HOW TO PREFORM EARTH RESISTANCE TEST

  Рет қаралды 244,684

rictor rictor

rictor rictor

4 жыл бұрын

This tutorial show how to carry out earth resistance test for commercial and resident building . Proper setting is importance for getting the better and accurate test result .

Пікірлер: 229
@kalamsa7445
@kalamsa7445 Жыл бұрын
Without much noise around, explained in a simple practical way...Thanks Rictor
@30mAkills
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@salumhongo3955
@salumhongo3955 11 ай бұрын
You demonstrate this critical task to look easily, Thank you very much a learn a lot through your video.
@fje1948
@fje1948 10 ай бұрын
The video I was looking for! Excellent explanation of the test. Thank you so much! Ps: The background music is pleasant and appropriate!
@castertroycabillar2863
@castertroycabillar2863 2 жыл бұрын
Thanks for this very informative vedio. More power.
@muhdyunus3894
@muhdyunus3894 3 жыл бұрын
Video paling sng difahami...tq sgt2
@MrSyahryzal
@MrSyahryzal 2 жыл бұрын
Mudah untuk difahami... Lama mencari video earthing test untuk menambah ilmu. Terima kasih boss
@PbaY.
@PbaY. 3 жыл бұрын
mantap tutorial nya .👍👍🌟🌟🌟
@o-techtips3871
@o-techtips3871 2 жыл бұрын
Thank you very much for your sharing very informative tips☺️
@yghiduppastimatikelak8854
@yghiduppastimatikelak8854 2 жыл бұрын
Good job ...thanks for sharing..
@kirotomato7316
@kirotomato7316 3 жыл бұрын
easy to understand,thank you sir for wharing the information for us
@marchomeautorepairs
@marchomeautorepairs 2 жыл бұрын
Keep up the good work
@foonglikwei3913
@foonglikwei3913 2 жыл бұрын
This teaching very useful and very easy to understand. Thanks and appreciate it 😊
@30mAkills
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@ohhappyday1548
@ohhappyday1548 2 жыл бұрын
thanks to your efforts, it is very helpful .. thank you..
@ofwj-ddah
@ofwj-ddah Жыл бұрын
Thanls for sharingbthis video. It helps me a lots
@electroboy3607
@electroboy3607 27 күн бұрын
Good interesting vedio😊😊😊
@manjunathamanju6204
@manjunathamanju6204 3 жыл бұрын
Thank you Sir this video very useful for all Electrical engineers
@electroboy3607
@electroboy3607 11 ай бұрын
Good job..🎉 im practical test
@MrOner07
@MrOner07 2 жыл бұрын
very easy to follow... you earned a subscriber!❤️😊
@30mAkills
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@kanthasamymuthusamy739
@kanthasamymuthusamy739 Жыл бұрын
Simple explainations.Easy to underdstand
@30mAkills
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@william5624
@william5624 2 жыл бұрын
Very good👍🏻
@sanjeevraghav3700
@sanjeevraghav3700 Жыл бұрын
Very nice vedio 👌👌kudos to your effort 🙏🙏👌
@30mAkills
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@joselitodupaya2092
@joselitodupaya2092 3 жыл бұрын
Thank you sir sa video
@anthondiy
@anthondiy Жыл бұрын
Thank you sir sa video another learning for earthing system
@redbirdgaming7905
@redbirdgaming7905 3 жыл бұрын
Thank you very much sir Many Thanks
@CrisBoy410
@CrisBoy410 Жыл бұрын
video excelente parabens , abraços do Brasil .
@nathan37141
@nathan37141 Жыл бұрын
Thank you Engineer
@ahmedbelazi2318
@ahmedbelazi2318 Жыл бұрын
Thank you for the effort made in the video.... I have a question... Is it true that the yellow wire is supposed to be an extension of the red wire, meaning on one line to give the reading... Why change in yellow only and should it be changed in red? ??
@fazrulchanneltv9157
@fazrulchanneltv9157 2 жыл бұрын
Tq Sir. Clear and easy to undrstand. This place is like "Bukit Bendera" 😅
@rictorrictor888
@rictorrictor888 2 жыл бұрын
Yes bro..bukit bendera..tqvm
@angelosrcayabyab6952
@angelosrcayabyab6952 2 жыл бұрын
thanks for sharing
@sahayaxaviersahayaxavier3217
@sahayaxaviersahayaxavier3217 3 жыл бұрын
Salute sir
@sanjeevraghav3700
@sanjeevraghav3700 Жыл бұрын
Appreciate 👌👌you have done share gr8 experience with kyoritsu instrument 💐 This is sanjeev raghav from kyoritsu
@rictorrictor888
@rictorrictor888 Жыл бұрын
Thank too .kyoritsu always the great equipment ..
