HVACR: Cooling Tower Service Call (Heat Trace Cable/Circuit Breaker Keeps Tripping) Short Circuit

  Рет қаралды 17,109

Jumper man Tech

Jumper man Tech

Күн бұрын

HVACR: Cooling Tower Emergency Service Call (15A Circuit Breaker Keeps Tripping for heat trace cable) Industrial Refrigeration Online Training
Heat trace is an electrical system used to maintain or raise the temperature of pipes and vessels. The electric heating is achieved by utilizing a resistant element that is run alongside the piping or vessel. Current heat trace technology utilizes a self-regulating polymer that controls the wattage of the element.
(TOOLS USED IN THIS VIDEO BELOW)
Fluke 902 FC HVAC True-RMS Clamp Meter
amzn.to/39wvwiK​
Veto Pro Pac TECH-LC Tool Bag
amzn.to/3qbmIWg
Supco ST09 Digital Pocket Thermometer, -40 to 392 Degree F
amzn.to/3oSAEn7
Fluke 62 Max Infrared Thermometer
amzn.to/2MJ7cTs
Wiha 32092 Insulated Screwdriver Set, 1000 Volt
amzn.to/39VSpxE
Knipex 9.5-Inch Ultra-High Leverage Lineman's Pliers
amzn.to/3cJd1Lv
Milwaukee M12 12V Cordless Lithium-Ion LED Stick Light
amzn.to/3aGYSMc
Milwaukee M12 XC6.0 Extended Capacity Battery Pack
amzn.to/39SudMw
Milwaukee Cut 1 Dipped GLOVES L
amzn.to/3s8H18O​
(CAMERA USED IN THIS VIDEO BELOW)
GoPro HERO8 Black Waterproof Action Camera
amzn.to/3aCDw2x
GoPro Head Strap with QuickClip
amzn.to/3cNQAVu
Thanks for watching!
Email: JumperManTech@Gmail.com
Follow me on Instagram! @JumpRmantech

