Live Incomer Tests at a 3 phase DB - AM2, AM2s, AM2e, 2391 Inspection and Testing Course

  Рет қаралды 3,107

Heads Up 4 Sparkies

Heads Up 4 Sparkies

Жыл бұрын

This video explains in detail, the requirements for carrying out live electrical testing at the incoming supply of a 3 phase distribution board. This is very useful for apprentice electricians about to take AM2, AM2s, AM2e end point assessments. Also for career CPD for electricians, and for electricians undertaking C&G 2391 Inspection & Testing Course.

Пікірлер: 24
@sports872
@sports872 Жыл бұрын
Enjoyed the video. Would like to see more testing videos if possible.
@headsup4sparkies
@headsup4sparkies Жыл бұрын
More to come!
@lewiswebb1843
@lewiswebb1843 8 ай бұрын
Thanks mate, got my am2s this Monday and this is spot on 👍🏻
@pvegod1484
@pvegod1484 Ай бұрын
Did you pass it mate? I’ve got mine in a couple week bricking it
@lewiswebb1843
@lewiswebb1843 Ай бұрын
Yea passed 1st time mate 👍🏻 I’ll be honest, if your here looking up videos to pass then you’ll probably be one of the guys that will pass either 1st time or on a return attempt 👍🏻 good luck 🤞🏻
@detroutspinners9933
@detroutspinners9933 Жыл бұрын
Brilliant video, really appreciate the time taken to animate the test sequences as well. Helps to visualise what you’re doing so much better!
@headsup4sparkies
@headsup4sparkies Жыл бұрын
Thank you 🙏.., I’m glad you found this helpful 😀
@user-cs9ch8ey9k
@user-cs9ch8ey9k 11 ай бұрын
Excellent video as always, thank you.
@headsup4sparkies
@headsup4sparkies 10 ай бұрын
🙏 Thank you .. hope it has helped ..
@monikacieminska5380
@monikacieminska5380 9 ай бұрын
Fantastic video. Thank you 👌😀
@headsup4sparkies
@headsup4sparkies 9 ай бұрын
Glad you found this useful 😀
@brianhewitt8618
@brianhewitt8618 Жыл бұрын
excellent 👍
@headsup4sparkies
@headsup4sparkies Жыл бұрын
Thank you! Cheers!
@glenngray3351
@glenngray3351 11 ай бұрын
Hi I am having a few issues on identifying the types of wiring and reference method on the Generic schedule of circuit details. Can help or advise please?
@headsup4sparkies
@headsup4sparkies 11 ай бұрын
This can be simple - or complex, depending on the variety of methods employed on the route. You can select the most used method on the route / the method with most detrimental effect .. or so on. The inspector should use engineering judgement to decide … this link to IET - Supporting BS7671 Appendix 4 .. might help electrical.theiet.org/media/1617/appendix-4-of-bs-7671.pdf
@azadsmail8
@azadsmail8 23 күн бұрын
Hi nice vid but I noticed that the highest reading is PEFC 950.3 this one should be doubled and recorded not the PSCC am I right? THANKS
@headsup4sparkies
@headsup4sparkies 11 күн бұрын
Hi … When testing between Line and Neutral (PSCC), the voltage potential is 230V .. we double this to allow for the PSCC between Line conductors as these would have a potential of 400V. The maximum potential to earth (PEFC) is 230 so therefore is not doubled. You only double the highest PSCC value.
@Rossisearle
@Rossisearle 11 ай бұрын
helpful but surely that Zdb your say is Ze because the is the 3 phase dno supply? is zdb would be at 2nd or 3nd distribution circuit ? ASKING
@headsup4sparkies
@headsup4sparkies 11 ай бұрын
Hi … If the board is at the origin of supply - then Zdb and Ze would be the same. Ze recorded on certificate and Zdb recorded on schedule of test results. If there is a sub main between the origin and the board under test .. then Zdb is measured at board with earth disconnected - and Ze from origin recorded on the certificate.
@headsup4sparkies
@headsup4sparkies 11 ай бұрын
The distribution board at the origin supplying the sub main, would also record this supply’s Zs on on it’s own schedule of test results, taken in the same manner but with the earth connected.
@headsup4sparkies
@headsup4sparkies 11 ай бұрын
The board in the video is assumed not to be at the origin of supply … Hope this helps 👍🏻
@Rossisearle
@Rossisearle 11 ай бұрын
​@@headsup4sparkies right... So like a three phase distribution circuit?
@headsup4sparkies
@headsup4sparkies 11 ай бұрын
Yes … we call them “Sub-Mains” when we distribute the supplies from DNO to distribution boards… and the circuits from there are “final sub-circuits” supplying current using equipment without further distribution.
FAULT FINDING - RING CIRCUITS
15:38
LEARN ELECTRICS
Рет қаралды 40 М.
Steel Conduit Bend, Set and Measure AM2s
15:42
Heads Up 4 Sparkies
Рет қаралды 136 М.
Заметили?
00:11
Double Bubble
Рет қаралды 3 МЛН
ХОТЯ БЫ КИНОДА 2 - официальный фильм
1:35:34
ХОТЯ БЫ В КИНО
Рет қаралды 2,7 МЛН
am2 am2S am2e writing out the Electrical Installation certificate
49:25
Completely Electrical's STEM show
Рет қаралды 7 М.
Fault finding on a S plan wiring system
4:48
Ian Hall
Рет қаралды 11 М.
S Plan with Solar Thermal Wiring AM2 and AM2s
6:48
Heads Up 4 Sparkies
Рет қаралды 8 М.
Electrical Channel - Testing Sequence - Dead
8:19
Warrington & Vale Royal College Electrical Training
Рет қаралды 99 М.
QR code 7 -- Three phase insulation resistance test
5:03
Companion Websites
Рет қаралды 172 М.
AM2 Assessments - DO's and DONT's ✍️
18:01
Scolmore Group
Рет қаралды 13 М.
Live testing
10:58
Paul Lansdowne
Рет қаралды 10 М.