Most Powerful Inverter Generator On The Market. Initial Load Test!

  Рет қаралды 22,715

HVAC GUY

HVAC GUY

Күн бұрын

In this video I go over the new DuroMax 16 kW Inverter Generator! #hvacguy #generator #generatormaintenance #generatorepairing ‪@DuroMaxPower‬ #duromax16000ih #electrical #electricalengineering #backuppower #prepping #wholehomebackuppower

Пікірлер: 101
@Critical-Thinker895
@Critical-Thinker895 Ай бұрын
The manual will tell you to run with eco off when powering items with a heavy surge. You have several of those. The problem is the eco mode cannot increase the rpm fast enough to deal with surge so it tries to make up using the inverter output and that drives it into overload. Just leave eco off to run your whole house.
@SmokyRibsBBQ
@SmokyRibsBBQ 3 ай бұрын
We live on the Mississippi coast and have had our problems with hurricanes over the years. This would be a great set up to have! Thanks for the video!
@HVACGUY
@HVACGUY 3 ай бұрын
Those hurricanes are no joke. We don’t see them as often as y’all. But, they still affect us, sometimes in a major way.
@jthonn
@jthonn 3 ай бұрын
I am near you, so I know your pain first hand.
@CloverWoodDIY
@CloverWoodDIY Ай бұрын
We just got hit by Beryl and my old genny quit powering my central HVAC. Decided today get a DuroMax 13kw tri-fuel. Yeah, the inverter would have been a better option but it’s also $3000 more. Long term, that’s the goal, but for now the 13kw will get us through the storms.
@Hullspeed
@Hullspeed 3 күн бұрын
Thanks for testing the Central HVAC and showing us how it worked! That's exactly what I'm interested in. I would love clean power but I'm concerned about motor starts on an inverter. This looks very promising; I was amazed that you could start the outdoor compressor on low idle.
@jthonn
@jthonn 3 ай бұрын
That is awesome. It covered the house with power to spare. Compared to most generators, it wasn't that loud. I don't know if you have natural gas, but if it can be converted, there would be no need to run for propane. I don't know if it is true for that one, but they claim you have to give them a cool down period every 4 hours. I have used generators before, but nothing of that magnitude. It looks like a badass machine to me. Thanks for sharing.
@bigblue3568
@bigblue3568 2 ай бұрын
Propane is KING in mass emergency situations. Propane can be stored indefinitely. Houston TX folks learned the hard way when they lost their natural gas supply due to frozen natural gas wells which rendered their house generators useless during that big freeze few years ago and several other times. Other areas in the states experienced the same after storms and hurricanes. His 16K kW is over kill for his needs though and will just needlessly burn up more of whatever his fuel choice is.
@Moondoggy1941
@Moondoggy1941 11 күн бұрын
@@bigblue3568 The best thing about Tri Fuel is three choices and opportunities, I understand why most manufactures do not want to do the Tri, natural gas system vary from region to regions, state to state, there is dominium requirement. The human factor is always the big X factor, DIY, semi pro aka expert have a big influence on how will it will work with Nat. Gas.
@CommercialGasEngineerVideos
@CommercialGasEngineerVideos 3 ай бұрын
Now that's a generous generator
@RichardDombakly
@RichardDombakly 24 күн бұрын
Hey commercial wiseguy good Line though!
@jackl9922
@jackl9922 3 ай бұрын
I run my Honda with ECO off, since a motor or compressor sags the voltage too long when starting. Great job!
@HVACGUY
@HVACGUY 3 ай бұрын
Great tip!
@robalexander7348
@robalexander7348 3 ай бұрын
Well done Curtis, that is a nice capable generator 👍 Au
@rexharvey8420
@rexharvey8420 Ай бұрын
Love your Wymarana! Geni looks pretty good too!
@dontbanmebrodontbanme5403
@dontbanmebrodontbanme5403 18 күн бұрын
I'm looking for a more powerful generator and was looking at a whole house generator, but the sticker shock was making me look elsewhere. I had no idea inverter generators have increased their power this much and I might just go this rourte. Great video!
@ChatGPT1111
@ChatGPT1111 2 ай бұрын
I have the 13kw dual fuel Duromax as a backup to my 22kw Generac whole house genny. These are nice units.
