Heat Detector Spacing Requirements

  Рет қаралды 7,924

Pyrotex Systems

Pyrotex Systems

Күн бұрын

NFPA 72 Chapter 17.6 Heat Sensing Fire detectors. This week we take a detailed look at code requirements for the mounting and spacing of spot type heat detectors.

Пікірлер: 9
@Kiranchnayak
@Kiranchnayak 2 жыл бұрын
Thank you for sharing.
@PyrotexSystems
@PyrotexSystems Жыл бұрын
Thanks for listening
@erickrodrigues4499
@erickrodrigues4499 4 ай бұрын
if I have a ceiling 90 by 90 with 28 feet high?
@mahademasudreon8403
@mahademasudreon8403 2 жыл бұрын
If the ceiling hight is continuously going down, will we multiple with different number? I mean in a shed the top of the shed is 25 feet hight but after 80 feet its turning out just 16 feet so is it necessary to reduce the multiple factor?
@cwolnicki
@cwolnicki 2 жыл бұрын
Good presentation! When you discuss spacing between detectors you show the clause that the minimum spacing between between detectors shall not be less than 0.4 x ceiling height. You then show a table which talks about multiples of listed ceiling heights and say that the value of 0.34 would not be ever applied. I think there are two different things, the first one being % of ceiling height the second being % of listed spacing. If you can kindly clarify.
@user-uv9zp1bh7t
@user-uv9zp1bh7t 2 жыл бұрын
I have a question, there is beam ceiling with height of 5.5 m and the beam depth is 1.1m and distance between beams 1.6 m (this case is not as mentioned in the code so how to locate heat detector? Sorry another question related to integration between smoke and heat detector in one beam ceiling as my case above?
@zohaibamjad4463
@zohaibamjad4463 2 жыл бұрын
if there is a hurdle so on what distance we should place our detector?
@hoseinparsa994
@hoseinparsa994 2 жыл бұрын
Great video so far. I have a question, There is a old fire alarm panel that installed at 1980, do you know what’s the code says about the heat detector type in the bathrooms at Motel? I would like to upgrade the system and the current heat detector is 195 inside the bathroom and then the sleeping area is 135 degree. Can I go with 135 instead of 195?
@PyrotexSystems
@PyrotexSystems Жыл бұрын
That should be determined based on ambient conditions in the space. I imagine a bathroom shouldn't get so hot that it needs a higher temp device, but you may want to double check that there isn't anything different happening in that room, like maybe a space heater that could cause false alarms. Some other possibilities is that maybe it was changed with the wrong part from a service tech that either didn't know better, or had the higher temp device with him. Again, the device installed should match whatever the ambient temperatures call for.
NFPA 72 Requirements for Duct Smoke Detectors
12:00
Pyrotex Systems
Рет қаралды 7 М.
Smoke Detector Spacing Requirements Part 2
22:16
Pyrotex Systems
Рет қаралды 6 М.
Мы никогда не были так напуганы!
00:15
Аришнев
Рет қаралды 6 МЛН
The child was abused by the clown#Short #Officer Rabbit #angel
00:55
兔子警官
Рет қаралды 24 МЛН
Class 4 | Heat Detector Spacing Requirements NFPA 72
8:56
Irfan CFPS
Рет қаралды 985
Smoke Detector Spacing Requirements Part 1
21:31
Pyrotex Systems
Рет қаралды 19 М.
Heat Detector
11:25
Fire & Safety with Salman
Рет қаралды 1,2 М.
How To Design A Fire Alarm System According To NFPA 72
34:38
Fire Pro
Рет қаралды 25 М.
Elevator Recall
23:05
Pyrotex Systems
Рет қаралды 3,5 М.
Intro to Fire Alarm IDC & SLC Circuits
26:00
Pyrotex Systems
Рет қаралды 5 М.
2020 09 03 13 28 Koffel Talk   NFPA 101   Life Safety Code®
1:30:39
APPALeadership
Рет қаралды 10 М.
Fire alarm design - Battery Calculation #Design #Batterycalculation
18:46
All about Fire Protection
Рет қаралды 10 М.
Inspecting And Testing Of Fire Alarm Systems NFPA 2005
26:50
SpenciTech
Рет қаралды 5 М.
РИСКОВЫЙ ШКОЛЬНИК На велосипеде #shorts
0:15
Леха МАК
Рет қаралды 5 МЛН
Unboxing MEGATRON 40th Anniversary Limited Edition Robot by Robosen
1:00