor and curriculum support, continuing education options, free videos and graphics, and so much more.

Пікірлер: 141
@mcarroll598
@mcarroll598 Жыл бұрын
I passed my Electrical Contractor Master License today in Ohio first try, It was really tough but your videos help A LOT! Thanks!
@garbo8962
@garbo8962 3 жыл бұрын
At an IAEI class about 6 years ago while stuck in the 2008 NEC was Told that to bond any CSST you have to go by what the manufacturer says. The NEC should have one spelled out method. I got called out to a friend who had a fire place feed by CSST mounted one inch above carpets. I was worried about people running a vacuum cleaner damaging this thin tubing over time. Anyway it took me halve a dozen phone calls to get an answer. Thanks for another great vid.
@mmareviewer.2372
@mmareviewer.2372 2 жыл бұрын
This guy is always passionate. Mike Holt working hard for us from his space!
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
I love you guys and want to do all I can to make your lives just a little easier and the world a little safer.
@eixr
@eixr Жыл бұрын
This is a great application for the Mechanical Contractor to use the Inter systems bonding connection we provide at the GEC.
@filomartinez1513
@filomartinez1513 Ай бұрын
Gracias Mike you are the men
@mr.g937
@mr.g937 2 жыл бұрын
I say just bond no matter what. Need to be prepared for future installation changes where the electrician is no longer there.
@kylem6532
@kylem6532 5 ай бұрын
Wow! What an awesome presentation and just the great info I needed. Thank you so much Mike and take care!
@MikeHoltNEC
@MikeHoltNEC 5 ай бұрын
You are most welcome.
@garbo8962
@garbo8962 2 жыл бұрын
I think that every duct should be bonded. Years ago where the duct work coming out the top of a gas furnace had a rubber noise isolation section. An old clothe covered by 14/2 NM cable was ran at a 90 degree angle from duct by touching it. After more then 20 years it rubbed thru insulation almost causing a fire. About 6 years ago we were told at a CEU class that every manufacturer of CSST has their own method of bonding. You would think they could get just 1 style if a clamp or fitting to bond all CSST.
@MR-nl8xr
@MR-nl8xr Жыл бұрын
Makes no sense NOT to bond the duct, yet having to make sure that there is EGC going to the Furnace for the sake of the Furnace Enclosure.
@norme7102
@norme7102 2 жыл бұрын
The reasoning behind the CSST bonding is to mitigate damage from lightning, the yellow coated stuff being very susceptible. I have seen two instances in the last three years where lighting blew a hole in unbonded CSST, one of which ignited the gas (luckily inside the fireplace). Our AHJ’s require gas line bonding as part of the electrical inspection which I fully support.
@davenag957
@davenag957 2 жыл бұрын
Just how is this accomplished, what type of ground clamp or special fitting? Is there a csst fitting with a bonding lug or do you just use a water pipe clamp that probably isn't approved for that use. No criticism, just trying to learn.
@jmac213stuff
@jmac213stuff 2 жыл бұрын
@@davenag957 This information is readily available from the UPC and Manufactures of CSST, but I don't recall it be some kind of special bonding clamp. The same clamps that I use for bonding ground rods, I use to bond CSST, gas pipes and water pipes.
@doublezmtnman
@doublezmtnman 2 жыл бұрын
If you bond your main black iron gas line do you still have to bond each branch csst line and if so which fittings the one at the appliance or the one coming off main line
@affinity3281
@affinity3281 2 жыл бұрын
@@doublezmtnman Only at point of entry into the building.
@wg1408
@wg1408 2 жыл бұрын
@@affinity3281 then do you just leave your regular pipe bondings at the water heater gas line and water pipe connected? Curious if that stays bonded and then you also bond/ground at gas meter just before the csst gets installed? That's where I'm running a 25' section of csst in my basement area just inside from the gas meter. I know how to attach the 6awg wire to the csst fitting but then where should I run that wire. Won't make it to my panel box (75ft) plus I'm not messing with that. Why can't I run her out and clamp to gas meter or drive a grounding rod 8' and attach.