@30mAkills
@30mAkills Жыл бұрын
This method is not FOP.
@user-ic5re6so6e
@user-ic5re6so6e 2 жыл бұрын
Thank you, sir
@VlogSidah
@VlogSidah 3 жыл бұрын
Mantap tuan,done support ya,maaf lewat.. 🙏🙏
@akilagayan6533
@akilagayan6533 Жыл бұрын
Good work 👍
@30mAkills
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@gabus1956
@gabus1956 2 жыл бұрын
Thank from Hungary
@30mAkills
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@iranweranga225
@iranweranga225 Жыл бұрын
Is there a specific number of times that earth resistance testing should be done for a specific area? (like number of times per meter squard)
@jillferrer6135
@jillferrer6135 2 жыл бұрын
thank you sir..
@robertotrinanes1744
@robertotrinanes1744 7 күн бұрын
What about the grounding rod resistance?each rod shall be tested and removed all connected cable before the test of total resistance grounding.
@muhdsolihin2641
@muhdsolihin2641 Жыл бұрын
should be disconnecting earth cable from house to ground chamber first. so you will get the purest ground resistance.
@pankajmishra43
@pankajmishra43 Жыл бұрын
Hiiii... You mean, first disconnect the earth cable from earth pit?? OR Can we shutdown the entire system before measuring earth resistance?? Pls guide
@Sim_Tiby
@Sim_Tiby Жыл бұрын
Disconnect the earth cable.
@DiReal_Donclassy
@DiReal_Donclassy Жыл бұрын
Of course he must have done that before starting the test otherwise the resistances of home equipment will distort the result
@igorsmirnoff8578
@igorsmirnoff8578 Жыл бұрын
Будьте любезны,выложите такое же видео с прибором KEW 4106,спасибо!!!
@matsetizar65
@matsetizar65 3 ай бұрын
when lightning strikes the earth doesn't the surge enter the house via the earth wiring? If so isn't it dangerous, probably better not to have any earthing system at all?
@arturotakuma4742
@arturotakuma4742 Жыл бұрын
excelent ¡¡¡
@pankajraina4832
@pankajraina4832 Жыл бұрын
Good sir 👍
@30mAkills
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@svh6195
@svh6195 3 жыл бұрын
Thanx!!
@wazzer5293
@wazzer5293 8 ай бұрын
Sir, how 1). If earth got voltage, what is the next action.. 2). When to use the setting mode 200 & 2000? Apprecite ur answer
@solomonnyaga7018
@solomonnyaga7018 10 ай бұрын
Does it mean now the earth resistance is perfect?
@dakwahislamcn6390
@dakwahislamcn6390 3 жыл бұрын
Lanjutkan
@neilblenkinsop2613
@neilblenkinsop2613 Жыл бұрын
To individually test the earth rod disconnect tape from earth rod
@francisrayang805
@francisrayang805 3 жыл бұрын
Hi sir. You did a very informative video thanks. I've a question for you.In the video you did the test on a big compound. I'm in a terrace house and the compound is very limited. I can't pull the yellow and red cable that long..only 3-4 meters to the nearest soil. Will it affect the reading? Please advice thks.
@rictorrictor888
@rictorrictor888 2 жыл бұрын
In that situation ..You can try nearest area to ground the spike ..
@rictorrictor888
@rictorrictor888 2 жыл бұрын
in that situation ..yes..
@30mAkills
@30mAkills Жыл бұрын
You have to maintain distance. Please read my other comments. Get permission from neighbours.
@yusufsupyan9940
@yusufsupyan9940 3 жыл бұрын
Luar biasa kawan Videonya. Sudah saya kirim Bungkusan komplit dan,paten, durasipun Aman. Sesuai undangan. Ditunggu Amanahnya ya..
@rictorrictor888
@rictorrictor888 3 жыл бұрын
Ya udah juga..terima kasih..
