Installing and programming a firelite CMF-300 control module

  Рет қаралды 13,329

NIC’S - SYSTEMS & ELECTRIC

NIC’S - SYSTEMS & ELECTRIC

Күн бұрын

Thanks for watching this is not a tutorial video just demonstrating my install and could be useful to fire alarm collectors

Пікірлер: 56
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
AB+ and AB- is for a class a loop I think and I apologize for calling the CMF-300 a CFM-300 that’s me being stupid 17:11 I meant to say the other ones metered 47 or close to but this one metered 36
@luis86910
@luis86910 2 жыл бұрын
What does it mean when green lit light stays lit ? Instead of blinking ?
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
@@luis86910 It means the control modules is active and turned on putting out power
@luis86910
@luis86910 2 жыл бұрын
@@nics-systems-electric right but it’s sending it to alarm
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
@@luis86910 No that does not put the system into alarm the system going alarm puts the control module into active
@lumenfirealarms
@lumenfirealarms 3 жыл бұрын
Hey I'm glad you followed my advice! And used the autoprogram function I told you didn't loose your information!! And you only need one 47kohms EOL that's why it only brings one but you connect on the other wire terminal you need to use the terminal where you put the EOL at the end of your video the other one doesn't need one! Stay safe and have fun! ...
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
So I need to put the NAC for the strobes on the terminals I installed the resistor later on?
@lumenfirealarms
@lumenfirealarms 3 жыл бұрын
@@nics-systems-electric yes you do, have fun! ...
@henrywilliam6325
@henrywilliam6325 3 жыл бұрын
That’s cool there’s so many different types of modules out there
@GeneBrodeJr
@GeneBrodeJr 2 жыл бұрын
Thanks for the in depth video. I came here to double check the wiring because the only cut sheet I could find at the moment was old and did not match the details I'm using for a project I'm designing. Looks like I have the right stuff.
@HJCF0520
@HJCF0520 3 жыл бұрын
Nice! I purchased a Milwaukee Fuel hammer drill/ impact drill kit a month ago and it is freaking amazing. Enjoy the heck out of it!
@marcberm
@marcberm 3 жыл бұрын
Maybe the green polling is to make it easier to tell a control module from a monitor module. Either way you're not crazy, any time we see stuff that's different from the usual it makes it kind of unique and neat to see. Keep at it! 👍
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
Yeah you’re probably right isolation modules may flash yellow not sure on that though but they do on notifier systems
@tmalley
@tmalley 3 жыл бұрын
@@nics-systems-electric they do
@techsavvydude
@techsavvydude 3 жыл бұрын
Nice! Good choice moving to red for your tools. I have the same 2853-20 and use the crap out of it. Holds up real nice.
@vrryan6
@vrryan6 3 жыл бұрын
Awesome, I really want to do this in the future
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
Ya that would be cool
@CJP_Productions
@CJP_Productions Жыл бұрын
I like this part( 6:07 ) I like the sounds of fire alarm enthusiast happiness :D
@nathanbirnofficial
@nathanbirnofficial 3 жыл бұрын
I see in the electrical section where the panel is there is a conduit party 😂😂 looks very professional
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
Yeah I’m running out of room in that area LOL
@VOLTRONDEFENDER4440
@VOLTRONDEFENDER4440 3 жыл бұрын
Nice that must be another adressable module but you actually stil need resistors it seems like on,y adressable pull station like the bg12lx don’t need resistors!
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
Yes because it’s turning addressable logic into conventional so it still has to monitor the conventional side in a conventional way which is using resistor values as far as the SLC none of the devices need resistors
@applebottomjeans7145
@applebottomjeans7145 3 жыл бұрын
one thing do you live in your garage
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
No not yet
@ryanwoods4691
@ryanwoods4691 3 жыл бұрын
@@nics-systems-electric Not yet...
@discjedi
@discjedi 3 жыл бұрын
@@nics-systems-electric I'd say you'd be pretty safe and secure in there 😄
@firekid1940
@firekid1940 3 жыл бұрын
Cool!
@FireAlert
@FireAlert 3 жыл бұрын
Nice! cool impact, Milwaukee is the best.
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
Yeah it’s a pain though because I like Milwaukee but I have some Makita tools and some Milwaukee tools