@user-sn8xs5wh2d
@user-sn8xs5wh2d 9 ай бұрын
Great video Mike! Thanks for the education.
@MikeHoltNEC
@MikeHoltNEC 9 ай бұрын
You are welcome
@davenag957
@davenag957 2 жыл бұрын
Another code Quagmire. Sounds like a mechanical contractor problem to me. It's their piping that they have been paid to install per the mechanical code. It's not my job to tell a sprinkler contractor how to install their work, or a gas fitter how to install their work, just like it's not their job to tell me how to install my electrical work. Unless it's specifically pointed out in the division 16 specifications on the approved plan, or the AHJ tells me specifically that I need to do it, I'm not going to be concerned with it. I've survived this trade for 40 years and I think common sense is the way to go in this case.
@jmac213stuff
@jmac213stuff 2 жыл бұрын
yes and no. Although the Mechanical Contractors needs to bond CSST during installation. Its the Electrical Contractor's responsibility to bond the system equipment, gas pipes, water pipes, ufers, ground rods, metal structure etc. in the first place. This include a hot water/cold water bonding jumper at the water heater, and to the house side of the gas meter (no jumper on the service side)
@SvenK-CAD
@SvenK-CAD 2 жыл бұрын
Thank you for sharing.
@scottmorse4225
@scottmorse4225 2 жыл бұрын
Something you may want to consider is when the gas piping is threaded onto the gas fitting of the appliance a non-conductive paste or approved tape is used on the threads. This isolates the piping from the appliance. So it is not bonded through the circuit grounding conductor but it's also not likely to become energized. Lol Just don't mount it to the building steel that is likely to become energized. This is always a fun point of contention with the inspectors. I just thought you'd want to think about it first before it comes up in a discussion.
@FrodoOne1
@FrodoOne1 2 жыл бұрын
I strongly doubt that any tape or "non conductive paste" would "insulate" any metal-to-metal threaded connection. (They merely fill the interstices of the joint to prevent leakage but metal-to metal contact WILL still exist.) Have you ever tested any such connections for "open circuit" - or even "high resistance""
@scottmorse4225
@scottmorse4225 2 жыл бұрын
@@FrodoOne1 yes I have tested it many years ago and found some of the times no continuity between the piping and the gas valve.
@CraziFuzzy
@CraziFuzzy 2 жыл бұрын
@@scottmorse4225 If there was so much tape in the fitting to act as an insulator - that fitting was not put together correctly.
@qomco
@qomco 2 жыл бұрын
@@CraziFuzzy I dont know abt that, im required to do tape and thread dope on gas appliances, so the thread connections will barely have any metal to metal surfaces. The inside of the pipe is not where the metal contact is
@doc13067
@doc13067 2 жыл бұрын
The paste actually moves out of the threads. It is the tapering of the threads that actually seals the connection. Just use some thread sealer tighten the gas fittings and then disconnect it and you’ll see that all the threads that made contact have nothing on them. Thread sealer will certainly not isolate different sections of pipe.
@holtrussell
@holtrussell 2 жыл бұрын
Thanks Mike!
@stepanvinnikov6024
@stepanvinnikov6024 2 жыл бұрын
King of the nec
@qomco
@qomco 2 жыл бұрын
Residential hvac apprentice, thank you sir! I just wish field wiring were as clean as your diagram
@commercialsparky7776
@commercialsparky7776 2 жыл бұрын
Great video, I watched it multiple times! I’m excited to start getting more books and information. Thank you for igniting a passion now to get my license. I pushed it off for awhile but I’m more determined now then ever and I have you to thank for that. Thank you for another amazing video Mr. Holt.
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
You are most welecome, God Bless
@tristatehomesllc599
@tristatehomesllc599 2 жыл бұрын
I would save more time bonding 100 gas lines before trying to explain this to our building inspectors. They're clueless.
@garbo8962
@garbo8962 2 жыл бұрын
When I piped in my gas furnance instuctions stated to use a dielectric union on the 3/4" gas pipe. I went to the local plumbing supply house and they did not have any in stock so I reused the original union. I did install 12/2 MC cable to replace 40 year old type AC cable. Often wondered if we should install a bonding jumper between the cold & hot water copper lines at gas water heaters due to they have insolated fittings even though they would bond together at downstream metalic faucets.