@bornstar9897
@bornstar9897 3 жыл бұрын
thanks
@siralexivan2006
@siralexivan2006 3 жыл бұрын
well done
@rictorrictor888
@rictorrictor888 3 жыл бұрын
Tqvm
@bundaajhalah
@bundaajhalah 4 жыл бұрын
Hadir nyimak 👍
@rictorrictor888
@rictorrictor888 4 жыл бұрын
thank you so much
@Bestofthebest383
@Bestofthebest383 2 ай бұрын
I had an exams question in college how to do earth rod test . I didn’t pass it 😢
@anthonykihanga2881
@anthonykihanga2881 Жыл бұрын
Thanks alot
@30mAkills
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@niezam1729
@niezam1729 3 жыл бұрын
Jika persekitaran rumah tamn agak sukar nk ambil bacaan,sb permukaan tanah @ berturap simen Dan jalan tar. 1- minutes 6.15 mase kita clamp wayar di electrod bumi.yg seeloknya copper tape @ cable incoming perlu ditanggalkan @ tidak semasa nak ambil bacaan.klu sye lihat Tuan x buka ..
@nasrulhelmeihalimppksistem7432
@nasrulhelmeihalimppksistem7432 2 жыл бұрын
kalau kawasan tar @ bersimen, boleh guna metal screen @ earthing mat. letak pada jarak yg ditetapkan & siram dgn air jd blh buat measurement
@fauzibafana9089
@fauzibafana9089 2 жыл бұрын
Can i know whether before the individual earth rod being tested you have to remove the connection of the earth rod from the rest.
@gniraj8501
@gniraj8501 Жыл бұрын
I am also have same question.
@30mAkills
@30mAkills Жыл бұрын
Yes it should be disconnected from service. If the voltage is more than 10 it will destroy the meter and also give false reading. Please read the user manual reg the max voltage limit that the meter will work safely in energised service without disconnection.
@gohpoikheng6030
@gohpoikheng6030 2 жыл бұрын
May i know why the cable for current is longer than the voltage?
@raemondbradford1629
@raemondbradford1629 2 жыл бұрын
When current is injected into the earth, then the voltage will change around the location of injection. The voltage reference cable spike needs to be some distance from the points where current is injected or removed, in order to try and find a location with minimal disturbance of earth voltage potential.
@surendrakverma555
@surendrakverma555 Жыл бұрын
Good 🙏🙏🙏🙏🙏
@30mAkills
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@loveandpeace594
@loveandpeace594 Жыл бұрын
thanks :)
@30mAkills
@30mAkills Жыл бұрын
Shifting potential spike in perpendicular ( left and right)direction is not correct.
@fidelcatsro6948
@fidelcatsro6948 Жыл бұрын
if we had no access to such equipment will adding more grounding rods to the ground all connected together potentially reduce the earth resistance?
@rictorrictor888
@rictorrictor888 Жыл бұрын
Yes.
@fidelcatsro6948
@fidelcatsro6948 Жыл бұрын
@@rictorrictor888 🐱👍🏿
@HENRYFANUELPHIRI
@HENRYFANUELPHIRI Ай бұрын
Why the leads are in same line? pliz assist me sir.
@prabhus4137
@prabhus4137 2 жыл бұрын
Hi sir I have a doubt. Could you please tell me the difference between 2 point, 3 point method. In megger it has 4 terminals C1, C2, P1, P2. how to measure earth pit resistance?
@30mAkills
@30mAkills Жыл бұрын
Short C1 and P1 and connect to electrode under test. P2 is for potential and C2 is for current spike. This is known as 3 point or Fall of Potential method. 4 terminals method is for testing soil as per Wenner method. This is for civil guys and not for electrical guys. Reg 2 point earth pit resistance testing: In India we don't/cant use this method because our public water supply is thru PVC pipes which is non conductor. Hope this helps.
@Bwelz2010
@Bwelz2010 Жыл бұрын
Good, Thanks
@ericmunkanta2964
@ericmunkanta2964 3 ай бұрын
Why is the leads in the same line
@DaBlackTradesMan
@DaBlackTradesMan Жыл бұрын
I have to perform this same test but outside of the building is all concrete, a shower room will be built in the basement but first the neutral to earth voltage needs to be tested, so how would I go about this?
@frankkennedy7831
@frankkennedy7831 Жыл бұрын
you silly person. what sort of system are you on?