@Robnord1
@Robnord1 3 ай бұрын
Man, that's a monster!!! I don't plan on using my new 7500W tri-fuel Firman generator ($700 @Costco) on gasoline either. Maybe I'll run it one time on gas just to be sure the carb works and run it dry. Should we be putting anything in the fuel tank to prevent rust? Fogging oil or swish around a little Marvel Mystery Oil maybe?
@jthonn
@jthonn 3 ай бұрын
That is a good idea. You can keep gas in it and add fuel stabilizer. If you do, change it out once a year.
@Robnord1
@Robnord1 3 ай бұрын
@@jthonn Yeah, that may be the best plan. I guess even with a coat of oil of some kind, air would condense some moisture in there long term. I do keep a good amount of non-ethanol fuel with stabilizer on hand, and rotate it regularly, so adding the generator to the rotate list is not a big deal. Thanks for your input.
@OcRefrig
@OcRefrig 3 ай бұрын
wd-40 in fuel tank will keep tank from rusting. Wd= water displacement.
@kens.3729
@kens.3729 3 ай бұрын
Our Power Company in STL Cut Tree Trimming Program causing Major Outages after 2006 Tornado and 2006 Ice Storm. Installed Natural Gas Generator, 12/2006.
@herewegoagain4041
@herewegoagain4041 Ай бұрын
Cost to run natural gas vs gas station gas per day
@TripleMachine
@TripleMachine 2 ай бұрын
That monster is going to swallow that tiny propane tank like nothing.
@knightwalker6561
@knightwalker6561 3 ай бұрын
low idle mixture is to lean also that tank is only about the equivalent to 4.5 gallons of gasoline
@paultice610
@paultice610 3 ай бұрын
That is a big giant beast all I have are two predator 3500s in parallel so I can get 50 A at 120 V and I just run a couple of window shakers and it runs my other stuff that I need just fine, but I don’t have many 240 V items in my house. My hot water heater is natural gas. Basically just my stove and my dryer. I can’t use in a power outage, but I have a hot plate and a microwave that is good enough to cook with in a power outage maybe one day I can get a big one like that
@OcRefrig
@OcRefrig 3 ай бұрын
@ paultice - Get a Propane barbecue for power outage & Normal life too. Also - air con - Mini splits - 12,000 btu are 115 volt now. Heat pumps too. Norcal refrigeration just installed one. $875.00 amazon.
@OcRefrig
@OcRefrig 3 ай бұрын
Get a used gas dryer. $50.00 a lot cheaper than electric to run. can be run on propane too. i've done it. no mods necessary. i've done it. works great. i just used an air hose as a propane hose. worked great. no air leaks = no propane leaks.
@throttlebottle5906
@throttlebottle5906 3 ай бұрын
@@OcRefrig hehe, yo man. I have natural gas here, but keep propane around and have generators. yeah, I mainly use one of the two bbq grills when power is out(not in storms), natural gas and propane grills both. but generators will run a microwave if needed, gas stovetop can be lit with no power(lighter/match) if need be. the oven needs power to make ignitor glow and gas valve(thermally open), stupid "newer ovens" yeah newer means early 90's on lol.
@johnwalker890
@johnwalker890 3 ай бұрын
Good deal Curtis, Yeah propane burns cleaner than gasoline, but less rpms, if you use the gasoline on the generator it will stink it up like a leaky car.......
@BigDaddy_MRI
@BigDaddy_MRI Ай бұрын
During break in, you should use non-synthetic oil. I thought I saw Mobile 1 but I could be wrong. Also, heavy inductive loads you should turn ECO mode off so that there’s no surge on the inverter system. After break in I think you can switch it back on. If there’s a surge over a certain value the inverter will trip off to protect itself. So during summer when the A/C kicks on, ECO off will allow the inverter to pull that power it needs with no surge. Finally, if you have issues with the engine having hard start after break-in, put Bosch platinum plugs in the engine. Those Chinesium plugs are NFG. A friend did that in his generator and fixed a multitude of problems he was having with the engine. He has a Harbor Freight 9,500 watt generator. Excellent video. Thanks for bringing us along.