@jmac213stuff
@jmac213stuff 2 жыл бұрын
I answered this in the questions above.
@MR-nl8xr
@MR-nl8xr Жыл бұрын
This is the same gawd damn problem that happens with so many other trades & installations of different kinds that it's overwhelming. If it's not the AHJ saying to do what the CODE says, it's the CODE saying to do what the OEM says, and if it's not the OEM saying to do what the Professional CONTRACTOR/TECHNICIAN says, it's the Professional CONTRACTOR/TECHNICIAN saying to do what the AHJ says; and around and around we go. I honestly see how we've suited ourselves into making sure everything is done by robots.
@Bigmal23652
@Bigmal23652 3 ай бұрын
Great video. I’ve always said it made zero sense to bond a gas pipe. I always figured it’ll go off like a bomb if it’s ever made to do , what it’s made to do.
@anthonyelectric6045
@anthonyelectric6045 2 жыл бұрын
A lot of miss information out there. Equipment Grounding Conductor. Done👍
@joelsnyder350
@joelsnyder350 2 жыл бұрын
Out city wants us to always bond the gas ..but especially if that flexible gas piping is used. I assume that is the CSST. Also, we don't bond underground propane tanks without a dielectric fitting. To prevent providing an alternate path to ground. They seem "UNlikely" to become energized if you ask me.
@joelsnyder350
@joelsnyder350 2 жыл бұрын
#vermont, #Burlington
@vince6829
@vince6829 18 күн бұрын
Thanks for sharing your knowledge.
@MikeHoltNEC
@MikeHoltNEC 13 күн бұрын
It's my honor.
@Chris_In_Texas
@Chris_In_Texas 2 жыл бұрын
Sounds like a government agency can't make up its own mind. When both NFPA 70 and NFPA 54 are contradicting each other. Then the AHJ's read it one way or another and can't agree either. In my own house, my gas line isn't bonded, but its more than 75' away from the panel. That being said technically or at least electrically, the gas line is bonded, indirectly, but the water line bond, through the water heater. There would be a need for bonding as many high efficiency gas water heaters or power vented water heaters do have electrical connections as well. However in our area they are just run romex into the box with no metal EMT or MC cables. But based off the info you presented the grounding conductor is normally screwed to the metal of the fixture directly. I know many of the cities require bonding around us, due to lightning strikes we get and set houses on fire. You get the flash over arc in the attic where the gas line and metal duct work from the chimney run through the attic as most fire places have gas run to them, even though there are no electrical igniters run to them. Great video Mike! 👍
@Apollo1965
@Apollo1965 7 ай бұрын
Bonding for static and dielectric charges
@joeybellosisfishinchronicl5250
@joeybellosisfishinchronicl5250 9 ай бұрын
I just had Rockville City in Maryland with same issue had me bond
@norrisharrington3332
@norrisharrington3332 2 жыл бұрын
Sued if you do and sued if you don't. Lawyers hard at work.
@Tmfndlb
@Tmfndlb 2 жыл бұрын
Gas ranges require 120 volt, and are typically connected to the same gas piping system as the water heater. So, the gas system must always be bonded. Also, what they mean by in accordance with NEC would mean NEC rules still apply to the bonding conductor. For instance, it should be secured or stapled, etc..
@CraziFuzzy
@CraziFuzzy 2 жыл бұрын
And that same gas appliance likely already bonds the EGC to the gas components in the appliance.
@Tmfndlb
@Tmfndlb 2 жыл бұрын
@@CraziFuzzy redundant grounding…
@Tmfndlb
@Tmfndlb 2 жыл бұрын
I feel like the purpose of this is an effective ground fault current path. If the gas pipe becomes energized, the current goes to ground, as it should. The breaker ideally trips as the amps increase to fault levels, instead of an an explosive gas contained in an energized pipe just sitting around, waiting to blow. If the appliance connected to the egc fails and the fault current somehow doesn’t trip the breaker, the gas line bond is like a fail safe. It’s pretty feasible too. I can’t count how many outlets I’ve seen with open grounds, especially in remodeled houses, where the contractor installs 3 prong outlets on a 2 wire system. I agree with Mike on most stuff, but this one I respectfully disagree with. Being an AHJ and master electrician myself, it’s our job to provide the practical safeguarding as mentioned in the NEC
@johny2903
@johny2903 Жыл бұрын
Confusing explanation.
