Replacing a school fire alarm system Notifier addressable elementary school upgrade (part two)

  Рет қаралды 16,855

NIC’S - SYSTEMS & ELECTRIC

NIC’S - SYSTEMS & ELECTRIC

Күн бұрын

Пікірлер: 101
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
Part 1 kzfaq.info/get/bejne/qtyVoZeG3LKqgas.htmlsi=7i8jvXRx56XYrtSr
@outlaw686
@outlaw686 9 ай бұрын
Notifier is in every way better, but I love the big red bells. I'm the kid in school who got excited when I heard there would be a fire alarm test.
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
Yeah I hear ya same here
@joshfriesen9401
@joshfriesen9401 10 ай бұрын
I love the pride you take in your work. Those portables’ booster panel wire management is a work of art. Keep up the fantastic work.
@washingmachinelad356
@washingmachinelad356 10 ай бұрын
I really love the idea how they replace old conventional fire alarm systems with modern adderssable fire alarm system. In the United Kingdom, they use call points instead of pull stations
@raizrindustries
@raizrindustries 10 ай бұрын
Awesome video! Also (At 5:53) that has to be the oldest and coolest heat detector I've seen so far in this system upgrade. I assume this one got thrown out with the other heats, but it's cool none the less.
@ILVT_Plumbing
@ILVT_Plumbing 10 ай бұрын
I agreed, i think it's really cool
@michaelclark2022
@michaelclark2022 10 ай бұрын
Yeah I don't blame you about that 14 ft ladder. I can tell it looked janky even before you were on it. Honestly you were playing a game of 50/50, because there was an even chance it would stay stable but yet it could fall and we don't want that happening. (Especially at a school.)
@SodiumInduction-hv
@SodiumInduction-hv 10 ай бұрын
i love these videos!!! keep up the great work! and it’s funny when the panel kept going to trouble again after acknowledging it!
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Thank you! Will do!
@aerhardt
@aerhardt 10 ай бұрын
49:07 I HATED the portables in my elementary school because they had Simplex conventional TrueAlert horn strobes (which have no volume adjustment and are always on high volume) on continuous. It was a portable with four classrooms and a hallway connecting all of them. When they first got it, I saw that they had System Sensor horn strobes (one in the hallway and one in each of the four classrooms) but I was hoping that they would just replace them with remote strobes in the classrooms. I’m glad you are setting them to low volume so those kids don’t have to go through the same pain.
@CGray1234
@CGray1234 10 ай бұрын
Augh, continuous? Like come on, they’re fire alarms, they could’ve at least used code 3
@aerhardt
@aerhardt 10 ай бұрын
@@CGray1234 Yeah I think that continuous is unfortunately still allowed in my area because I have never heard a system on code 3 in my life.
@mikeross880
@mikeross880 10 ай бұрын
Well done Nic, or to put it another way “you have a knack when it comes to installing many a well organized NAC Nic” Can’t wait to hopefully purchase a bell, pull and heat in the not too distant future. Also Nic whatever you do be sure and keep that silver metal heat detector from early on as those are extremely rare now. I think I now know why Edwards discontinued them early on; supposedly due to their aluminum body they were much more prone to falseing in certain situations (such as steam) so plastic was the preferred material thereafter. Finally be sure to save one of those original Edwards EOL plates from back in the day; love those super cool looking resistance symbols they would cast on them. Nice asbestos suit Jamie; must have been tricky mounting those new heats up there. Excellent job guys.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Thanks as far as those heat detectors I think they are cool I do like the look of them Edwards doesn't make them anymore but I've still seen them installed as recent as a few weeks ago so they are still produced just by a different company can't remember who makes them
@Mr.WonderfulGaming
@Mr.WonderfulGaming 10 ай бұрын
Hes risking his life wiggling that ladder lol
@TheLastWolfBane
@TheLastWolfBane 10 ай бұрын
I love these videos, I still don't know why some smoke have 3 lines and others only have 2. and thanks
@scottbrockman5883
@scottbrockman5883 9 ай бұрын