@30mAkills
@30mAkills Жыл бұрын
Check with normal clamp or multimeter in volts mode between earth and neutral of any 3 pin socket connected to that service. The voltage value should be below 2. Hope this helps.
@fje1948
@fje1948 10 ай бұрын
@@frankkennedy7831 Perhaps you are the silly person making such an inappropriate comment! 🤢
@azleeman
@azleeman 3 жыл бұрын
Saya nak tanya, bukankah testing dibuat semasa pemasangan rod sahaja (sebelum kita sambungkan dengan earth DB atau sebelum sambung ke perlindungan kilat)
@rictorrictor888
@rictorrictor888 3 жыл бұрын
Kedua2 nya boleh ..sebelum dan selepas ..Sebenarnya Cooper tape itu bukan utk pelindung kilat..
@dumindathusuth2026
@dumindathusuth2026 Жыл бұрын
@japhethm6103
@japhethm6103 6 ай бұрын
What readings should tell me that the resistance is not okay please
@rictorrictor888
@rictorrictor888 6 ай бұрын
depend on local regulation ..as lower as possible. .below 10ohm
@KGL101293
@KGL101293 2 жыл бұрын
Hi, I have a Kyoritsu 4105A unit too, and I am getting "1. . ." reading at 20 ohm dial, who do you think is the problem, and how to fix this? Thank you.
@deutroitcity
@deutroitcity 2 жыл бұрын
It's over limit. U need to dial up the limit. Cannot use 20ohm. Because the reading is above 20 ohm
@nasiadomary4893
@nasiadomary4893 Жыл бұрын
How about if the reading is 25ohms What can i do to get less than 5Ohms?
@30mAkills
@30mAkills Жыл бұрын
@@nasiadomary4893 1. If possible increase the depth of electrode. 2. Insert another electrode at a distance of at least twice the buried depth of 1st electrode and link both at top. Eg.: If 1 st electrode buried depth = 3 M then second electrode should be installed at a distance of minimum 6 M away and both should be linked with wire or strip at the top. 3. Wet the pit by watering because dry earth is a bad conductor. Note : Chemical electrodes are fraud work. Hope all this helps.
@nasiadomary4893
@nasiadomary4893 Жыл бұрын
@@30mAkills Thanks🙏🙏
@leomarbecilla2785
@leomarbecilla2785 2 жыл бұрын
hi sir. how do you perform it in a building where there is no earth ground to put the spike?
@rictorrictor888
@rictorrictor888 2 жыл бұрын
Extent green wire..
@rictorrictor888
@rictorrictor888 2 жыл бұрын
For condo there should have main electrical grounding
@lonedragon4410
@lonedragon4410 2 жыл бұрын
Below 5ohm is acceptable right?
@rictorrictor888
@rictorrictor888 2 жыл бұрын
Yes
@yosuaabimo9379
@yosuaabimo9379 7 ай бұрын
Test ini apakah harus saat listrik off?
@muhammadaresyamilbinazman7935
@muhammadaresyamilbinazman7935 2 жыл бұрын
Tumpang tanya, kan ada 20ohm, 200ohm, dan 2000ohm. Yang tu nak laraskan berdasarkan faktor apa ye?
@fidelcatsro6948
@fidelcatsro6948 Жыл бұрын
dasarkan 20ohm setting
@AutodidactEngineer
@AutodidactEngineer Жыл бұрын
The test should be done preferably during the driest season to prevent moisture from ruinning your values!
@File-Transfer
@File-Transfer 4 ай бұрын
I have a question, engr. Why is it required in the earth resistance tester manual to damp the surroundings?
@AutodidactEngineer
@AutodidactEngineer 4 ай бұрын
@@File-Transfer I don't know about that
@stanleyozoilo1587
@stanleyozoilo1587 Жыл бұрын
What is the accurate value for best low resistance using Megger machine
@rictorrictor888
@rictorrictor888 Жыл бұрын
0 ohm
@30mAkills
@30mAkills Жыл бұрын
@@rictorrictor888 Practically not possible. Is earth full of gold?
@fje1948
@fje1948 10 ай бұрын
@@rictorrictor888 I wish 😂
@castertroycabillar2863
@castertroycabillar2863 2 жыл бұрын
Sir what is the porpuse for higher ohms setting.is it same result as 20ohms setting.thanks
@rictorrictor888
@rictorrictor888 2 жыл бұрын
Yes..same.