@shshshs2
@shshshs2 2 жыл бұрын
Hey mike, I see that your newest products are going digital. Is there a option for people who probably want the Dvd version of it? I think there should be a option of someone who want the physical copy of it or digital.
@mathman0101
@mathman0101 2 жыл бұрын
They are as DVDs are becoming redundant. They have always had the digital copy that was the default.
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
DVDs will be available until January 2026; so no worries. Just aske for them, since digital is the default.
@johnbelt7676
@johnbelt7676 Жыл бұрын
If the water needed to be bonded then the presence of the gas water heater would require the gas to be bonded since the gas and water are bonded within the water heater. Then would you say the gas is bonded via the water pipe? Don’t thing so
@lanceramsdell4921
@lanceramsdell4921 Жыл бұрын
Any good plumber knows that when you connect dissimilar metals like black gas piping to copper gas piping a dialectic union is recommended. The dialectic union breaks the electrical bond, so theoretically the pipe on one side of the dialectic union could become energized and not trip the breaker. Also, if the pipe becomes energized by lightning it could explode at the dialectic union. Thoughts?.
@johnkulpowich5260
@johnkulpowich5260 7 ай бұрын
Your the best
@MikeHoltNEC
@MikeHoltNEC 7 ай бұрын
LOl, thanks
@wg1408
@wg1408 2 жыл бұрын
My iron pipe gas line is bonded at the hot water heater and furnace. But I'm adding 25ft of CSST in my basement area close to the gas meter. Curious if I should run the bonding clamp 6awg wire from csst brass fitting to the exterior of my house grounding point on outside of house where panel box runs to.
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
According to the National Fuel Gas Code, NFPA 54, section 7.12, you only need to bond CSST tubing if it's not of the 'arc-resistant jacket type.' See www.gastite.com/us/products/flashshield/flashshieldplus_csst/
@pauloconnell7668
@pauloconnell7668 2 жыл бұрын
Mike, do gas water heaters have electric pilots or electric spark etc to ignite the gas burner?
@FrodoOne1
@FrodoOne1 2 жыл бұрын
Some may but some may be via a "manually operated" piezo electric ignition. However, if a metal water pipe is "bonded" to the "Grounding Electrode" of a building and that water pipe (or any water pipe connected to that water pipe) is connected to a metal "water heater", any metal gas pipe connected to that metal water heater IS (automatically) BONDED to the Grounding electrode - by quite heavy "gauge" solid copper/steel/etc "Conductors". Any extra "bonding" is redundant!
@JohnQPublic345
@JohnQPublic345 Жыл бұрын
They use old fashioned thermocouples. High efficiency ones use intermittent spark ignition, as well as some tankkess
@mathman0101
@mathman0101 2 жыл бұрын
Yeah it’s a big head scratcher Mike damned if you do damned if you don’t. Here is where you have to go back to the issue of why you need to bond. Is that metal part likely to become conductive and create a hazard shock risk? Overbonding a metal part that does not need it can create shock risks of its own. Two tests here one is a functional one is the conductive part connected to the mass of the earth/ground (absent any connection to the electrical installation) If so you could look to bond. More effective is to test. The piping may go through voids, walls or floors where it joins to plastic piping that is non-conductive (or at least far less conductive) or is insulated on terms of a jacket or sheath on the pipe there would be no need to bond. Second to test You could do a continuity resistance test between a real ground (main ground terminal) and the metal part using long lead (null the leads) if that resistance reading is greater than the differential resistance (using ohms law at a given safe current say 5, 10 or even 30mA) at 120v less body resistance (assume 1000 ohms when wet but could be lower if a child is considered or different parts of body) the. if resistance of the metal part with respect to ground is greater than the differential in resistance at a safe level less body resistance then most likely no need to bond. You will need a proper continuity meter that can measure up to at least 1Mohms and not a multimeter. I know Uk electricians are given guidance by its standard setter to make such a determination. Of course one reading does not tell the whole picture as design considerations change as well as the electrical installation changes then that would also be need to be considered.