@brianbyers2682
@brianbyers2682 Ай бұрын
WRONG!! 99.9% of all new engines come with synthetic oil
@BigDaddy_MRI
@BigDaddy_MRI Ай бұрын
@@brianbyers2682 Well, that is what the operating manual says. You do what you need to do. Fine with me.
@MrWeldWell
@MrWeldWell Ай бұрын
@ brain trust 2682 The non-synthetic oil is best for breaking in to seat the rings. After break in, the synthetic oil will work well because of its heat tolerance and longer life, which comes in handy when people who think they know it all forget to be diligent in their maintenance during an emergency. ;-), but I'm sure you will go ahead and do what you need to do!
@donls1sscme
@donls1sscme 21 күн бұрын
​@brianbyers2682 your wrong small engines should be run on conventional oil and the manuals say that
@Moondoggy1941
@Moondoggy1941 11 күн бұрын
@@donls1sscme As someone else has spoken I have taken it to heart, It is not the quality of the oil that is important but the frequency of the oil.
@jimharmon3404
@jimharmon3404 3 ай бұрын
Check the manual for that system. I think you need a bond to ground via a ground rod right at the generator. Also check the grounding requirements of your electric provider and ask a local licensed electrician. Calculate propane consumption perhour and then the expected time backup power is needed. That will help you decide how big a tank you will need to have filled up. My preference would be using Natural Gas. The last time I had lost power it was about 10 days.
@bennyrussell5551
@bennyrussell5551 3 ай бұрын
Invertor is much quieter than a open frame (contractor generator)
@fgcchevy
@fgcchevy 3 ай бұрын
Can you post links for everything you used to plug it into the house please?
@m9ovich785
@m9ovich785 3 ай бұрын
High idle as You stated is not an idle at all. It is running the Engine at full 3600 RPM... When You were running low RPM The inrush currents were to much for Propane to overcome.
@throttlebottle5906
@throttlebottle5906 3 ай бұрын
when the power is out here, I go with minimal needed equipment/lighting powered on. well pump, some lighting, fridge/freezer and cooking appliances( one microwave and gas oven) although I will generally just use the gas grill outside, unless storming bad. the rest is un-needed, but handy. I don't bother with backup power unless it out or is said to be out for more then two hours.
@mikem5823
@mikem5823 3 ай бұрын
you may need a bigger tank of LP , once you start to get above 5Kw you need allot more gas , that small tank may not be able to produce GAS lp fast enough. there is a kit I seen to connect 2 tanks together to supply enough GAS..
@throttlebottle5906
@throttlebottle5906 3 ай бұрын
an little 18lbs cylinder is useless for all generators, except for when full and very short testing. for a generator that size to be of any use, you'd need minimum of 500lbs tank (for about few days low power usage) want to use lots of power? better get 1000+ gallon tanks(multiples or larger!)
@spockmcoyissmart961
@spockmcoyissmart961 21 күн бұрын
These large gens are great for short term use. 1-2 days. Now paying for and storing enough fuel for the long term is another story. I would like to see a 20lb tank hooked up and time run time. This will help to calculate larger tank size and run time in emergency.
@Eddy63
@Eddy63 3 ай бұрын
Nice product & nice demo ... Thx
@harrydickson4575
@harrydickson4575 3 ай бұрын
👍👍👍
@jeffhagberg6796
@jeffhagberg6796 3 ай бұрын
I've found on inverter generators that when pulling hard starting things keeping it on hi idle is better For the generator. I have a 8500 watt DuroMax generator runs my house well. The new heat pump ,I installed a soft start on it haven't tried it yet but I hope things work well on the generator and Ac. Curtis what do you think about the soft start add on?
@JJDuval
@JJDuval 3 ай бұрын
I would also like your opinion on a soft start I have an old trane 3 ton that would probably need one with my 10000/8000 duromax genny
@HVACGUY
@HVACGUY 3 ай бұрын
I haven’t used many. I’ve heard lots of cautionary tales, but have never actually seen one cause harm to a system.
