How HVAC Refrigerant Pressure Switches Work & Troubleshooting!

  Рет қаралды 165,464

AC Service Tech LLC

AC Service Tech LLC

Күн бұрын

Пікірлер: 116
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Support- www.patreon.com/acservicetech Tool List- www.amazon.com/shop/acservicetech For those that are looking for the tools used in the videos: (Linked Below) Appion Valve Core Removal Tool amzn.to/2uYr8WL UEI DL479 Multimeter with temp sensor amzn.to/2jtsUbJ Blue Vapor Yellow Jacket Gauge- amzn.to/2Ju7pan Red Liquid Yellow Jacket Gauge- amzn.to/2sSFmGH Quick Coupler for the Gauges- amzn.to/2sTk8Ze JB Test Gauge High Side- amzn.to/2ruQb0l JB Test Gauge Low Side- amzn.to/2qR0utM Manual Copper Tube Swage/Expander- amzn.to/2WRPa1M Uniweld Hydraulic Swaging Tool- amzn.to/2MlrI8m Uniweld Swage and Flare Kit- amzn.to/2T55jyn Ameriflame Oxy Acetylene Torch Setup- amzn.to/2SRm3JF #2 Tip for Oxy Acetylene Torch- amzn.to/2SPDaeD Cap-N-Hook Tip for Oxy Acetylene- amzn.to/2MbhpUk Air Acetylene Torch Setup- amzn.to/2aQalsb 15% Silver Brazing Rods- amzn.to/2gVLyLc Nitrogen Regulator- amzn.to/2bXdR5f Nitrogen Flow Meter- amzn.to/2brvoBg NitroVue Flow Reg- amzn.to/2MiulYv Ultrasonic Leak Detector- amzn.to/2Lw4Zpr UEI DL479 Multimeter with temp sensor amzn.to/2jtsUbJ Magnet Jumpers- amzn.to/2PyKPQZ Alligator Jumpers- amzn.to/2PxqJXn Fieldpiece ST4 Dual Temp Meter amzn.to/2wc1ME3 Fieldpiece Bead K Type Temp Sensor amzn.to/2DBwKfs Fieldpiece Wet Bulb Temp Sensor amzn.to/2RRI7Tw Fieldpiece TC24 Temp Clamp amzn.to/2qHLyjZ Yellow Jacket Refrigerant Gauge Set amzn.to/2aenwTq Refrigerant hoses with valves amzn.to/2aBumVI Yellow Jacket Gauge set & hoses amzn.to/2vLVkV9 Yellow Jacket 4 Port Manifold w Hoses amzn.to/2BkuGIq FieldpieceSMAN360 Digital Manifold Set amzn.to/2BdoaD4 FieldpieceSMAN460 Digital Manifold Set amzn.to/2nB4Fe6 Compact Ball Valve for Refrigerant Hose amzn.to/2KUisW8 QuickDisconnect 90 for refrigerant hose amzn.to/2MMtVcg JB 6 CFM Vacuum Pump amzn.to/2nqbvo8 Appion Blue 3/8" to 1/4" Vacuum Hose amzn.to/2uYlVyc Appion Red 3/8" to 1/4" Vacuum Hose amzn.to/2uYg6Ro Appion Valve Core Removal Tool amzn.to/2uYr8WL Yellow Jacket 1/4" by 1/4" hose amzn.to/2umtcod CPS Vacuum Micron Gauge amzn.to/2v1nM3O Supco Vacuum Micron Gauge amzn.to/2v1JRiA RectorSeal Bubble Gas Leak Detector amzn.to/2ckWACn UEI DL389 Multimeter amzn.to/2xAdaJf Other tool links can be found in the video description section. Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal- www.amazon.com/shop/acservicetech
@stuzman52
@stuzman52 5 жыл бұрын
Great demonstration of showing how to check pressure switches and its operation. The biggest tip was that not all pressure switches have schrader valves which is a great safety tip for beginner techs to remember.
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks a lot Stuzman!
@artics1031
@artics1031 5 жыл бұрын
Every time i click one of your videos, its straight forward and very informative for a tech or who is trying to be one. You are a good teacher you should be one if you are not.
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks a lot Artur, I am an HVACR teacher. I am also putting a refrigerant handling book together. I you would like to get on the book release list, just send me your email at info@acservicetech.com and thank you very much for your comment!