@jmac213stuff
@jmac213stuff 2 жыл бұрын
It just maybe a local code. Here is California Equipment bonding includes gas metal piping and water lines. This is in addition to 2 ground rods, or a ufers. There requirement is two or more grounding conductors. Also water lines at the water heater needs to have a jumper from hot to cold at the water heater piping. This is required by the electrical contractor when installing service panels here. What the diagram with the water heater is not showing, is the bonding connector back at the gas meter main already bonded, therefore no bonding required of the gas pipe at the gas water heater. The 2015 uniform plumbing code 1211.2 Bonding of CSST Gas Piping. CSST gas piping systems shall be bonded to the electrical service grounding electrode system. The bonding jumper shall connect to a metallic pipe or fitting between the point of delivery and the first downstream CSST fitting. The bonding jumper shall be not smaller than 6 AWG copper wire or equivalent. Gas piping systems that contain one or more segments of CSST shall be bonded in accordance with this section. [NFPA 54:7.13.2]. Its true, no mater what you do, you get sued. Thumbs up there.
@wg1408
@wg1408 2 жыл бұрын
My iron pipe gas line is bonded at the hot water heater and furnace. But I'm adding 25ft of CSST in my basement area close to the gas meter. Curious if I should run the bonding clamp 6awg wire from csst brass fitting to the exterior of my house grounding point on outside of house where panel box runs to.
@jmac213stuff
@jmac213stuff 2 жыл бұрын
@@wg1408 yes, CSST requires it own bonding according to the manufacture's recommendation. In my opinion, always bond to a point that is a permeant location, and that if bonding for other equipment can be removed without disturbing the other bonding clamp/connection then it's a good spot. good luck.
@carylamari6546
@carylamari6546 Ай бұрын
I think what they mean when they say in accordance to the NEC is, lets say you use drive a grounding electrode because it is closer and less work or the basement is completely finished and it is easier to install a ground rod and attach the gas pipe to that with a #6 conductor. In the NEC it says all grounding electrodes need to be connected together. So you need to find some way to create continuity between your new electrode to the building grounding electrode. I believe this is what they mean in the NFGC. IMO
@MikeHoltNEC
@MikeHoltNEC Ай бұрын
Let's start out with you are 100% wrong. Please watch the video again.
@carylamari6546
@carylamari6546 Ай бұрын
@@MikeHoltNEC Wouldn't be the first time I was wrong lol Would you mind telling me where though? I have always been under the impression all ground rods must be interconnected which is what I thought was meant by in accordance with the NEC. I am always wanting to learn?
@MikeHoltNEC
@MikeHoltNEC Ай бұрын
​@@carylamari6546 This video is about the 'bonding' of gas piping. So it's not related in any way to connecting the interior gas piping system to a ground rod.
@carylamari6546
@carylamari6546 Ай бұрын
@@MikeHoltNEC Well I agree and not to be obstinate because you are right however I have in the past installed a ground rod and interconnected it to the main ground rod outside with a #6 wire and then connected the interior Gas Piping system to the new ground rod. It actually was suggested by the home inspector because the Gas Pipeing system was on the other side of the house in a utility room and the rest of the basement was finished and not able to fish a wire to the panel. It was just one situation where I thought it satisfies the code and bonded the gas pipe to the main house ground system. Sometimes we have to think outside the box and only mentioned it as one possible justification for satisfying the statement in accordance with the NEC. But thanks for all you do, I respect your knowledge a great deal.
@MikeHoltNEC
@MikeHoltNEC Ай бұрын
@@carylamari6546 The National Electrical Code does not require the gas pipe system to be 'grounded' at all. So there is nothing for the electrican to do. So if they do nothing, they are in accordance with the NEC.
@billgatewood9578
@billgatewood9578 2 жыл бұрын
Code is a minimum, my county requires gas piping to be bonded.
