Fire alarm HVAC shutdown installation on my home fire alarm system

  Рет қаралды 5,952

NIC’S - SYSTEMS & ELECTRIC

NIC’S - SYSTEMS & ELECTRIC

Күн бұрын

Пікірлер: 74
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
I am aware of the typo made in programming. The whole system since this video has been reprogrammed with all new names and spelling corrected. This set up in this video didn't end up working, next weeks video will show the problem and the fix.
@davidsalmons80
@davidsalmons80 10 ай бұрын
I really enjoy the content that you're doing you have taught me a lot of stuff that I didn't know and I thank you for that
@bradwilmot5066
@bradwilmot5066 10 ай бұрын
Good call on killing the 24V power. (we break the R wire on the thermostat in the system I maintain instead of at the transformer, but it does the same thing). I suggest putting the duct detector in the supply air, as of now, if the blower motor releases its' magic smoke, the DD won't go into alarm until there is an MFT of smoke in the rest of the house... Better for the detector to catch it right away...
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Yeah that was a thought I had the whole time the problem is finding a location on the supply air that is suitable for mounting and since in my location here it doesn't seem to matter if it's on the return or the supply or both I had to put it on the return as it was the only flat surface I could mount to but I agree with what you're saying
@roberttrains
@roberttrains 10 ай бұрын
I believe on that series of furnace there is fire alarm input they use that sane board in the small commercial units.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Yeah I think there might be just more of a pain to get to. this set up I did in this video didn't end up working anyways so you will see some changes in next weeks video
@topher8634
@topher8634 10 ай бұрын
It's the S/D terminals. You make them up and it will shut down.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
@@topher8634 yes I wasn't aware of them at the time but they seem like a pain to get to anyways. but yes I'm an idiot should have known they were there.
@Josh_T.
@Josh_T. 10 ай бұрын
cutting the secondary on the transformer is still an acceptable way of unit shutdown regardless of dedicated FA shutdown contacts
@topher8634
@topher8634 10 ай бұрын
@@nics-systems-electric you don't know until you know. You already have a vast knowledge of high and low voltage. Control circuits are a beast in themselves. You'll get it I'm confident.
@ulises5369
@ulises5369 10 ай бұрын
Amazing video Nic!! This is the reason why i like addressable systems you can do all sorts of crazy mapping and stuff like that. I'm planning on doing something similar except on my older gas fired furnace (1994, no ac) it has these little bimetallic heat sensors that break the 24v AC going into the board so i might just tap into that with some F2 spade connectors (so i can easily revert back to how it was) but i've seen apartment installs always break the "R" wire but i would rather prefer the system to shut down immediately rather than wait 90-120 seconds.
@Josh_T.
@Josh_T. 10 ай бұрын
the reason why the Relay 1 NO terminal is on the other side is simply bc honeywell wanted to stay consistant with the locations of the older style modules. the older style modules only had room for 5 terminals on each side so the NO open contact was always on the other side. the newer style modules can support that 6th terminal but for consistancy sake they kept it the same layout as the old style. it becomes very useful when you are replacing an old module that failed, and the wire would too short to reach the other side of the new module.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
That makes sense I could've sworn I came across one where it had all six terminals on the one side but I could be imagining things I understand that concept of making it easier for a replacement but it's a pain when you need a resistor across and you have to extend it all the way across the module lol
@Josh_T.
@Josh_T. 10 ай бұрын
@@nics-systems-electric yep i hear ya there
@Josh_T.
@Josh_T. 10 ай бұрын
might have mentioned this in another video but IMC (international mechanical code) requires the duct smoke be on the return side. considering your residential air handling unit is still below the CFM where duct smokes and unit shutdown to begin with, putting it on the return side is more than acceptable.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Yes I think you mentioned that in another video I'm not sure what it is in Canada though as I've seen it on both sides we do require HVAC shut down and duct detection regardless of CFM I've seen it on as small as fans servicing bathrooms for ventilation
@Josh_T.
@Josh_T. 10 ай бұрын
@@nics-systems-electric gotcha i suppose your codes differ, my state has adopted IMC so generally i see return side only, but i do still see supply only and return and supply both.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