@Viper81766
@Viper81766 5 жыл бұрын
What Paul Danner is to automotive Diagnostics this man is to HVAC technology . Amazing teaching and diagnostic skills :-)
@jrm163
@jrm163 9 күн бұрын
Nowadays only those high-price ACs have these switches, while the rest have almost zero! Yes, they want your AC to blow up ASAP! Part of planned obsolescence! Good job, EPA!
@nunezravelin3898
@nunezravelin3898 3 жыл бұрын
That's the best video I ever seen about low and high pressure switches!
@Petracca-01
@Petracca-01 Ай бұрын
Absolute amazing video 2nd yesr sparky who haven’t learnt much as of yet and this has just helped me out so much thank you
@user-vb8jl6nf4k
@user-vb8jl6nf4k 4 жыл бұрын
You’re the best Craig I really appreciate all what you’re doing and thanks a million for sharing your knowledge and pass it to the new generation
@danielprice9997
@danielprice9997 Жыл бұрын
I know this is an old video, but Im just finishing school and the material you put out is fantastic. I have your book…right now Im just a goofy new guy..but your book is my goto source. Thanks again.
@YTsux24-7
@YTsux24-7 5 жыл бұрын
Late to the party because I'm on call this week and was pretty busy yesterday. It was interesting that you could hear an audible click when those pressure switches opened and closed, however you would never hear it with the compressor or the fan running. Good stuff Craig!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks a lot Tomon8tor!
@luispina317
@luispina317 2 ай бұрын
You do a great way at explaining things in thorough. Thank you sir
@stanleykania7184
@stanleykania7184 Жыл бұрын
I find all this HVAC stuff to be awesome. Electricain here from Indiana, Pa
@dmitriyeveasley2646
@dmitriyeveasley2646 Жыл бұрын
Great video for a beginner. I always enjoy watch and learning from your videos.
@tunaman2200
@tunaman2200 3 жыл бұрын
Thank you so much for posting these videos. It really ads to my diagnosing arsenal.
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
You are so welcome!
@acrepairnearme
@acrepairnearme 5 жыл бұрын
Thank you! New camera?) Video quality is much much better.
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Yes, I trying to put out all 4k now thanks to you Patrons! Thanks Tapch MC!
@BindarRouge
@BindarRouge 4 жыл бұрын
Thank you so much for this video. Never learned that much in training or working in the field. Having a trouble with a fairly new Trane heat pump. Something I have never heard of or seen before. The contactor had an intermittent problem which after two visits got to see first hand. Customer was complaining about a grinding noise (always a red flag) so I came and checked but found nothing wrong and pressures good. Only oddity was a fried lizard on top of the capacitor. The cap checked out OK. About 2 weeks later unit wasn't working. Cap still good but unit wouldn't work. Standing pressure was over 200psi. I pushed contactor in and ran fine. When I released it stuck just slightly as I moved my hand away. Didn't give that much thought and went to attic to check safeties there. All was fine. Back to HP. When I went back outside the unit came on. As I was watching the gauges the contactor started to spark and arc bouncing in and out making the grinding noise the customer had mentioned and was really scary! I pulled the disconnect and replaced the contactor but again the unit would not come on. I thought maybe compressor went out on thermal. Only thing I could find was the low voltage was being stopped by the high pressure or high temperature switch. Now I need to figure out which one and replace it. I am guessing it fried when the contactor arced but not sure. Watched this to see if I could learn more about these switches and how to test them. THANKS!
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Also check for incoming line voltage and voltage drop while running. There could be an issue there, thanks!
@BindarRouge
@BindarRouge 4 жыл бұрын
@@acservicetechchannel never seen where they wired the high pressure and high temperature in line together. I was able to pull the connection to it and put it on the contactor for now to get them cooling. Guess I am going to have to replace both but it looks like pressure switch is welded in .... ARGH
@duanehouston7689
@duanehouston7689 18 күн бұрын
Thanks!
@acservicetechchannel
@acservicetechchannel 17 күн бұрын
Thank you very much for your encouragement!!
@logicalrat
@logicalrat 5 жыл бұрын
Got my universal in the mail today, thanks dawg. Your videos are very helpful for someone green like me.
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thats awesome Cole! Congratulations!
@BrettWae
@BrettWae 5 жыл бұрын
I love this channel, thank you so much for taking time to make and post these videos!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks a lot Brett!
@PaulHVAC1
@PaulHVAC1 5 жыл бұрын
Craig once again your give outstanding video instruction! Keep up the good job Cheers!!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks a lot Paul HVAC!