Пікірлер: 66
@JOSERization
@JOSERization 3 жыл бұрын
Love the way you pronounce conduit “con do it”
@JumpermanTech
@JumpermanTech 3 жыл бұрын
You CON DO IT if you believe my friend!!!🤣🤣🤣 Well thank you!😄 Thanks for watching👍 Stay safe out there & stay tuned for new videos every week🔧
@GB-ue6wr
@GB-ue6wr 3 жыл бұрын
You can also ring them out to ground.. any resistance to ground will tell you what wire is bad. Good job man!
@JumpermanTech
@JumpermanTech 3 жыл бұрын
I couldn't find any grounded wires using resistance🤷‍♂️ This one was weird or maybe its my meter. Thank you & thank you for watching!🔧👍
@smyejhamza
@smyejhamza 3 жыл бұрын
@@JumpermanTech You could do it using the screw that holds the junction box if you want, :p
@simohvac9222
@simohvac9222 3 жыл бұрын
nice troubleshooting man, you are right never rush
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Thank you brother! Definitely don't rush💯 Stay tuned!
@refrigerationconfidential4376
@refrigerationconfidential4376 3 жыл бұрын
JMT nice find and troubleshooting
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Thank you bro!! Much appreciated🙏🙏🙏💪🙂 Keep up the good work🔧
@armandotorres626
@armandotorres626 3 жыл бұрын
Your videos are very informative, thanks for sharing the knowledge... Great backdrop of the city!!! 😊😊
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Thank you Armando! Your comment is very much appreciated🙏 Thank you & thank you for watching!👍🔧
@alexeytech1495
@alexeytech1495 3 жыл бұрын
Great problem troubleshooting video. Well explained step by step.
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Thank you very much! Your comment is very much appreciated🙏 Stay safe out there & stay tuned for new videos every week🔧
@romonek
@romonek 3 жыл бұрын
Nice tool bag
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Thank you! It's the Veto Pro Pac Tech LC🙂👍 Thank you & thank you for watching! Stay safe out there & stay tuned for new videos every week🔧
@SoutheastHVAC
@SoutheastHVAC 3 жыл бұрын
Awesome man! I just took a job that will potentially experience me to chillers like this. I’m coming from rack refrigeration. I’m stoked
@joecorbin5158
@joecorbin5158 3 жыл бұрын
Use a megaohm meter.. and test the wires!!!!
@JumpermanTech
@JumpermanTech 3 жыл бұрын
I couldn't find any grounded wires using resistance🤷‍♂️ Can you buy me one boss? 🤣 Thanks for watching!👍🔧
@alexschulein7002
@alexschulein7002 3 жыл бұрын
Sorry to say but I had to put a comment here, underneath the tower you had a split in a box, in that box bare copper and charring on the wire, did you fix that?? Didn't see you fix that, didn't hear you mention you fix that. You should have started ohming out the faulty side, would have saved you a couple of walks back and forth. You moved that flexible part of conduit, you could have temporarily negated the fault and made a bad conclusion. Just letting the breaker pop is bad fault finding, it's guessing. Read the manual of you meter and discover new faultfinding ways. I'm sure there is a continuity check on that meter, use it.
@neilvestervictor180
@neilvestervictor180 3 жыл бұрын
great troubleshooting
@brianchamblee8182
@brianchamblee8182 3 жыл бұрын
Like that you check what the customer said was true.
@JumpermanTech
@JumpermanTech 3 жыл бұрын
I learned that one the hard way a few times haha always need to check for yourself! Thank you for watching 👍🔧Stay safe out there & stay tuned for new videos every week
@izzybell11
@izzybell11 3 жыл бұрын
Great job. Helpful video. ⭐️⭐️⭐️⭐️⭐️
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Thank you very much! Much appreciated🙏 Thanks for watching! Stay safe out there & stay tuned for new videos every week🔧
@AlecMeijerinkNL
@AlecMeijerinkNL 3 жыл бұрын
I’d rather use an insulation tester on the wiring instead of having to try the breaker with live power. Seems to me like a much more safe way to work
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Couldnt find any grounded wires using resistance🤷‍♂️ Can you buy me one boss?👍 Thanks for watching!
@AlecMeijerinkNL
@AlecMeijerinkNL 3 жыл бұрын
@@JumpermanTech if I could, I would ;)
@JumpermanTech
@JumpermanTech 3 жыл бұрын
@@AlecMeijerinkNL 🤣🤣🤣
@lumconline3215
@lumconline3215 3 жыл бұрын
Can’t believe I watched this’ this dude is a dope
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Why can't you believe you watched this haha Thank you so much! & thank you for watching🙂 Appreciate this comment dude! Stay safe out there & stay tuned for new videos every week🔧
@KIRBZVIDS
@KIRBZVIDS 3 жыл бұрын
I really like your videos well expanded what your doing and epic views at work working on new youk roof tops 👌👍
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Thank you very much! I really appreciate your comment🙏 Thank you also for watching. I'm glad you like my videos and enjoy the footage🙂Stay safe out there & stay tuned for new videos every week🔧
@nicolerennie
@nicolerennie 3 жыл бұрын
great work!!🌟🌟🌟
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Thank you thank you! Much appreciated as always🙏 Stay safe out there & stay tuned for new videos every week🔧
@douro20
@douro20 Жыл бұрын
Any idea of the capacity of the chiller?
@eduardc5706
@eduardc5706 3 жыл бұрын
I worked in that cooling tower before 😅. This is 130 5th ave in the city.