@crosswire7777
@crosswire7777 2 жыл бұрын
But who's responsibility is that? The mechanical guys or you the electrician? Who's liable for the spark that ignites the flames?
@JohnQPublic345
@JohnQPublic345 Жыл бұрын
Technically then, shouldn't the short (2 or 3 foot) section of csst between the appliance gas shut off and furnace or water heater be bonded? If yes, I've never seen it done
@a-ron9884
@a-ron9884 Жыл бұрын
Yes
@RobertSmith-lw2bx
@RobertSmith-lw2bx 2 жыл бұрын
Mike I think the Florida Building Mechanical Code reads close to the same way as what you stated from NEC 54
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
I had Mario check this out and you are 100% correct!
@RobertSmith-lw2bx
@RobertSmith-lw2bx 2 жыл бұрын
@@MikeHoltNEC thanks. Just passing along information for the cause.
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
@@RobertSmith-lw2bx And it is 'appreciated!'
@user-sj5fo3yn1g
@user-sj5fo3yn1g 4 ай бұрын
Gas or no, wouldn’t the water heater still need power? For the igniter. It is still bonded to ground.
@MikeHoltNEC
@MikeHoltNEC 4 ай бұрын
A gas water heater does not have any electrical wiring. The electricity for igniter circuit is by a thermocouple.
@bobsbarnworkshop
@bobsbarnworkshop 5 ай бұрын
It is my understanding that according to code CSST gas pipe needs a #6 ground conductor connected to the pipe connector or iron pipe at the input of the gas service to the building. In case of lightning strikes!? I am running csst to a ceiling furnace in my workshop that has 120v to it so it would be bonded by that circuit, so the whole thing seems contradictory!
@bobsbarnworkshop
@bobsbarnworkshop 5 ай бұрын
Back to CSST bonding. Your point of view is just from an electricians point of view. But as a homeowner we have to comply with all building codes to get service to our homes! So even though the NEC doesn’t require any more bonding but the national fuel code does, then it has to be done!
@MikeHoltNEC
@MikeHoltNEC 5 ай бұрын
I is not in the NEC, so it does not have to be done per the NEC. It's a NFPA 54 mechanical code, not the NEC. So it's not required to be done per the NEC (we don't have any requirements). Who does NFPA 54 bonding is up to the building offical, not the electrical inspector.
@stephengirtz
@stephengirtz 2 жыл бұрын
Does the gas bonding help to reduce static electricity in the pipe?
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
I'm not aware that gas piping has static electricity on it, but bonding is not for that purpose.
@germanarellanocampos5119
@germanarellanocampos5119 2 жыл бұрын
It has always puzzled me that duct work is not considered a likely conductive surface ,eventhough mechanically controlled dampers are installed by a low voltage connection or in some bigger equipment 120v and low voltage wire sometimes is ran inside the duct to facilitate the installation of a thermostat. All this still doesn't make it under code a likely to become energized surface🤔. Mike what is your opinion?😳
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
I'm 'guessing' that most 'metal' duct is mechanically and electrically connected to the air-handler. The air handler is connected to the circuit equipment grounding conductor (bonded).
@networkingdude
@networkingdude Жыл бұрын
It's my understanding you bond gas piping for lightning protection irregardless of its likelihood to become energized.
@MikeHoltNEC
@MikeHoltNEC Жыл бұрын
Now you know better.
@bryanz5904
@bryanz5904 2 ай бұрын
I am thinking. In some situations, the popes could get static electricity they still need bonding?
@MikeHoltNEC
@MikeHoltNEC 2 ай бұрын
They are bonded by the circuit equipment grounding conductor, see 250.104(B).
@bryanz5904
@bryanz5904 2 ай бұрын
@@MikeHoltNEC Thanks Mike, bless. BTW, we do not use the LEB(Local Equipotential Bonding) and MEB (Main Equipotential Bonding) in USA right? I did not see them in the building, for European projects/IEC there is.
@user-dg5sz6yw3y
@user-dg5sz6yw3y 2 ай бұрын
What Mike Holt course is this video associated with?
