In this video we cover Genteq Variable Speed Constant Airflow ECM Troubleshooting, including diagnostics and motor replacements. www.genteqmotors.com/Products... MCV18134E
Пікірлер: 40
@jonminnella41576 ай бұрын
Great technology however the price of the motor is a big problem
@PBS-nm1uu2 жыл бұрын
great presentation, thanks
@shifter82078 ай бұрын
I had a similar problem with a 2.3 and the Supco tradefox tester and the motor ran but not with harness. Not sure if some testers have different ways of testing the motor
@dadlaponizil36872 жыл бұрын
Hi and thanks for making this helpful tutorial. Where can I purchase a TechMate Pro and most importantly, where can I get documentation on the communication protocol--the command set-- it uses to talk to an ECM 3.0 module?
@Powellandturnerinc2 жыл бұрын
clear instructions nice
@mercedessalazar87699 ай бұрын
Hi, When you connect the TechMate Pro does the motor run in full speed?
@Garth2011 Жыл бұрын
Are the modules still failing way too early such as the power in rush component? Seems that those ECM's are well over priced for the benefits they give as just one service call eliminates any savings on power for life.
@minnesotasalamander5913 Жыл бұрын
Good video.
@vegaslowblower87813 жыл бұрын
We ordered a UZ-1 tester, seems dated. Is this tester better
@djmillerscountryshack10492 жыл бұрын
WHY are the control modules connected to the motor and not just in some easy access panel?
@dyorneyman341 Жыл бұрын
Im waiting gor you to say the voltage ouput in the communication cable...
@24rxman5 ай бұрын
Is techinspect from supplyhouse the same tool as tech mate pro?
@tlindsey97694 жыл бұрын
What options are available to replace the ECM with a standard motor, which is far less expensive and easier to replace. Thank you for any info.
@leslieabraham60743 жыл бұрын
You can attach a fan relay wire green and common to the 24 volt, and then your fan speed tap to normally open, and a wire from line 1, and then line 2 or common goes to common of the transformer.
@travelingkaspersworld40963 жыл бұрын
Perfect question.
@tomtom15412 жыл бұрын
@@leslieabraham6074 sure, but that means the fan will only work on 1 speed through that relay. The ECM motor can have up to 5 speeds depending on the model.
@leslieabraham60742 жыл бұрын
@@tomtom1541 yeah I think he's looking for a cheaper option. Like the PSC motor.
@tomtom15412 жыл бұрын
@@leslieabraham6074 well sure, but he's going to end up spending more money on electricity. So in the long run you haven't saved any money.
@mikhaelkozik6455 Жыл бұрын
Had problem with gentec ecm 3.0 motor yesterday. Got test tool(i think its called ecm pro from united). Had error on main logic board 68. Has to do with communication to motor. Used the tool and motor ran whole day till i ordered new board thinking motor was good. Replaced board and same error on new board and old motor. Replaced motor and it works fine. So control board on motor is bad, why did motor ran with the tool?
@Jason-wc3fh Жыл бұрын
So the tool is nothing more than sending 24vac to some specific terminals on the module of the motor that receives 24vac. That is all it does, nothing fancy, it's nothing but a set of jumpers. So most of the time when there's a fault, the 24vac does nothing to get the motor to run and then you're ok to change the module... In your case, you had a bit of an anomaly where the 24vac part of the module was fine, but there's also some communication wiring for controlling the speeds (which is usually through low voltage dc signals and what not)... That particular part of your module seems to be what failed. It's a little unusual, but that would be frustrating since the tool wouldn't recognize that issue. The tool is still far dumber and simplified for what the ecm control does. This is obvious by the fact you're not controlling any speeds of the blower except one fixed speed, yet the furnace board does ramp it up and down and has almost endless speeds.
@bryantaylor976011 ай бұрын
I’ve had this same issue twice recently. Each time motor ran with tester, ended up being faulty modules for specific taps for cooling.
@jeff37414 жыл бұрын
Thanks for this great video. Do I need to get an EON "drop-in replacement" motor programmed? If so, what does that involve?
@RegalRexnord4 жыл бұрын
Thank you for your message. Please give us a call and we can better assist: Customer Service: Induction motors Technical Support 800-672-6495 Electronically Commutated Motors (ECM) Technical Support: (866) 503-8566, Option 3 Hours: 8am - 5pm CST (Monday - Friday)
@jamesdaws34573 жыл бұрын
Hey Jeff. Did you get an answer to this question? Do you need to get an Eon drop in replacement motor programmed?
@jeff37413 жыл бұрын
@@jamesdaws3457 Regal Beloit was hesitant to even talk to a DIYer about it. Nor could I get a straight answer from any forum. I eventually bought a reconditioned one from www.ebay.com/usr/unitedhvacmotors. It works fine. I had to switch a couple wires in the harness since my motor turned the opposite way. But they had instructions for that.
@jamesdaws34573 жыл бұрын
@@jeff3741 Thanks Jeff. We're you able to get one with the same model number or did one work with a different model number? I suspect the myriad of model numbers and programming codes are mostly a smoke screen.
@jeff37413 жыл бұрын
@@jamesdaws3457 I contacted the seller and told them what I had. They sent me the one that worked. I think the programming is based on the multiple speeds the fan runs. The RPMs for slow and fast are different for the various models. I tried an unprogrammed motor first and it didn't work at all. That's when I went with the e-bay seller.
@bostonbruinsfanboy2 жыл бұрын
How to troubleshoot: buy our tool. Brilliant.
@techfive72022 жыл бұрын
Ive used this tool on a 16 pin trane variable speed. It ran great on full speed with the tool so I replaced the board and the motor still ran at like 100cfm lol.
@user-ty2uz4gb7v2 ай бұрын
My genteq x13 died after 8 years
@kevinmaxey55082 жыл бұрын
10, 15 yrs? Which is it? You can't remember 5 yrs? I question your honesty by that one ridiculous statement 🙄
@Garth2011 Жыл бұрын
Its a trend. I can understand how many people will quote $100 to $200 million or 3 to 5 years etc. Tells you very little except that they have no idea.
@heethen1128 ай бұрын
I’m old so you saying this is easier doesn’t work for me. I prefer to know exactly where when why how the problem is. Not offering a Corel module is dumb too. Now we have the even stupidest technology with Bluetooth will present many new problems.. too many to cover, but one I will say is, now people that shouldn’t be trying to fix things they don’t comprehend!! On top of it will take away from many aspects of technicians..??
@dwayneflint83326 ай бұрын
just a piss poor design.. designed to fail.. planned obsolescence.. should be a class action lawsuit.