@30mAkills
@30mAkills Жыл бұрын
For soil testing and also in hill areas.
@wtnyambizi9876
@wtnyambizi9876 Жыл бұрын
What about the distance btn the spikes does it matter !?
@anthonykihanga2881
@anthonykihanga2881 Жыл бұрын
5 meters up to 10 meters it depends on soil type
@30mAkills
@30mAkills Жыл бұрын
Thumb rule for current spike distance from electrode = Minimum 8 to 10 times the buried depth of earth electrode. Eg., If earth electrode is 3 M long then C spike should placed about 24 to 30 M distance. This is to avoid '"zone of influence"' factor. Most manufacturers wont tell this because the distance will affect their tester sales in city and town areas where space is congested. So they suggest 5 M and 10 M which will not yield correct value. I challenge Kyoritsu in this matter.
@fje1948
@fje1948 10 ай бұрын
@@30mAkills Thank you for this comment - can you please provide some formal references to confirm y you our comment - Thank you!
@wilsonloo8576
@wilsonloo8576 3 жыл бұрын
Hi Rictor , may i know how to know the result is good or bad? Many Thanks
@rictorrictor888
@rictorrictor888 3 жыл бұрын
low in reading is the batter .must below 10ohm.some time we can get 0 ohm. that the best..
@octaviohurtado2779
@octaviohurtado2779 3 жыл бұрын
It depends on your country standards. But the Best is the nearest to 0 ohms which is imposible to get 0 ohms. Also there are many methods to make the measurraments, it depends on your country standards too.
@yumon6515
@yumon6515 3 жыл бұрын
Sir, can I set the tester 200ohm? Should I take that result? Thank you 🙏
@rictorrictor888
@rictorrictor888 3 жыл бұрын
yes..
@GUDANGLAMPUSURYA
@GUDANGLAMPUSURYA 2 жыл бұрын
Om untuk mengetahui brp kedalaman grounding rod yg di tanam bagaimana ya ? 🙏
@GUDANGLAMPUSURYA
@GUDANGLAMPUSURYA 2 жыл бұрын
Apakah bisa di test dgn ohm meter tersebut
@rictorrictor888
@rictorrictor888 2 жыл бұрын
Kedalam nya sehingga rod gak bisa masuk lagi..baru di uji..jika masih tidak mendapat kan bacaan yg dikehendaki..buat point baru sehingga mendapat bacaan yg paling rendah
@kennedymutuku8950
@kennedymutuku8950 Жыл бұрын
Hello Sir,what if the result is above 10,let say 50..how can you improve this to 5?
@AutodidactEngineer
@AutodidactEngineer Жыл бұрын
Use a combination of vertical and horizontal grounding! My tip would be get copper/or in poorer countries galvanized pipe works well enaugh and install it in conjunction with galvanized steel bar/ or do the same but with copper if you can afford it!
@fidelcatsro6948
@fidelcatsro6948 Жыл бұрын
add more earthing rods all around the place the more the better🐱👍🏿
@neilblenkinsop2613
@neilblenkinsop2613 Жыл бұрын
All earth rod supplies these days are carbon steel with copper coating add to and go deeper using brass connection.
@junsmackalbos4565
@junsmackalbos4565 Жыл бұрын
Sir the result you shown is that good or bad grounding
@rictorrictor888
@rictorrictor888 Жыл бұрын
Good ..under 10 ohm
@junsmackalbos4565
@junsmackalbos4565 Жыл бұрын
Thanks sir......
@islammaidul6999
@islammaidul6999 2 жыл бұрын
Overall resistance how is it calculation sir
@rictorrictor888
@rictorrictor888 2 жыл бұрын
Total of test 1 ,2 ,3 then / by 3..it show on video min 13.20
@Mike-ry4ti
@Mike-ry4ti Жыл бұрын
Your value of 1.63 ohms is a little high. Ideally less than 1 ohm is what you want...
@aruquest25
@aruquest25 3 жыл бұрын
The green wire is for?
@rictorrictor888
@rictorrictor888 3 жыл бұрын
electrode wire..
@olegkotletov7857
@olegkotletov7857 3 жыл бұрын
green wire is for grass. grass is green. make sense right? put green wire on grass and see resistance of grass. grass is green, green wire is green too. make sense right? right.