@MikeHoltNEC
@MikeHoltNEC Ай бұрын
Grounding and Bonding, www.mikeholt.com/bonding-and-grounding.php
@REG3305
@REG3305 2 жыл бұрын
What's with the wobbling bulb in the background?
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
It's a floating light based on electromagnetism! I love it.
@REG3305
@REG3305 2 жыл бұрын
Very cool, sir!
@WardCo
@WardCo 2 жыл бұрын
What about a plug-connected wall furnace? As long as it is plugged in, great. But say it is unplugged. Pipe unlikely to become energized? I guess. But what if someone drives a nail through the drywall and hits both the NM cable and the gas pipe that are running in the same cavity to supply the unit?
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
Likely to become energized is that the gas pipe is connected to equipment that has power. If this is the case, then the gas is already bonded as explained in the video.
@NoneFB
@NoneFB 2 жыл бұрын
This needs to be redone.
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
Please give me 'specific' details on why you made this comment.
@nickdeliso7026
@nickdeliso7026 2 жыл бұрын
So, if my propane tank is connected to my range, and the range is plugged in, is it bonded?
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
Yep, per 250.104(B)(1).
@nickdeliso7026
@nickdeliso7026 2 жыл бұрын
@@MikeHoltNEC Not sure what your numbers been but I’m in Florida. Is that the code number
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
@@nickdeliso7026 This is the National Electrical Code reference to support my response.
@nickdeliso7026
@nickdeliso7026 2 жыл бұрын
@@MikeHoltNEC ok, thanks. I want to make sure I do all of this to code. You’ll be surprised how little some of these propane companies know about this.
@Vothtrucks
@Vothtrucks Жыл бұрын
I wish I had the time to wait through the blah-blah-bla to learn the answer to the question.How. about showing how it is done,, then why it is done, and so on. I want to do it right . I want to do it safely... but I need to do it today . Thanks
@cheddarcheese
@cheddarcheese Жыл бұрын
When are water pipes likely to become energized?
@AngelRomero955
@AngelRomero955 Жыл бұрын
When your don’t pay your water bill
@xnotyourhero
@xnotyourhero Жыл бұрын
What about the 2018 NEC Code? 400 AMP ground Service residential. Bonding requirements for Gas Lines. I’m reading bonding jumper not smaller than 6AWG. Does 400 amp require my bonding jumper to be larger for the gas line?
@FrodoOne1
@FrodoOne1 2 жыл бұрын
If a metal water pipe is "bonded" to the "Grounding Electrode" of a building and that water pipe (or any water pipe connected to that water pipe) is connected to a metal "water heater", any metal gas pipe connected to that metal water heater IS (automatically) BONDED to the Grounding electrode - by quite heavy "gauge" solid copper/steel/etc "Conductors". Any extra "bonding" is redundant!
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
You are correct.
@realestateservicessaleshea99
@realestateservicessaleshea99 2 жыл бұрын
Thanks 🤔?
@seantreakle1174
@seantreakle1174 2 жыл бұрын
Mike I just had a gas line become energized on a job I was doing and the gas pipe was not grounded thought about the whole situation and I think that it's wise that the gas company and the plumbers ground their gas lines on a separately derived grounding system foundation steel and ground rod separate from ours. Those gas lines should be separated from our electrical systems so there's no chance of those lines to be energized I believe that's the future.if we grounded them to our systems there's a chance our systems could become energized do too bad connections God bless you mike you guys are doing a great job I've learned so much from your show Sean Treakle Platteville Colorado with Brian electric
@SvenK-CAD
@SvenK-CAD 2 жыл бұрын
So I would guess best thing to do would be to install it then disconnect it after.
@carlosgraterol1098
@carlosgraterol1098 2 жыл бұрын
How calculated size grounded gas piping for switchgear 2500 amps?
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
Watch the video again, and check out 250.104(B).
@carlosgraterol1098
@carlosgraterol1098 2 жыл бұрын
@@MikeHoltNEC I have a doubt between 250.66 and 250.102 table
@philgonzales5310
@philgonzales5310 2 жыл бұрын
Why would you want the fault go to gas pipe. Had to do that in a house it sounded scary
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
That's a good point that I hadn't consider. That is one reason that the NEC does not have any bonding requirement for gas piping.