@jericosha2842
@jericosha2842 3 жыл бұрын
This is a great demonstration. Love the little custom tool you brazed to show this. Demystified them for me =)
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
Glad you enjoyed it!
@deloct
@deloct 5 жыл бұрын
Always great learning channel. Yes I use Amazon to get some of tools on the list. Thank you.
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
That is great, anything purchased after entering those amazon links provides a commission for the channel! I used to have so many people asking where to get the tools from that were used in the video so it takes care of two birds with one stone. Thanks Octavio Delgado!
@meaneme
@meaneme 3 жыл бұрын
This is very useful, I appreciate this tremendously.
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
Glad it was helpful!
@deanslevin5511
@deanslevin5511 2 жыл бұрын
Really appreciated your hardworking bro..it really help me to understanding the ptc better..thanx bro👍👍👍
@daimlerblanco3752
@daimlerblanco3752 5 жыл бұрын
Amazing video wow I’m speechless you are a great instructor thanks for sharing
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thank you very much! Have you seen the sample pages and outline from my refrigerant charging book at acservicetech.com yet? Thanks!
@thedogwoodclub3288
@thedogwoodclub3288 Жыл бұрын
do you guys have a video like this on transducers?
@chithrabharathi1678
@chithrabharathi1678 9 ай бұрын
Excellent explanation.
@ericstrauss6755
@ericstrauss6755 4 жыл бұрын
Thanks so much for comprehensive demonstration. Helped me a lot.
@carcanbus
@carcanbus 3 жыл бұрын
Thank you man I learnt a lot from you video
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
Glad to hear it!
@suhailasaba1051
@suhailasaba1051 4 жыл бұрын
Very very very great explanation.
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thanks a lot Suhaila!
@DanO181919
@DanO181919 5 жыл бұрын
Thank you, thank you.... you have taught me so much. God bless!!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks a lot Danny! May the Lord Bless you too!
@alphabears6342
@alphabears6342 4 күн бұрын
So if my heat pump is not running and the low pressure switch is OL, that would be normal?
@humbertomacias3239
@humbertomacias3239 6 күн бұрын
Do you have to change the filter drier if your swapping a switch with no shrader?
@kengardner5097
@kengardner5097 3 жыл бұрын
Do the pressure switches come standard with a Schrader depressor so they can be changed out?
@spelunkerd
@spelunkerd 4 жыл бұрын
Brilliant explanation!
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thanks a lot spelunkerd!
@soloaviles
@soloaviles 2 жыл бұрын
Great video, very informative! Thank you for making this.
@BlueWorldPhotography
@BlueWorldPhotography 3 жыл бұрын
Great video!
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
Glad you enjoyed it
@hauvu1989
@hauvu1989 2 жыл бұрын
this helped a lot
@ejohnfall
@ejohnfall 5 жыл бұрын
Very good information thank you
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks ejohnfall!
@davidallen9024
@davidallen9024 3 жыл бұрын
Great video
@acservicetechchannel
@acservicetechchannel 3 жыл бұрын
Thanks for the visit
@pedronavarrete8131
@pedronavarrete8131 5 жыл бұрын
Awesome video, I like all of your videos
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks a lot Pedro!
@gentrylabarda8576
@gentrylabarda8576 Жыл бұрын
Brilliant
@padilla7019
@padilla7019 5 жыл бұрын
Another great video
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Luis!
2 жыл бұрын
It wasn't clear whether the firs number is when the sensor opens circuit and the second number when it closes the circuit.
@thomasguillen5898
@thomasguillen5898 Жыл бұрын
Hello there Question. will a defective pressure switch make a condenser unit not cycling off when reaching set temperature? Thanks for any advice....
@fridgydownunder6734
@fridgydownunder6734 5 жыл бұрын
Thank you for making this video👍🏽👍🏽👍🏽
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Edgar!
@tendajiburnett5824
@tendajiburnett5824 11 ай бұрын
So, are all pressure switches normally closed
@hewaakrey8581
@hewaakrey8581 3 жыл бұрын
Thanks I wanna know working and cut out and cut in pressure for frions Can u explain if possible
@ianigop2738
@ianigop2738 2 жыл бұрын
thank you very much sir.
@search4truth616
@search4truth616 4 жыл бұрын
The Lennox unit I just repaired at my home has a pressure switch with a reset button on it. The outdoor unit would not power on at all. I pushed the button on the High Pressure Switch and the unit started running again. I felt a distinct click when I pushed the button which you can not feel in subsequent pushing.
@deanmartin1966
@deanmartin1966 5 жыл бұрын
Great Video
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks Deanmartin1966!