@throttlebottle5906
@throttlebottle5906 3 ай бұрын
HINT! when heat-pumps go into "defrost mode", they generally, change the reversing valve to "air conditioning" mode to de-ice the condenser coil, while they BANG the "electric heat strips" on full power to keep it from blowing cold air inside the house. that is more than most all generators will handle. there are cases where it can work if the backup heat strips are on multiple breakers and the highest current breaker can be left OFF, as to not overload the generator. but it all depends on the homeowner knowing/recalling to only turn on certain breakers/loads when on gen power. as for "soft start/start setup" on compressor/motors, yes if sized proper and system is in good working order, they can lower the peak start current and shorten it by far.
@JJDuval
@JJDuval 3 ай бұрын
@@throttlebottle5906 well for me being in fl I would only be using it during hurricane season so heat strips would not be a problem
@kg4muc
@kg4muc 3 ай бұрын
At times I wish my Honda was inverter but it manages clean enough power to handles my audio and video equipment as well as my computers. Talk about your 50 amp cable being heavy all I had when I wired mine here was 4/0 UG 😅 The 50 amp breaker might trip but the ug won’t burn up lol Glad I did utility work in a previous life so I had the Burndy crimp tool and plenty of block splices lol
@addminusDIY
@addminusDIY 26 күн бұрын
Nice quiet duromax
@bigblue3568
@bigblue3568 2 ай бұрын
Propane is King during any mass emergency situation. Propane can be stored infinitely and is reliable unlike gas and natural gas supplies. IF a potential long lasting power outage occurs no matter what fuel choice selected it will be highly sought after and in low supply so its best to not waste any of it such as using oversized generator producing power you don't need nor will ever use. No need to power entire house and cooling every room using homes central air.. Best to select a room such as master to use as a temp living area to stay cool, add it to one of your circuits of choice for power. Pick out a nice size window AC unit or portable one to use along with a moderate size generator in the 6500 kw size to power it along with few other circuits such as well pump, fridge etc.
@condor5635
@condor5635 Ай бұрын
Exactly my take too. Thats what I did. Small 8,000 btu window unit. 6,000 watts running generator, 2 refrigerators, lights, fans and 45 gallons of gasoline (get it BEFORE the storm :) ...
@user-qd3pi5ji7q
@user-qd3pi5ji7q 3 ай бұрын
Wondering the kW cost when using propane. Is this cheaper than the outrageous rates the power company now charges?
@CommercialGasEngineerVideos
@CommercialGasEngineerVideos 3 ай бұрын
Good point
@throttlebottle5906
@throttlebottle5906 3 ай бұрын
NO, they suck propane down like it's free water in the middle of an huge drought... :)
@ArcadiyIvanov
@ArcadiyIvanov Ай бұрын
Not supposed to use Low Idle with house backup hookup - it's right there in the manual describing the function of that button.
@user-oj1ri5ld3x
@user-oj1ri5ld3x 3 ай бұрын
Running on propane you don't change the as often as you would on gasoline on propane it runs so clean
@ChatGPT1111
@ChatGPT1111 2 ай бұрын
Just heard the Trifuel (incl NG) version of this model is coming out. Wish I had waited instead of getting the 9KW Champion Tri Inverter. But it was only $1350 so I can get two.
@dong4617
@dong4617 3 ай бұрын
What did you do with you Predator inverter? It would work fine unless you turned on everything.
@HVACGUY
@HVACGUY 3 ай бұрын
Sold it
@oceanmariner
@oceanmariner 3 ай бұрын
Propane is less powerful than gasoline, so you'll go thru propane faster than gas. But propane doesn't go bad from sitting and gum up the carburetor like gas does. So with propane it can sit for years and start right up. I work with marine diesel generators. You may need some hard start kits on some motors if you're marginal on power.
@throttlebottle5906
@throttlebottle5906 3 ай бұрын
good information for those not unknowing.
@ChatGPT1111
@ChatGPT1111 2 ай бұрын
You mean soft start kits.
@MrWeldWell
@MrWeldWell Ай бұрын
Hard start capacitors appear to be more effective and cost-efficient than soft starts for AC compressor motors. After installation, I observed a more than 50% decrease in amp draw for both starting and running units. (4 ton)
@MrWeldWell
@MrWeldWell Ай бұрын
@@ChatGPT1111 Hard start capacitors appear to be more effective and cost-efficient than soft starts for AC compressor motors. After installation, I observed a more than 50% decrease in amp draw for both starting and running units. (4 ton)
@richmurphy1787
@richmurphy1787 2 ай бұрын
At 9000 W at 240 V you’re pretty much at 47 A on that one circuit you need to hook up the other 50 amp cord.
