2023 NEC Box Fill Lesson

  Рет қаралды 4,961

My Fortress Construction

My Fortress Construction

Күн бұрын

Box fill calculation doesn't have to be difficult. There are four primary things to add together to get the total volume in cubic inches needed for all wire and devices:
#1 A Conductor counts as 1 conductor volume (unless its +12" then it counts as two)
#2 Grounds count for 1 conductor volume until you reach 4 then each additional ground = .25
#3 All internal cable clamps count as 1 conductor volume (there is debate as to which field added clamps count into the equation so it is safer to add any that protrude into the box)
#4 Each Yoke (switch or receptacle) counts as 2 conductor volumes unless the yoke takes up two gangs, which then makes it count as 4.
A less common situation would be a stud or hickey needing to be calculated into the box fill. A stud is a threaded rod which will support a luminaire like a Chandelier. A hickey is a type of support nut that would generally thread onto a stud and act as a coupling. They both require a single conductor volume to be added for each one in the box. You only add them if they are attached to the strap and enter into the junction box.
Another thing to consider would be if you have 14/2 NM cables coming into a junction box and one 12/2 NM cable coming in, you would have to rate all of the 14 gauge conductors as 12 gauge and multiply by the 12 gauge volume allowance. If you had a single 12 gauge ground then only the grounds would be multiplied by the 12 gauge column, and not the conductors. Conductors and grounds are figured separately.
Box Fill Volume multiplier for each conductor size:
18 gauge = 1.5 cu.in.
16 gauge = 1.75 cu.in.
14 gauge = 2.0 cu.in.
12 gauge = 2.25 cu.in.
10 gauge = 2.5 cu.in.
8 gauge = 3.0 cu.in.
6 gauge = 5.0 cu.in.
0:00 Introduction
0:19 Box Fill For Beginners
4:21 Summary of Basic Box Fill Calculation
5:01 1st Practice Box
6:47 2nd Practice Box
7:21 3rd and 4th Practice Boxes
8:50 5th Practice Box
10:12 6th Practice Box
11:03 FINAL BOX
15:03 Summary
15:20 Rant Dance

Пікірлер: 10
@jaxonprice7962
@jaxonprice7962 6 ай бұрын
great video helped me out a lot!!!
@MyFortressConstruction
@MyFortressConstruction 6 ай бұрын
That's what I was hoping to hear!
@Verminator151029
@Verminator151029 Жыл бұрын
Thank you! This is probably the most useful and educational video I've watched this year. I have always done my own electrical work at my house and always try to ensure I'm following the electrical code in my area. This Box Fill stuff is something I never knew about, so thank you! Now I'm heading out to the garage to see if those cubic inches markings are on my plastic electrical boxes! I've saved this video for futire reference. Absolutely terrific! Thank you again!
@MyFortressConstruction
@MyFortressConstruction Жыл бұрын
You're very welcome, and I hope many others find it useful too!
@Kamawah
@Kamawah 2 ай бұрын
There's a box fill calculation app you can use for this. Much easier.
@JesusRamirez-vt6lk
@JesusRamirez-vt6lk 7 ай бұрын
Do you have any calculations for emt? Great video
@MyFortressConstruction
@MyFortressConstruction 7 ай бұрын
I do not since EMT fill is pretty straightforward, but charts like this are helpful: www.elliottelectric.com/StaticPages/ElectricalReferences/ElectricalTables/Conduit_Fill_Table.aspx
@icevariable9600
@icevariable9600 3 ай бұрын
I believe you made a mistake on your ground calculation on the metal luminaire box. You said "Since the grounds have a 12 AWG connected to them, that means they will count as 2.25 cubic inches even though the majority are all 14 AWG." 2023 NEC states "A single volume allowance...shall be made based on the largest equipment grounding conductor ENTERING the box. A 1/4 volume allowance shall be made for each additional equipment grounding conductor that enters the box, based on the largest equipment grounding conductor ENTERING the box." So it looks like the total ground volume allowance should be 8 + 1 (for the 12") = 2.25 volume allowances x 2.00 (Table 3124.16(B)(1) multiplier for 14 AWG) = 4.5 cubic inches.
@MyFortressConstruction
@MyFortressConstruction 3 ай бұрын
Interesting. Definitely have to pay attention to verbage and definitions. I was told to adjust everything if there's one, regardless of its origin, as long as it was 12" or longer, but I think your argument is a good one.
@TomArmyGuy
@TomArmyGuy 2 ай бұрын
yah really "simple" lmao
National Electrical Code (NEC) Box fill calculations
25:17
Ryan Jackson
Рет қаралды 34 М.
Box Fill Calculations Explained
8:56
Craig Michaud- Electrical Instructor
Рет қаралды 72 М.
A little girl was shy at her first ballet lesson #shorts
00:35
Fabiosa Animated
Рет қаралды 22 МЛН
Get 10 Mega Boxes OR 60 Starr Drops!!
01:39
Brawl Stars
Рет қаралды 14 МЛН
My Cheetos🍕PIZZA #cooking #shorts
00:43
BANKII
Рет қаралды 25 МЛН
Box Fill for NEC 2023 with an Example + What got Deleted?
10:50
Sparky Channel
Рет қаралды 19 М.
Determining the Number of Conductors | Box Fill Calculations
8:54
Master The NEC
Рет қаралды 1,8 М.
Sizing pull boxes (NEC 2020)
7:47
Jarod V Music
Рет қаралды 2,6 М.
Box Fill Calculations - Electrical Box Fill (THE EASY WAY)
9:55
The Excellent Laborer
Рет қаралды 71 М.
Conduit Fill / Different Insulation types
9:41
Craig Michaud- Electrical Instructor
Рет қаралды 55 М.
Electrical Wiring Basics
23:40
BrettleyBuilt
Рет қаралды 2,7 МЛН
10 Incredible Homemade Inventions Which Are On Another Level
13:15
Creation Holic
Рет қаралды 4,3 М.
Are You an Electrician? These are 5 Formulas You Should Know!
17:00
Electrician U
Рет қаралды 891 М.
Quick "Cheat Mode" Box Fill Calculations with 2020 NEC
5:43
Sparky Channel
Рет қаралды 29 М.
A little girl was shy at her first ballet lesson #shorts
00:35
Fabiosa Animated
Рет қаралды 22 МЛН