@@Josh_T. it's hard to keep track of it here as they seem to change it every code cycle a little bit
@williamcantlon862
@williamcantlon862 10 ай бұрын
I like how you don't just make these videos you make it funny!
@Dilsonalarmsandelectrics
@Dilsonalarmsandelectrics 10 ай бұрын
Nick, you should probably get another one of those devices that gives you a text message on the fire alarms go off the reason why is if you we’re at the school behind your house doing testing or whatever you can get a text message that the fire alarms went off or went into trouble
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
It is connected to the one in the garage however they do not give trouble notification
@redlinepe3461
@redlinepe3461 10 ай бұрын
hey nic you should do an overview of all your tools you use on all your projects and for work. i think some of us world love to see the stuff you use to maybe get an idea on what we should get ourselves.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Might do that someday
@Big_Noob-ROBLOX
@Big_Noob-ROBLOX 10 ай бұрын
It's nice watching your videos when bored Nic
@ChrisTopher284765490
@ChrisTopher284765490 10 ай бұрын
HVAC Typo in the labeling. Just FYI. Great Job again Nic !
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Yeah the whole program has been redone since the video with all new device labels and spelling corrected
@eDoc2020
@eDoc2020 10 ай бұрын
I'm wondering if it's better to use the normally open instead of normally closed contacts. The reason to do this is if the fire alarm system or SLC goes down you wouldn't be letting the furnace run without protection. The downside of course is that if there's SLC trouble your house will go cold.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
The module should stay in its standby position if the SLC was lost
@JessieMHadaller
@JessieMHadaller 10 ай бұрын
The release circuit would be for those door release magnets that hold the doors open and close the doors when the alarms go off.
@firealarmexpert25
@firealarmexpert25 10 ай бұрын
Thanks for this. Been wanted to do this when I make my house system with my duct detector we talked about in Insta
@mightydave1345
@mightydave1345 10 ай бұрын
Make sure it turns the compressor off or it will end up going out of high pressure, could damage it over time
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Contactor let's go
@mightydave1345
@mightydave1345 10 ай бұрын
@@nics-systems-electric that's good. Canadian fire alarm and regs are so different, compared to UK ones
@dragonfireproductions790
@dragonfireproductions790 10 ай бұрын
DC is always a power factor of 1
@topher8634
@topher8634 10 ай бұрын
That transformer secondary is the "R" terminal i was speaking of. That is the control power for the whole system. If you kill it everything should shut down. The reason you only have 2 wires at the t stat is because you have the Honeywell prestige IAQ system. The tstat is powered by 24VAC with those 2 wires and switches the different operations wirelessly to that gray module underneath your duct detector. Its called an EIM for equipment interface module.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
I figured the thermostat that must be wireless as there's only two wires a whole bunch of people told me I'm wrong that it is wired so thanks for letting me know that I was right lol. This set up it didn't end up working anyways where once the system was running in cooling or heating it didn't shut down even when the board lost power so I redid this set up which that video will be up next week.
@topher8634
@topher8634 10 ай бұрын
@@nics-systems-electric no you weren't wrong if you look at stat you should see an R and C terminals which is 24VAC hot and common. All the system functions (compressor, reversing valve, blower, aux heat) are switched via relays on that EIM based on wireless signals from stat.
@chrisgamecave
@chrisgamecave 10 ай бұрын
Kirby vac? Nice!
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
What's that?
@Pbell
@Pbell 10 ай бұрын
0:26 we typically had to do both Return and Supply. In my opinion it is really not necessary but the inspector wanted it that’s what he got.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
I have seen that I've also seen return only and supply only they seem to change it every code cycle it's hard to keep track
@leafmk
@leafmk 10 ай бұрын
Good Job! that really nice.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Thanks!
@brandongotzpowers
@brandongotzpowers 10 ай бұрын
Good video 😊
@keithpierce8458
@keithpierce8458 10 ай бұрын
Nice job
@brianfortuna6691
@brianfortuna6691 10 ай бұрын
Nice system! 😊👍🏻
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Thanks!
@UnknownPedestrian
@UnknownPedestrian 10 ай бұрын