@OcRefrig
@OcRefrig 3 ай бұрын
Cool Generator. What about Trying to use the Broiler in the oven or the stove top To Boil a Pot of Water for Spaghetti. a Propane Barbecue , That Generator & a 100 or 200 gallon Propane tank & You are all set for a Week or 2 without power. Smart man not filling with gasoline. that way you don't have to worry about gumming up the carb etc. i would not use gasoline either unless You have to. just takes all that gasoline & varnish out of the equation. You should try living with it for a Weekend once & see what happens. it would be interesting. see how long a 5 gallon propane lasts. You could use refrigerant scale figure 1 lb of propane for how much time.
@throttlebottle5906
@throttlebottle5906 3 ай бұрын
also to note, you should do a fair break in period before applying the house load/equipment. run full speed no load for a while( 20-30 minutes), then apply half load for 20-30 minutes (portable heaters work well, outdoors, in cooler weather). then vary the load from about half to 3/4. stop and change oil! (units with or especially without oil filter/pressurized lube).
@Moondoggy1941
@Moondoggy1941 11 күн бұрын
All electric house, he needs to go big on the inverter.
@erickweinzapfel196
@erickweinzapfel196 Ай бұрын
Do you recommend soft starts for your AC units? Great video. Thanks
@dontbanmebrodontbanme5403
@dontbanmebrodontbanme5403 18 күн бұрын
I just checked the price. $5K? Uggghhh....that's expensive, but might still be worth it.
@condor5635
@condor5635 Ай бұрын
Love this generator just don't understand why they don't make it tri-fuel. Most folks would want to run NG on this.
@peter-pg5yc
@peter-pg5yc 3 ай бұрын
Here in san jose power outage you lose cell phones too. wifi is nope..
@user-oz6xr4wo7d
@user-oz6xr4wo7d 3 ай бұрын
Turn on the inverter devices on it economical in electricity. Regular air conditioners consume high current while they and electric heaters are starting their work. etc
@joemesser2681
@joemesser2681 3 ай бұрын
Propane tank should be a 30lb minimum
@HVACGUY
@HVACGUY 3 ай бұрын
Hmm. Could be why I had those difficulties. I have two large tanks. I’ll try them next.
@Robnord1
@Robnord1 3 ай бұрын
Those 20lb tanks are much easier for women to handle than 30s or 40s. I got lots of 20lb tanks so my wife can change them easily if I'm not around. Could the regulator ice up on a long, hard run in a very cold and humid climate more easily on a 20 lb tank? Yes it could...but wrapping a tarp or blanket around it alleviates the problem unless you're in North Dakota or Canada maybe.
@throttlebottle5906
@throttlebottle5906 3 ай бұрын
@@Robnord1 it's not just the issue of regulator icing up, as the whole tank will ice up and the pressure drop too low to supply it anymore. in general any high volume using device needs an large tank and should ever be let run to below 40% fuel level! (yes all will often be ok to 25 to 35% range, on 1000+ gallon tanks). tiny tanks and high draw devices will fail at 70% or more of fill volumes, as they just cannot supply that much, nor the peanut regulators.
@Robnord1
@Robnord1 3 ай бұрын
@@throttlebottle5906 That's interesting. Small tank freeze-ups have not been an issue here in my part of western WA, where winter temps rarely dip under 20 deg F. Maybe I haven't experienced either regulator or tank freeze-up because our generator (6700 run Watts on LP) probably draws under 40K BTUs. Next winter I'll hook up one of my 20s to my home, which can exceed 100K BTUs, with everything on and see if it fails on a frosty day. Thanks for mentioning it. I'd rather find a problem now than in the middle of an extended grid down emergency situation.
@throttlebottle5906
@throttlebottle5906 3 ай бұрын
FYI an 18LBS propane tank isn't big enough to supply it ever(other than full tank short test/low output) otherwise you'll want minimum of an 500 gallon tank or far larger to feed it for any real sustainable usage in an power outage.