I have just watched this on KZfaq after watching Part one. First off, these videos are a little long so I had to watch this on 1.25 & 1.50x speed and at normal speed. Sorry about that. Second, as far back as I can remember, in my Junior or Senior year in High School and attending Sno- Isle program, which BTW is another High School, I remember when they had to replace the old Fire alarm system and the Fire alarm Control panel in the Main Office. The Fire alarms were old, about 25 years & were replaced by EST Genesis horn/strobes in the class rooms and the Intergrity horn/ strobes on the outside and 2 in the Greenhouse & the Portable they had. They also had a Wheelock AS horn/straps in the Cafeteria andsome Heat and smoke detectors in the classrooms as well. Thirdly, I do agree with you about the 14 foot ladder and I also agree that older buildings that were built in the 50s, 60s and 1970s didn't have any codes or any Fire codes & they weren't enforced or not in placed. In my opinion, it's as if the contractors didn't care about the safety and the well-being of the occupants in a certain building or the location or sound level of the older Bells or Horn/ Strobes or they simply didn't have the money to fix the problem or "troubles". Aside from that, I still like the bells, it's sad that some of them aren't being used anymore, (well not those 11 or 12 inch bells), and being replaced by horn/strobes or even speaker strobes which they're okay 🙂👍😊.
@HorrorPl4Yer
@HorrorPl4Yer 10 ай бұрын
U did a great job with this video keep it up well done
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Thank you
@HorrorPl4Yer
@HorrorPl4Yer 10 ай бұрын
@@nics-systems-electric no problem
@dutchwolf2675
@dutchwolf2675 10 ай бұрын
Great video! Can’t wait for the last parts! Hope it went well. Keep up the great work!
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Thank you, glad you enjoyed!
@enricodigi
@enricodigi 10 ай бұрын
Great video 👍
@Nothinghere0101
@Nothinghere0101 10 ай бұрын
I was literally watching part 1 at 6:00AM lmao
@Huey-Gamer
@Huey-Gamer 10 ай бұрын
at your house you should connect the generator for supervisory ( running )
@FurbyGaming125
@FurbyGaming125 4 ай бұрын
7:01 Creepy
@SnowyTechy
@SnowyTechy 10 ай бұрын
i kind-of like to see whats behind the bells, because at my school they still use the circle bells.
@EASsirenVids01
@EASsirenVids01 10 ай бұрын
Professional work as always. Did you keep the IO-64?
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
It turns out to actually be an IO 1000 I kept it originally but sold it
@EASsirenVids01
@EASsirenVids01 10 ай бұрын
@@nics-systems-electric nice
@EASsirenVids01
@EASsirenVids01 10 ай бұрын
I mainly just hate to see stuff get thrown out, so I’m glad it went to a good owner, espically considering it’s still in great shape
@whelenvortexr4
@whelenvortexr4 10 ай бұрын
I wonder if they'll use this system for parts in the other buildings when this school get demolished?
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Hard to say you'd think it would be a yes as it won't be that old but then you would also have a period of time without a fire alarm system which may or may not be a problem
@zacharyboney6930
@zacharyboney6930 10 ай бұрын
Hey man love the videos! Hey do you get to use Wheelock, Gentex, Simplex, Faraday, or Siemens devices?
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
No wheelock doesn't seem to have as many options and I've never seen gentex or faraday in Canada and you can only use devices listed for use with the panel you are installing
@zacharyboney6930
@zacharyboney6930 10 ай бұрын
@@nics-systems-electric Oh ok makes sense. And that’s cool! Keep up the good work man!
@ebelray6890
@ebelray6890 10 ай бұрын
18:35, those IT people suck. I run those same Cisco access points and the mounting brackets for them are cheap and all over Ebay. They won't transmit as far either sitting on a metal object versus being mounted on drywall. Seeing that shotty work kills me...
@aerhardt
@aerhardt 10 ай бұрын
What are you doing with the ceiling mount horn strobe that you mentioned in the last video? I wouldn’t think the old system would have had any bells on the ceiling.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Yes there was a trouble bell on the ceiling that was mistakenly accounted for during the device count
@aerhardt
@aerhardt 10 ай бұрын
@@nics-systems-electric Wow I have never heard of a bell on the ceiling.