@MNor-nb8sp
@MNor-nb8sp 2 жыл бұрын
What we do if earth volt not zero
@rictorrictor888
@rictorrictor888 2 жыл бұрын
Find another location for grounding the rod..
@30mAkills
@30mAkills Жыл бұрын
De-energize that service and procced if the voltage is more than 10.
@FabioHM71
@FabioHM71 2 жыл бұрын
the operator wears the helmet because there are suspended loads?
@rictorrictor888
@rictorrictor888 2 жыл бұрын
He worries falling mango fruit..hahaha
@FabioHM71
@FabioHM71 2 жыл бұрын
@@rictorrictor888 hahahaha ;-)
@fidelcatsro6948
@fidelcatsro6948 Жыл бұрын
there are flying cats around in the neighborhood
@ervingjonaj9082
@ervingjonaj9082 6 ай бұрын
music is shocking
@thanhthoangngo2591
@thanhthoangngo2591 3 жыл бұрын
hi sir, if the screen will perform "1 . " , what's wrong?
@rictorrictor888
@rictorrictor888 3 жыл бұрын
show me photo..
@octaviohurtado2779
@octaviohurtado2779 3 жыл бұрын
The valor is over the Range selectionated in the istrument or the cables are not conected correctly to the Spikes You should to check again all the conections. If the problem continue changue the Spikes of place.
@thanhthoangngo2591
@thanhthoangngo2591 3 жыл бұрын
@@octaviohurtado2779 Thank you! I'll check carefully. Good day!
@thanhthoangngo2591
@thanhthoangngo2591 3 жыл бұрын
@@rictorrictor888 Sorry, I don't know how to share a photo via a youtube comment. Anyway, I'll check my device. Thank you for your guidance.
@johnhayhurst5884
@johnhayhurst5884 3 жыл бұрын
Very Very different to how it's done in the UK, In the UK those reading wouldn't be satisfactory but the method is way different so I don't know. Interesting though
@azleeman
@azleeman 3 жыл бұрын
Maybe the humidity in UK is different if we compare to Malaysia. The water in soil can effect the meter reading.
@nasrulhelmeihalimppksistem7432
@nasrulhelmeihalimppksistem7432 2 жыл бұрын
@@azleeman biasanya ada 2 jenis earth tester yg selalu diguna measure grounding resistance. yg dlm video ni guna kyoritsu & location potential spike tu ditengah2 antara ground rod & current spike. yg satu lg jenama megger tapi jarak potential spike tu 62% dari jarak antara earth rod & current spike. & potential spike tu kena ubah 10% ke depan % 10% ke belakang dari kedudukan asal & diambil average dr 3 reading td. mungkin kat uk guna jenama megger sbb tu dia ckp different dgn kt sini.
@30mAkills
@30mAkills Жыл бұрын
All over the world FOP (Fall of Potential) method is same.
@johnhayhurst5884
@johnhayhurst5884 Жыл бұрын
Incorrect@@30mAkills
@30mAkills
@30mAkills Жыл бұрын
@@johnhayhurst5884 then tell the correct. Here our earthing is TT.
@lenslens7379
@lenslens7379 2 жыл бұрын
I think 1/RT = 1/R1 + 1/R2 + 1/R3
@SpecialVeloce
@SpecialVeloce 10 ай бұрын
Sorry your Appying the wrong formula, it's average, not resistances in paralel
@johnvillellegunas186
@johnvillellegunas186 Жыл бұрын
Hi sir. If floor is concrete, how to insert voltage and currrent spikes?
@fidelcatsro6948
@fidelcatsro6948 Жыл бұрын
break concrete and place into the soil below?
@30mAkills
@30mAkills Жыл бұрын
It need not be inserted. Wrap the spikes in wet towel and place them horizontally on the concrete floor with weights (stone) placed on the sack. Wet the whole area by watering.
@fje1948
@fje1948 10 ай бұрын
@@fidelcatsro6948 Jesus, what planet are you on…..
@fje1948
@fje1948 10 ай бұрын
@@30mAkills Excellent explanation….
@fidelcatsro6948
@fidelcatsro6948 10 ай бұрын
@@fje1948 planet Kittygystan 🐱 of the 23rd Constellation, why do you ask amigo?
@bruce.bchannel9046
@bruce.bchannel9046 3 жыл бұрын
Macam mna kalo erathing buat ats tnh bacaan bukit tu tnh...