@DanTDMJace
@DanTDMJace 3 жыл бұрын
I have a question: Where did pickle come from in PICKLE 700 - SYSTEMS & ELECTRIC?
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
Just a random name I thought of honestly
@DanTDMJace
@DanTDMJace 3 жыл бұрын
Ok, I was just wondering.
@kevinmoran6220
@kevinmoran6220 Жыл бұрын
If you wired your strobes for your carbon monoxide separately on their own nac circuit on the panel, Go into nac programming it’s defaulted to zone 00,change that to match the zone on your carbon monoxides
@nics-systems-electric
@nics-systems-electric Жыл бұрын
That would be my first choice I can't remember the specifics of why I couldn't go with that but for some reason it didn't want to activate on supervisory
@kevinmoran6220
@kevinmoran6220 Жыл бұрын
@@nics-systems-electric Oh I hear you that does get complicated. You’d have to change things in zone reporting and all that total pain
@nics-systems-electric
@nics-systems-electric Жыл бұрын
@@kevinmoran6220 yeah I don't remember the specifics but it was something along the lines of that but it was much easier to just program the control module I'm sure it is possible with the unboard nac's but I think it was a lot more difficult than it was worth
@fst1775
@fst1775 3 жыл бұрын
Nice install!
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
Thanks
@chacehood
@chacehood Жыл бұрын
I’m confused. The cut sheet says to use the bottom terminals. T7 & T8 for class B with eol. You didn’t do that. How did it work?
@nics-systems-electric
@nics-systems-electric Жыл бұрын
Yes that is incorrect I believe that's why I added the resistor on the other terminal possibly
@firealarm300andmore4
@firealarm300andmore4 3 жыл бұрын
Cool
@nateh4190
@nateh4190 2 ай бұрын
Solid green on crf indicates what?
@nics-systems-electric
@nics-systems-electric 2 ай бұрын
Solid green on a control module means it's active
@calebmorand4604
@calebmorand4604 Жыл бұрын
Does this module supervise the auxiliary power being fed to it? Or do you need an end of line relay to supervise the auxiliary power? I appreciate your help!
@nics-systems-electric
@nics-systems-electric Жыл бұрын
l will look into that give me a couple days maybe leave me another comment again in a couple days from now to remind me and I'll let you know
@calebmorand4604
@calebmorand4604 Жыл бұрын
@@nics-systems-electric hello. Where you able to find out if the cmf-300 needs a power supervision relay for the 24vdc aux power? Thanks!
@safetyzone2962
@safetyzone2962 3 жыл бұрын
2nd Like
@mewing-gawd
@mewing-gawd 3 жыл бұрын
You forgot the resisters
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
And then I put it in and it was fine I just didn’t realize it needed 2
@vrryan6
@vrryan6 3 жыл бұрын
GREEN POLLING!
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
I know right it’s so cool for some reason maybe I’m just crazy
@vrryan6
@vrryan6 3 жыл бұрын
@@nics-systems-electric i think it flashes green to differentiate if its a monitor or control but someone will have to fact check me on that
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
@@vrryan6 probably. isolator modules might flash yellow that might just be notifier though
@vrryan6
@vrryan6 3 жыл бұрын
@@nics-systems-electric Cool, if I do this I want to use a system sensor co detector and use 2 Gentex commander 3 yellow/white horn strobes on whoop.
@nics-systems-electric
@nics-systems-electric 3 жыл бұрын
@@vrryan6 that be cool
5 Story Building - Backbone of the SLC
7:09
Joe Klochan
Рет қаралды 40 М.
❌Разве такое возможно? #story
01:00
Кэри Найс
Рет қаралды 3,2 МЛН
How to add a monitor module/pull station to a already programmed fire alarm system
16:04
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 10 М.
23 - Monitor Modules - Introduction to Fire Alarms
9:45
Joe Klochan
Рет қаралды 96 М.
home made Fire alarm communicator for under $100 no phone line, no sim card, no subscription!
33:25
Damper Relay Wiring
2:58
Pyrotex Systems
Рет қаралды 39 М.
Fire sprinkler flow switch monitor module install, programming and testing
37:16
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 9 М.
32 - Metering a Ground Fault - Introduction to Fire Alarms
16:03
Joe Klochan
Рет қаралды 60 М.
39 - Elevator Shunt Trip - Introduction to Fire Alarms
13:08
Joe Klochan
Рет қаралды 47 М.
What is a Fire Alarm System?
11:06
RealPars
Рет қаралды 2,1 МЛН
Fire-Lite Addressable Panels - SLC Issue Discovery
23:55
Drew Whitehead
Рет қаралды 19 М.
Making a Heated Seat
12:09
ElectroBOOM
Рет қаралды 13 МЛН