@chris-ij4vc
@chris-ij4vc 2 ай бұрын
As far as I know you can't use propane & low idle that's for gas only &. According to instructions
@TexasNightRider
@TexasNightRider Ай бұрын
What Is The THD Rating?
@edpippin
@edpippin Ай бұрын
Will it convert to natural gas?
@rustyBdTZ
@rustyBdTZ Ай бұрын
think it would start a 3 ton rheem LRA 79?
@happyyardservice2914
@happyyardservice2914 2 ай бұрын
After adding oil, throw away that battery and hook up a normal car battery that has a solar charger hooked up to it.
@MrWeldWell
@MrWeldWell Ай бұрын
Hard start capacitors appear to be more effective and cost-efficient than soft starts for AC compressor motors. After installation, I observed a more than 50% decrease in amp draw for both starting and running units. (4 ton)
@condor5635
@condor5635 Ай бұрын
How can you see a 50% reduction in running of an AC using a hard start? I understand the starting reduction.
@prestonthomas9406
@prestonthomas9406 Ай бұрын
Strange Duro-Max doesn’t recommend break in with gasoline. I have a 12000 dual fuel Duro-Max and the manual recommended running for 5 hrs with gasoline to break it in. Anyway…
@caroleemoreno8086
@caroleemoreno8086 17 күн бұрын
They are so nice but too pricey for me.
@mikeburchett-bs3qw
@mikeburchett-bs3qw 11 күн бұрын
Not tri fuel that’s just nuts why not is the question
@schrodingersmechanic7622
@schrodingersmechanic7622 Ай бұрын
$5000 msrp, ouch. $6300 will get you a Kohler stationary unit with an auto transfer switch. A competent DIY'er can install either themselves if they do their homework. Not sure this makes sense at this price point
@jamesballard2335
@jamesballard2335 3 ай бұрын
You didn't mention that you satisfied
@RDM-346
@RDM-346 22 сағат бұрын
DO NOT BUY DUROMAX GENERATORS UNTIL THEY HAVE PARTS AVAILABLE. NO PARTS ON WEBSITE OR AMAZON, NOWHERE ELSE. CORRECT ME IF I'M WRONG
@JetFire9
@JetFire9 11 күн бұрын
Any company that makes big generators that work on propane, but not natural gas, should face massive fines and jail time for all executives and board members and their families and childhood friends.
@TLeightonWomack
@TLeightonWomack 3 ай бұрын
You should never use synthetic oil to break in a small engine.
@MrWeldWell
@MrWeldWell Ай бұрын
The non-synthetic oil is best for breaking in to seat the rings. After breaking in, synthetic oil will work well because of its heat tolerance and longer life. ;-)
@speedwayman100
@speedwayman100 13 күн бұрын
I'd have thought these invertor generators would be quieter than that,not much difference between that and a typical generator as far as sound but price i could get two regular generators as compared to one of these.
Whoa
01:00
Justin Flom
Рет қаралды 13 МЛН
Schoolboy Runaway в реальной жизни🤣@onLI_gAmeS
00:31
МишАня
Рет қаралды 3,6 МЛН
لااا! هذه البرتقالة مزعجة جدًا #قصير
00:15
One More Arabic
Рет қаралды 52 МЛН
SPONGEBOB POWER-UPS IN BRAWL STARS!!!
08:35
Brawl Stars
Рет қаралды 16 МЛН
Propane Generator Fails You Keep Making!
10:30
JOHNNY'S WEEKENDS
Рет қаралды 41 М.
Soft Start Killed Compressor! UNEDITED Central AC Service Call for No Air Conditioning Revealed!
14:20
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 203 М.
Cheap vs. Expensive Generator (Surprising Results)
25:49
Ambition Strikes
Рет қаралды 634 М.
Home Warranty Calls Me After Another Company Couldn’t Fix It
36:23
Will running on a generator damage your house? Inverter vs standard vs standby
29:33
Duromax XP9000ih 9000 Watts Inverter Generator Running a 5-TON AC
8:02
Gavin’s Garage
Рет қаралды 40 М.
Best RV Generator Option! Parallel Generators Vs Large Generator.
11:06
Whoa
01:00
Justin Flom
Рет қаралды 13 МЛН