@ba177ba18
@ba177ba18 4 жыл бұрын
Hi, My condenser isn’t turning on due to refrigerant leak and 24 volts are shut off not getting to the contactor. Since the condenser is not turning on, how do I pump the refrigerant into the system to increase the pressure order to run again? Can i still pump the refrigerant when condenser unit is off? please help thanks 🙏
@KSWKREW
@KSWKREW 3 жыл бұрын
Please do not try to add refrigerant into a system without being properly trained first . Not only can you possibly harm yourself or the equipment, it’s against USA federal law for anyone not EPA certified to buy and handle refrigerants.
@babaolowo35
@babaolowo35 2 жыл бұрын
Thanks 👍
@SaresMLee
@SaresMLee Жыл бұрын
So the high pressure switch is NC switch and low pressure switch is NO?
@SaresMLee
@SaresMLee Жыл бұрын
If yes, how can we get 0,001 resistance across both of them!?
@padaddy
@padaddy 2 жыл бұрын
I have an intermittant low pressure fault but it occurrs a few seconds *after* the compressor stops any ideas?
@Zay408er
@Zay408er 2 жыл бұрын
Super sweet video. you da man
@sfchannel764
@sfchannel764 3 жыл бұрын
Great video sir 👍.. I have 1 question. In case of gas shortage due to gas leakage occurs. Low pressure switch will disconnect the electrical circuit and the compressor will be off. So, what is the procedure to fill the refrigerant gas to the outdoor unit? .. So the compressor can turn on again after we fill refrigerant..
@pigadokamayad3393
@pigadokamayad3393 2 жыл бұрын
Bypass first the pressure switch. To run the compressor to fill up gas into the system.
@elaineamason9218
@elaineamason9218 4 жыл бұрын
excellent job thank you
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thanks for watching!
@mahfuj7695
@mahfuj7695 4 жыл бұрын
About education vedio....... Very nice
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
Thank you!
@mondoalvarez2486
@mondoalvarez2486 5 жыл бұрын
You and videos kick ass .. Keep up !!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Thanks a lot Armando!
@juannanez3969
@juannanez3969 2 жыл бұрын
What happens if I’m checking for continuity and one of the switches is giving me a measurement of 430 ohms? This is when I have my meter set for continuity. The other one just showed 0 ohms.
@onlyulee866
@onlyulee866 4 жыл бұрын
What would you recommend for cut in and out if the box room 50/55 degree on 404a refrigerant
@OthmanAlikhan
@OthmanAlikhan 2 жыл бұрын
Thanks for the video =)
@abaidaramex2818
@abaidaramex2818 3 жыл бұрын
What can be the issue standing pressure is good and then compressor comes on the pressure go very fast down and compressor shut off??
@inoahmann7542
@inoahmann7542 3 жыл бұрын
Probably a restricted metering device or low refrigerant.
@brianr1165
@brianr1165 2 жыл бұрын
My heat pump cuts of in heat or ac mode and flashes 5 times after about 10 min of running. And will not cut back on. Buuuut the pressure is correct all the way up to when it cuts off. Bad pressure switch maybe???
@ProjectDreamCatcher
@ProjectDreamCatcher Жыл бұрын
Hi guys. GREAT channel. Had a fault code showing 02 (high pressure switch) and replaced with exact same. Still showing 02? Is there a reset somewhere on the board that I can't find? The compressor & fan work fine ONCE I get the blower motor working. It trys to start 3 short times, then waits. The last time I got it running the speed was sporatic until it stopped? Replaced the capacitor with same a while back & cleaned the blower fan cage. I just have an Etek 10709 multimeter - probably need a new eh? System is an All-in-one outside Q7RE - 042K. Any ideas will be a Christmas present 🎅. Thanks
@jameswestii454
@jameswestii454 5 жыл бұрын
I have a 2013 RUUD 3.5 ton heatpump, Model #13PJL36A01 with 410a and a 63 ft. lineset. Yesterday it shut off after running 1 minute and 45 seconds. Liquid pressure stays at 175psi the whole time and vapor pressure started at about 50psi and immediately when unit came on the vapor side pulled into a vacuum. LED 1 is on but LED 2 flashes which states low pressure switch open. What are my possible causes? Been running great, filters clean as well as outdoor unit. Indoor unit has TXV at 2 o'clock position as called for in manual.
@MrCbell57
@MrCbell57 5 жыл бұрын
I have a 95 thunderbird which compressor is not coming on. It has what appears to be a 4 wire high side switch. I was not finding any way to test this 4 wire system.