@georgeofthejungle2132
@georgeofthejungle2132 2 жыл бұрын
Authority having jurisdiction supercedes NEC...
@tristatehomesllc599
@tristatehomesllc599 2 жыл бұрын
No it doesn't. There are areas in the code where the NEC will differ to the AHJ on gray areas like "NM cable protection". But this doesn't mean they can just make up their own rules.
@georgeofthejungle2132
@georgeofthejungle2132 2 жыл бұрын
@@tristatehomesllc599 tell that to a county inspectors buddy. In my area the inspectors make up stuff all the time. Who you gonna argue with then? If they say jump. You better say how high, and really if you have any experience, you know this is fact.
@MikeHoltNEC
@MikeHoltNEC 2 жыл бұрын
I 'never' jumped with an inspector told me to do something that was not NEC required. Inspectors get their power from the uneducated electrician. Those that are educated stand up and help the inspector understand that they can't 'push' everybody around.
@georgeofthejungle2132
@georgeofthejungle2132 2 жыл бұрын
@@MikeHoltNEC I wish they were willing to learn in my area. Around here they act more like the police than inspectors always taking, the I'm above you stance never willing to even look at code book, half the time they just flex their government muscles. I appreciate your response and wish things were different in my area.
@majorintherepublick5862
@majorintherepublick5862 2 жыл бұрын
Gas fired furnace, gas must be bonded, gas fired stove
@ae7454
@ae7454 Жыл бұрын
too many code makers that dont work in the field
@MikeHoltNEC
@MikeHoltNEC Жыл бұрын
Why do you say that?
@BT_aka_PET_ROOSTER
@BT_aka_PET_ROOSTER 2 жыл бұрын
Shocker… mechanical guys trying to get out of work by throwing it at the electrical contractor.
@donwelke940
@donwelke940 Жыл бұрын
How stupid. Gas pipe comes out of the ground, a lot of ground. One giant grounding rod, in the ground. I get the service conductor ground/bond satisfies the requirement but how stupid. Now you have two grounds for the home/buildings. Want a third one out by the fire pit in the backyard? How stupid.
@SMShannon55
@SMShannon55 Жыл бұрын
Most underground gas line (both distribution and service) now is yellow cross linked polyethylene, not metal. It doesn’t switch to metal until it gets to the shutoff valve just before the regulator, thus, it’s not grounded by being a metal pipe in the ground.
Grounding, System and Equipment [250.4, 2020 NEC]
33:35
MikeHoltNEC
Рет қаралды 100 М.
3 Ways to Plumb for Gas with Master Plumber Eric Aune
10:50
Matt Risinger
Рет қаралды 24 М.
Haha😂 Power💪 #trending #funny #viral #shorts
00:18
Reaction Station TV
Рет қаралды 15 МЛН
OMG🤪 #tiktok #shorts #potapova_blog
00:50
Potapova_blog
Рет қаралды 17 МЛН
КАРМАНЧИК 2 СЕЗОН 7 СЕРИЯ ФИНАЛ
21:37
Inter Production
Рет қаралды 448 М.
MEU IRMÃO FICOU FAMOSO
00:52
Matheus Kriwat
Рет қаралды 40 МЛН
Conductor Insulation, NEC 2020 - [310.4], (19min:06sec)
19:06
MikeHoltNEC
Рет қаралды 17 М.
WARDFlex® Bonding Installation
6:04
Ward Manufacturing, LLC
Рет қаралды 9 М.
Grounding Versus Bonding (26min:26sec)
26:26
MikeHoltNEC
Рет қаралды 245 М.
Gas pipe sizing March 2019
8:30
Greg Taylor
Рет қаралды 116 М.
CSST Gas Piping Problems
2:05
Artisan Home Inspection Atlanta
Рет қаралды 157 М.
Haha😂 Power💪 #trending #funny #viral #shorts
00:18
Reaction Station TV
Рет қаралды 15 МЛН