@topher8634
@topher8634 10 ай бұрын
Nic, were you able to fix your HDMI cable issue? I don't see the video listed anymore.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Maybe
@achannelwithnopurpose1977
@achannelwithnopurpose1977 10 ай бұрын
Will you save the new devices when the school is demolished? You said something about the old school (in a previous vid or this vid) being demolished in favor for a new one that is bigger and better.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Hard to say if I would have the ability to as I won't be with the school district at that point
@achannelwithnopurpose1977
@achannelwithnopurpose1977 10 ай бұрын
@@nics-systems-electric maybe you could keep some contacts. That’s what I did to get my 4100U from the old highschool it was installed in.
@justinramey121
@justinramey121 4 ай бұрын
Nic Do you have a part three
@nics-systems-electric
@nics-systems-electric 4 ай бұрын
There is a part three verification of it yes
@Firealarmperson902
@Firealarmperson902 10 ай бұрын
where do you buy your fire light stuff
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
eBay
@carsonkalinowski
@carsonkalinowski 10 ай бұрын
Do you ever get shocked by the wires when the system is on?
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Not fire alarm
@carsonkalinowski
@carsonkalinowski 10 ай бұрын
Ok thanks for your feedback you are the best person to reply to my comment and questions
@CGray1234
@CGray1234 10 ай бұрын
The electrical current output is 24V DC so it's very unlikely to get shocked
@buddyochoa2
@buddyochoa2 10 ай бұрын
Is it not a problem to keep the system down for work if the building is unoccupied, or did they have to have people doing fire watch overnight?
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Usually depends on what the building management wants to do with it since it's unoccupied so there isn't a life safety concern usually if they do want firewatch they will have a security guard come around every hour
@lolMyke
@lolMyke 10 ай бұрын
I can’t believe that fire alarm breaker wasn’t painted red & locked on
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
They don't have to be here
@splatoongigi2523
@splatoongigi2523 7 ай бұрын
What are resistors for?
@nics-systems-electric
@nics-systems-electric 7 ай бұрын
For supervising the circuit if the circuit had a break anywhere the panel would no longer see resistance and know there was a trouble
@cussmustard4748
@cussmustard4748 10 ай бұрын
Is the bilingual signage common across all of Canada?
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Yes
@iansanchez1470
@iansanchez1470 10 ай бұрын
Don't forget to Label EOL on alarms that have the End of Line Resistor
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
We don't put them in the device box that is illegal in Canada they have to be under a end of line plate
@iansanchez1470
@iansanchez1470 10 ай бұрын
I Live in the US and i see that installers write EOL on the alarm itself with a sharpie as End of Line resistor on the alarm itself or they may be writing more detail like for example: EOL CKT 1, I know the US requirements but i don't know canadisn requirements because I live in the US but i'm still learning more about the canadian requirements
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
@@iansanchez1470 yes it would make sense to label the end of line device if you had the resister on the actual device however that isn't allowed here sometimes we still will label the end of line plate after the end of line device
@mewing-gawd
@mewing-gawd 10 ай бұрын
have u seen any residential smoke detectors in schools? in my middle school there were some and in my elementary school there were a lot of
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Just temporary for sleepovers in areas that don't have smoke detection
@mircomamsecohardwareandsafety
@mircomamsecohardwareandsafety 10 ай бұрын
19:45 LOL
@leafmk
@leafmk 10 ай бұрын
I wish I can get the IO 64/Portable Panel.
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Turns out it's actually an Io 1000
@leafmk
@leafmk 10 ай бұрын
@@nics-systems-electric Oh. Tho I wish I can get the panel from portables
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
@@leafmk it's sold now
@leafmk
@leafmk 10 ай бұрын
@@nics-systems-electric Aww man.