@acservicetechchannel
@acservicetechchannel 4 жыл бұрын
I would recommend just trying to look up the model number on the switch so you know exactly what it is supposed to do and how it operates at the pressures, thanks!
@dapperdon7212
@dapperdon7212 5 жыл бұрын
How would you test if the system went out due to low or high pressure cutout? Thanks!
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
You wouldn't get 24v on each side of the pressure switch, only on one side. Put the multimeter probe on a common and the other probe on one side, then move the one probe from the one side to the other side to check for 24v on each side, thanks!
@atubebuff
@atubebuff 2 жыл бұрын
@@acservicetechchannel I never understood how some defrost controllers claim to detect a LP or HP when the switches are wired in series between Y & T1.
@Fj707ap
@Fj707ap 5 жыл бұрын
I have unit that takes 7 lbs of 407 c. What would be the static pressure with the unit off with an ambient temp exceeding 115 degrees?
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
247-280 psig with the system off at 115 degrees thanks!
@rtd2348
@rtd2348 5 жыл бұрын
AC Service Tech LLC something I’ve always struggled with, determining the proper pressures for given refrigerant at different ambient temperatures. How do you know what the pressure should be at a certain ambient?
@rtd2348
@rtd2348 5 жыл бұрын
AC Service Tech LLC also thank you for making these videos , you are a great instructor and really know how to break things down and make it make sense 👍👍
@carlossierra2190
@carlossierra2190 2 жыл бұрын
The example of having the LPS and HPS in series connected to the contactor is wrong
@sannyvalencia1558
@sannyvalencia1558 2 жыл бұрын
I need that explanation in Spanish, it looks very professional but I don't speak much English, and I had a problem that I think has to do with your video, that's why I'm watching it but I don't understand English very well, I'd like to hear it in Spanish.
@runningcoyote3897
@runningcoyote3897 5 жыл бұрын
Doesn't the compressor have an internal pressure switch?
@acservicetechchannel
@acservicetechchannel 5 жыл бұрын
Yes it does but you don't want that to releasing much because it will become weak and start leaking, thanks Running Coyote!
@jrm163
@jrm163 9 күн бұрын
I don’t think so! Otherwise, compressors wouldn’t blow!
@waynemiles7027
@waynemiles7027 7 ай бұрын
The question is how do you know which switch has a valve core depressor in them so you don’t Blow the charge when you try to RELACE THEM!
@ruhtrohraggy7497
@ruhtrohraggy7497 7 ай бұрын
They said how you can tell.. read the literature.
Thermostat Wiring Diagrams! 10 Most Common!
6:04
AC Service Tech LLC
Рет қаралды 305 М.
Charging R-410A Refrigerant into an Air Conditioner! Pressures, Temps, Tips!
27:56
AC Service Tech LLC
Рет қаралды 1,5 МЛН
WHO CAN RUN FASTER?
00:23
Zhong
Рет қаралды 45 МЛН
Ik Heb Aardbeien Gemaakt Van Kip🍓🐔😋
00:41
Cool Tool SHORTS Netherlands
Рет қаралды 9 МЛН
When you discover a family secret
00:59
im_siowei
Рет қаралды 14 МЛН
Air Conditioner Troubleshooting! Connecting, Measuring, Fixing, Disconnecting!
21:05
HVAC  076 Pressure Switch Refrigerant
16:34
Love2HVAC with Ty Branaman
Рет қаралды 43 М.
Refrigeration: Low Pressure Control As Temp Control
25:22
Christopher Molnar
Рет қаралды 91 М.
Failed Compressors - Don't JUST REPLACE IT
24:59
HVAC School
Рет қаралды 62 М.
Trane Heat Pump with Bad HPS, Diagnosed! #hvac #airconditioner #heating
11:46
Jeff’s HVAC Adventures
Рет қаралды 19 М.
Liquid Line Restriction on AC Unit Explained! Found Bad TXV!
13:35
AC Service Tech LLC
Рет қаралды 391 М.
A2L Refrigerants R-454B and R-32 Explained! Bottles, Changes, Rules, Tools!
22:15
How to Check AC Freon Level
16:52
Word of Advice TV
Рет қаралды 2,1 МЛН
How to Test Pressure Switch on a Furnace
14:26
Word of Advice TV
Рет қаралды 610 М.
WHO CAN RUN FASTER?
00:23
Zhong
Рет қаралды 45 МЛН