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Maybe it looks similar but this is a different building lol Not far from where you are talking about!! 🤣🔧
@eduardc5706
@eduardc5706 3 жыл бұрын
It also had my old company sticker AFGO, that's why I said. 🤷🏻‍♂️
@JumpermanTech
@JumpermanTech 3 жыл бұрын
@@eduardc5706 It does have an old AFGO sticker👀 This account has been handled by a private contractor for the last 10 years or more🙂 Good eye & thanks for watching!🔧
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Dude another person just mentioned the same address as you! Haha
@sarahmarouaessalhi850
@sarahmarouaessalhi850 Жыл бұрын
What is electricity just to start?
@jfrancis98
@jfrancis98 3 жыл бұрын
Ohm it. Meg it. Why you no use amp meter while checking load on breaker?
@charlespaine987
@charlespaine987 Жыл бұрын
Would not the ohms meter / continuity been quicker and safer testing method
@borys444
@borys444 3 жыл бұрын
First video i have watched of urs and it’s excellent. What is the correlation between volts and amps? Assuming amps r supposed to present with volts? What happens if the volts r there and not the amps? Thanks 🙏
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Thank you so much! I appreciate you watching & leaving a comment🙏🙂 The correlation would be best understood after learning about "Ohms Law". This is what they teach in schools when learning about electricity. The correlation & take away would be as the voltage increases//Amperage decreases and vice versa - As voltage decreases//Amperage increases⚡Something to note: As the amperage increases so will your electrical bill!!!😅 Voltage is a measure of the pressure that allows electrons to flow, while amperage is a measure of the volume of electrons. It's quite tricky. I should make a video on ohms law🙂 Stay safe out there & subscribe for new videos every week🔧
@borys444
@borys444 3 жыл бұрын
@@JumpermanTech will do brother man, stay safe as well. Cheers!!
@Reefertech
@Reefertech 3 жыл бұрын
Please make a video on electrical, that’s always been tricky for me. ! Thank you great troubleshooting!
@EmpowerEngine
@EmpowerEngine 3 жыл бұрын
GOod job dude!!
@senbe4067
@senbe4067 3 жыл бұрын
nice video sir
@arcad1an292
@arcad1an292 2 жыл бұрын
Are you in NYC?
@joecorbin5158
@joecorbin5158 3 жыл бұрын
Self regulating heat trace...?
@jackjanuario9502
@jackjanuario9502 2 жыл бұрын
Con-Do-It
@JumpermanTech
@JumpermanTech 2 жыл бұрын
"Welcome to New Yawk"
@Novusilluminatus
@Novusilluminatus 3 жыл бұрын
Yo son what are you doing at express' cooling tower? LoL
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Express cooling tower? Lol what
@Novusilluminatus
@Novusilluminatus 3 жыл бұрын
@@JumpermanTech 130 5th ave is the address of the cooling tower. Am i right?
@JumpermanTech
@JumpermanTech 3 жыл бұрын
@@Novusilluminatus You're the 2nd person to mention that same address! It's not. This location is on Park Avenue👀 Must have the same setup
@Novusilluminatus
@Novusilluminatus 3 жыл бұрын
@@JumpermanTech we saw a sticker on the cooling tower of the company we used to work for lol
@JumpermanTech
@JumpermanTech 3 жыл бұрын
@@Novusilluminatus 🤣🤣🤣
@syedbasheer8210
@syedbasheer8210 3 жыл бұрын
💫💫💫💫
@JumpermanTech
@JumpermanTech 3 жыл бұрын
Syed!! My brother!! Thank you as always!🙏💫💫💫💫
@richardtillett9950
@richardtillett9950 3 жыл бұрын
THHN /THWN Stranded wire be better than that solid core wire. Looks like someone Didn't put the correct wire and put solid wire very terrible thing to put.
@JumpermanTech
@JumpermanTech 3 жыл бұрын
I very much agree with you! I ran solid wire before through conduit with bends as my boss didn't want me to buy stranded since I already had the solid in my truck and man oh man did I learn the hard way🤦‍♂️ Biggest pain in the butt and it was a mess. I understand to use it in places that code requires but man, I am NOT a fan of it haha I was wondering if this was correct. Thank you for the feedback & watching! Stay safe out there & stay tuned for new videos every week🔧
@user-wm7ez5ib6x
@user-wm7ez5ib6x 2 жыл бұрын
Где тебя учили!!!!!
@inthegovScoville-vo4jj
@inthegovScoville-vo4jj Жыл бұрын
Proto grounds
@inthegovScoville-vo4jj
@inthegovScoville-vo4jj Жыл бұрын
David organ trail
Air Conditioner Keeps Tripping Breaker... Stop Resetting it!
25:37
HVACR Survival
Рет қаралды 32 М.
Zombie Boy Saved My Life 💚
00:29
Alan Chikin Chow
Рет қаралды 25 МЛН
Running With Bigger And Bigger Feastables
00:17
MrBeast
Рет қаралды 157 МЛН
Cute kitty gadgets 💛
00:24
TheSoul Music Family
Рет қаралды 12 МЛН
Please Help Barry Choose His Real Son
00:23
Garri Creative
Рет қаралды 23 МЛН
THE BAR AC IS COOLING INSTEAD OF HEATING
22:34
HVACR VIDEOS
Рет қаралды 36 М.
RAYCHEM XMI Heating Cable Installation
15:55
nVent Thermal
Рет қаралды 16 М.
Crucial Knowledge To Heat Pump Troubleshooting
14:15
Jersey Mike HVAC
Рет қаралды 27 М.
Water Treatment Training for Cooling Towers, Chillers and Boilers
21:43
Cooling Tower Setpoint For Chiller
19:24
HVACTIME
Рет қаралды 36 М.
Warehouse Unit Heaters Not Heating
18:29
HVACR Survival
Рет қаралды 7 М.
На что способен ваш компьютер?
0:34
ПОЧЕМУ МИКРОФОНЫ ИГРОВЫЕ? 🧐
0:46
KEKTAR
Рет қаралды 746 М.
iPhone 15 Plus на Изгибе
0:59
Sergey Delaisy
Рет қаралды 165 М.
Сделал из зарядного устройства нечто!
0:48