I wouldn't switch the control board for the AC itself, those american standard systems like to throw errors when the control board doesn't behave the way its intended, instead I would switch the 24v control for the thermostat, therefore it completely disables thermostat control when the fire alarm is active without killing power to the control board.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
That doesn't work unfortunately it is a wireless thermostat it will continue to run. Killing power shouldn't be a problem anyways you kill power to the board every time you open the door to change the filter
@UnknownPedestrian
@UnknownPedestrian 10 ай бұрын
@@nics-systems-electric understood, I didn't see any other problems than just switching the control board, that was the only concern, honestly I was only looking at it from like an amp draw point of view, but it's within spec as you mentioned so all good there
@ukfireenthusiast2301
@ukfireenthusiast2301 10 ай бұрын
Where's ayla? or however you spell it, I didn't see them this video.
@shreknigga9785
@shreknigga9785 10 ай бұрын
second, love the vids btw
@applebottomjeans7145
@applebottomjeans7145 10 ай бұрын
why is the relay polling so much?
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Just as much as any other module there's only five modules on a system capable of 159 so it will poll quickly
@TheofficialInfinitypulse
@TheofficialInfinitypulse 10 ай бұрын
The level 1 and 2 slc isolator is flashing yellow
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Level one and level two
@bradwilmot5066
@bradwilmot5066 10 ай бұрын
Also, if you didn't catch it, you misspelled HVAC when programming the point...
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Yes I did since this video I have gone through the entire program redid every device to look cleaner and fix any errors which there are plenty of because of my disability which makes spelling my spelling terrible
@Techben16
@Techben16 10 ай бұрын
@@nics-systems-electric I really enjoy your content. I have always had a passion for alarm systems and fire alarm systems. Sadly, I took a different career path (IT Computer Technical Analyst). I would love to learn how to do stuff like that, but being in QC, the rules are very strict... Maybe one day I'll find a job posting that offer you the mandatory courses. Also, It is not evident about your disability. All this nice and smart work, I would have not been able to tell. Keep it up man!
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
@@Techben16 Thank you. I just have some sort of spelling disability can't remember what it's called I just call it not being able to spell shit.
@Corwin09-ji8sx
@Corwin09-ji8sx 10 ай бұрын
11:11 Oops! Honneywell forgot to give you the English manual!
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
At 12:35 I grabbed the English one they didn't forget to give one I just picked up the French one first
@Corwin09-ji8sx
@Corwin09-ji8sx 10 ай бұрын
My bad there
@Manakboy123
@Manakboy123 10 ай бұрын
Iooo
@elektrokinesis4150
@elektrokinesis4150 10 ай бұрын
first
@elevatingaroundtown
@elevatingaroundtown 10 ай бұрын
Dang it
@michellebertrand7702
@michellebertrand7702 10 ай бұрын
No one cares anymore.
@VoidsDemise5443
@VoidsDemise5443 10 ай бұрын
​@@michellebertrand7702true
@The_FireAlarmGuy
@The_FireAlarmGuy 10 ай бұрын
​@@michellebertrand7702ok but if he wants he can say it
@CGray1234
@CGray1234 10 ай бұрын
@@michellebertrand7702facts 💯
@theplanetmc181
@theplanetmc181 10 ай бұрын
5th!
@MrFfwrch
@MrFfwrch 10 ай бұрын
4nd
@Chaeuraersat
@Chaeuraersat 10 ай бұрын
3rd
Fixing Fire alarm HVAC shutdown problem
36:49
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 7 М.
这三姐弟太会藏了!#小丑#天使#路飞#家庭#搞笑
00:24
家庭搞笑日记
Рет қаралды 48 МЛН
طردت النملة من المنزل😡 ماذا فعل؟🥲
00:25
Cool Tool SHORTS Arabic
Рет қаралды 18 МЛН
Can This Bubble Save My Life? 😱
00:55
Topper Guild
Рет қаралды 83 МЛН
My Cheetos🍕PIZZA #cooking #shorts
00:43
BANKII
Рет қаралды 28 МЛН
It's time for change, it's time for Linux.
10:53
DankPods
Рет қаралды 192 М.
Simplex 4008 Test 1: My New Voice Evac System
13:05
Equalstar's Alarms
Рет қаралды 293
My House Lost Power Again! Generator has More Problems During Power Outage.
21:43
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 19 М.
Fire Alarm Testing at a Brand New Elementary School! Notifier NFS2-3030 & L-Series.
50:58
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 12 М.
September testing (Night time) Fire alarm, emergency lighting, back up generator, UPS's
30:18
Simplex 4008 Home Fire Alarm System Test 3-29-23 w/ Major Updates
26:27
Fire Alarms of Northeast Kansas
Рет қаралды 5 М.
25 - Control Modules - Introduction to Fire Alarms
10:00
Joe Klochan
Рет қаралды 202 М.
New System Test 1
19:35
NewAgeServerAlarm
Рет қаралды 78 М.
Trouble in the night fire alarm problems and troubleshooting
26:03
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 18 М.
这三姐弟太会藏了!#小丑#天使#路飞#家庭#搞笑
00:24
家庭搞笑日记
Рет қаралды 48 МЛН