@rictorrictor888
@rictorrictor888 3 жыл бұрын
tetap kena dapat kan bacaan bawah 10 ohm juga...tapi ada kaedah2 untuk menurunkan bacaan jika di buat atas tanah berbukit..tq
@bruce.bchannel9046
@bruce.bchannel9046 3 жыл бұрын
Sa lbih 15ohm bgtu
@bruce.bchannel9046
@bruce.bchannel9046 3 жыл бұрын
Nnti whatapps kmi 0138724857 mhu tnya kaedah lain
@rictorrictor888
@rictorrictor888 3 жыл бұрын
@@bruce.bchannel9046 boleh tambah point lagi tu..atau guna wayer tembaga bogel gulung jadi kan coil...tanam terus dlm tanah.hujung nya sambung ke electrod yang sedia ada..
@bruce.bchannel9046
@bruce.bchannel9046 3 жыл бұрын
Mcm mna cara ti
@daspecialist1220
@daspecialist1220 Жыл бұрын
Attack of the silent explanation vid strikes yet again
@rictorrictor888
@rictorrictor888 Жыл бұрын
Hahaha..Mr bean vers 2
@ahmadwahab1641
@ahmadwahab1641 3 жыл бұрын
untuk apa select ke earth voltage?
@rictorrictor888
@rictorrictor888 3 жыл бұрын
kita uji dahulu jika terdapat voltage dalam tanah.. terutamanya di kawasan kediaman yang berdekatan dengan sub station
@fidelcatsro6948
@fidelcatsro6948 Жыл бұрын
kalau ada voltage baguslah pasang diode boleh charge bateri kereta anda🐱👍🏿
@aruniimalka6123
@aruniimalka6123 2 жыл бұрын
what is this aim?
@rictorrictor888
@rictorrictor888 2 жыл бұрын
Protect human and electrical equipment from electric short
@user-vd6wb5ef8v
@user-vd6wb5ef8v 8 ай бұрын
Why to use this device with long cables and sticks while THEORETICALLY one can get more relevant results using any household electric appliance like, say, Incandescent light bulb, a mulimeter and the old good Ohm's Law? One terminal of the bulb is connected to live (hot), the other to earth and the current is measured. Divide voltage by current and subtruct the bulb's resistance and the result is the earth resistance. What is wrong in such approach?
@Godfa539
@Godfa539 6 ай бұрын
The results would only be resistance on the load , not main earth resistance
@user-vd6wb5ef8v
@user-vd6wb5ef8v 6 ай бұрын
@@Godfa539 will you justify this statement please?
@hidennseek1483
@hidennseek1483 4 ай бұрын
I get what you mean and yes you can get accurate measurement through ohms wall but use a proper load resistor that is large enough to limit the current so the damage you will cause on the ground rod is limited.
@MasudRana-sr1vf
@MasudRana-sr1vf 2 жыл бұрын
One time check can't ? Why 3 time check,
@rictorrictor888
@rictorrictor888 2 жыл бұрын
More accurate ..
@SpecialVeloce
@SpecialVeloce 10 ай бұрын
And if you need to get only one value, measure twice to rule out reading errors.
@thunderhype5972
@thunderhype5972 2 жыл бұрын
Sub
Earth Electrode Testing
14:16
John Ward
Рет қаралды 499 М.
Iron Chin ✅ Isaih made this look too easy
00:13
Power Slap
Рет қаралды 36 МЛН
Получилось у Миланы?😂
00:13
ХАБИБ
Рет қаралды 4,4 МЛН
Earthing vs. grounding
7:06
Paul Saladino MD
Рет қаралды 92 М.
Ground Rod Resistance
2:47
Northwest Lineman College's Lineman Channel
Рет қаралды 152 М.
How to Test a Lightning Protection System? ⚡
8:15
Axis Electricals
Рет қаралды 17 М.
What is Earth Resistance? How to measure it?
9:10
Axis Electricals
Рет қаралды 25 М.
اساليب قياس مقاومة الارضى بالجهاز
9:01
المهندس رجب نصر
Рет қаралды 222 М.
How to use a multimeter like a pro, the ultimate guide
12:55
James Gatlin
Рет қаралды 1,8 МЛН
INSTALLING AN EARTH ELECTRODE
7:36
Bristolsparky
Рет қаралды 5 М.
Iron Chin ✅ Isaih made this look too easy
00:13
Power Slap
Рет қаралды 36 МЛН