@NyxKemo
@NyxKemo 10 ай бұрын
@@leafmktrust me you do not want an Edwards IO panel, they have more than issues
@jacobisworld9516
@jacobisworld9516 10 ай бұрын
Wish you could put in speaker strobe
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
And how would you do that
@aerhardt
@aerhardt 10 ай бұрын
It’s not very common in Canada and it would be impossible with just two wires.
@Dawezil
@Dawezil 10 ай бұрын
my school has a still working perf fine EST Edwards 6632 pannel!
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Nice those are newer than 6500s
@Dawezil
@Dawezil 10 ай бұрын
@@nics-systems-electric nice!
@IanGSully
@IanGSully 9 ай бұрын
So why is this school getting demolished in 5 years anyway?
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
Because it's an old pos and it's not big enough and needs seismic upgrades anyways
@IanGSully
@IanGSully 9 ай бұрын
@@nics-systems-electric Plus the Asbestos, and wacky fire alarm wiring? Yeah, this school needs to be see ya later!
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
@@IanGSully the fire alarm is fine now once it's installed just can be more difficult to troubleshoot. asbestos only becomes a problem if it needs to be disturbed and then you have to do an abatement of it which makes seismic upgrades challenging to do in the school year when kids are around
@IanGSully
@IanGSully 7 ай бұрын
@@nics-systems-electric That's if that building doesn't get destroyed by a massive earthquake. Which to my understanding you are due for one.
@cdarting91
@cdarting91 9 ай бұрын
There’s something odd about a gym with no windows.
@nics-systems-electric
@nics-systems-electric 9 ай бұрын
Really!? That's interesting as almost all of our schools more than 10 years old don't have any windows in the gyms.
@wenxelle
@wenxelle 9 ай бұрын
I want free alarm snooze😢
@MichaelKsAlarms
@MichaelKsAlarms 7 ай бұрын
Hi
@darksecrets874
@darksecrets874 10 ай бұрын
Second
@mircomamsecohardwareandsafety
@mircomamsecohardwareandsafety 6 ай бұрын
Fire alarm not fire alert
@The_FireAlarmGuy
@The_FireAlarmGuy 10 ай бұрын
First
@rayarsenault4774
@rayarsenault4774 10 ай бұрын
5:02 too close to an air-mover? (yes, I know it's not you).
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
No it's a heat detector not smoke detector and it's very low CFM bathroom exhaust anyways
@ILVT_Plumbing
@ILVT_Plumbing 10 ай бұрын
did you keep any old devices or panels
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
Kept the stuff I wanted
@ILVT_Plumbing
@ILVT_Plumbing 10 ай бұрын
@@nics-systems-electric Did you keep that cool silver heat detector
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
@@ILVT_Plumbing maybe
@ILVT_Plumbing
@ILVT_Plumbing 10 ай бұрын
@@nics-systems-electric its the one at 5:53
@nics-systems-electric
@nics-systems-electric 10 ай бұрын
@@ILVT_Plumbing yeah I don't remember that was a few months ago
Notifier replacement fire alarm system of verification elementary school
52:48
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 15 М.
2024 annual home fire alarm system testing/verification. Entire system test.
40:12
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 13 М.
Нашли чужие сети в озере..💁🏼‍♀️🕸️🎣
00:34
Connoisseur BLIND420
Рет қаралды 3,6 МЛН
女孩妒忌小丑女? #小丑#shorts
00:34
好人小丑
Рет қаралды 78 МЛН
123 GO! Houseによる偽の舌ドッキリ 😂👅
00:20
123 GO! HOUSE Japanese
Рет қаралды 6 МЛН
I Built a Transparent Boomerang (it's lethal)
13:10
Mike Shake
Рет қаралды 4,1 МЛН
Testing fire alarms (EARRAPE!)
8:28
FireAlarms
Рет қаралды 27 М.
My House Lost Power Again! Generator has More Problems During Power Outage.
21:43
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 18 М.
Notifier NFS2 640 Programming Guide
28:30
Roxxofoxxo
Рет қаралды 27 М.
Setting off 40 fire alarms 2024 New Year's fire alarm ringing/sound off! Happy New Year!
12:58
Replacing fire alarm system at Elementary School. Full addressable replacement day #2