Practical Training on Manometers

  Рет қаралды 20,474

HVAC School

HVAC School

Жыл бұрын

Bert teaches a practical training class on manometers. In air conditioning applications, we commonly use manometers to measure static pressure, but they may also measure gas pressure in furnaces and pool heaters.
Static pressure refers to the pressure acting on the inner surfaces of the ducts in HVAC systems, and it is affected by airflow resistance; we can think of static pressure as an indicator of airflow. The filter and the coil are also sources of airflow resistance, so we often see static pressure drops across those components. Static pressure may either push against the ductwork (positive, on the supply side) or pull against it (negative, on the return side). Manometers measure this static pressure in inches of water column.
We can find the total external static pressure (TESP) by placing one manometer probe above the filter and another just above the blower and adding the readings to see how much airflow resistance that blower has to overcome. You can compare the measurement with the TESP on the data tag, which shows the static pressure conditions under which the unit was tested by the manufacturer.
The MERV rating on the filter can affect your return static pressure reading; higher MERV ratings can reduce the static pressure on the return side; we can test the actual resistance by measuring static pressure across both sides of the filter: in the return and between the filter and the coil. Dirty coils or filters can reduce the supply static pressure and will make the TESP low if you measure static pressure before the filter in the return, which can be a misleading airflow indicator. Evaporator coils will always cause a pressure drop, but clean coils usually cause a pressure drop of less than 0.1 inches of water column, so a large amount of soil can increase that pressure drop significantly.
Manometers have pressure probes with holes on the side; the probes should point in the opposite direction of airflow to yield the most accurate readings. When using a manometer as a diagnostic tool, you can take readings with and without the filter to see how much it may be contributing to the static pressure drop. We typically want to see a static pressure of less than or around 0.5" WC; once we reach 0.8" WC or higher, we start to see reduced blower motor efficiency, shorter blower lifespans, and more issues. You can also use manometers to locate duct restrictions; collapsed ducts will cause the static pressure to skyrocket as the airflow reaches the restriction, but visual inspections may be more useful if you suspect that the ducts may have collapsed.
If you want to figure out the static pressure drop across the coil and place your manometer probe before the filter or immediately before the blower (above the coil), you will have negative static pressure. Some diagnostic apps may have trouble calculating TESP readings in those locations, so you may have to do the math yourself to figure out the pressure drop across the coil.
Buy your virtual tickets or learn more about the HVACR Training Symposium at hvacrschool.com/symposium.
Read all the tech tips, take the quizzes, and find our handy calculators at www.hvacrschool.com/.

Пікірлер: 23
@calebdaniel581
@calebdaniel581 Жыл бұрын
The Fieldpiece manometer operation manual says that the tip should be pointed toward airflow and that the arrow on the baseplate should be pointed towards airflow not with airflow. I may have misunderstood, but it appears you recommend putting it in the opposite direction as what the manual states. Is there a reason why you recommend positioning it in the opposite direction? Again thank you for all the helpful videos!
@cadamham
@cadamham Жыл бұрын
Do it both ways. Even do it with just the hose and no tip. You won’t see an appreciable difference in any of the measurements
@jessetesterman2271
@jessetesterman2271 Жыл бұрын
Yes, that’s right Caleb. I misspoke in the class even though I displayed it installed correctly. I think my comment mislead the editor, so we have the visual with red airflow arrow pointed backwards. Also @me’s comment is nearly always true. It doesn’t practically matter with the airflow in most residential systems
@papapapist
@papapapist Жыл бұрын
Bert is an asset with many talents 😆 his dry delivery is actually very effective
@peepeepoopoo1399
@peepeepoopoo1399 Жыл бұрын
Give that dude a bonus so he can get a haircut 😂
@mackenziegray2090
@mackenziegray2090 Жыл бұрын
Kinda like his hair lol
@scottallen5182
@scottallen5182 Жыл бұрын
Great job Bert!
@jasonjohnsonHVAC
@jasonjohnsonHVAC Жыл бұрын
A manometer measures differential pressure. You need differential in order for flow to commence . Same concept is in use with hydronics, temp etc etc.....its about inducing flow with the smallest differential (head loss, friction loss )needed to operate properly to achieve a set parameter. We use this in large commercial equipment. I work on equipment with a design static of 1.5", 2", 2.5" wc with VAV's, building pressure. In hydronic systems we use differential pressure set points to modulate VFD'S based on differential readings for when zones, coils,bypass valves etc etc shut down.
@logans3365
@logans3365 8 ай бұрын
Upgrading my havac system with quality filtration, they didn’t seem to care about that much back in the day, but these old houses have filthy air quality.
@squatfreak1184
@squatfreak1184 6 ай бұрын
Simple but effective
@anthonygesswein1830
@anthonygesswein1830 Жыл бұрын
just wondering how are you getting an accurate static won't the hose to the wireless probe get pinched in the door was just wondering
@jessetesterman2271
@jessetesterman2271 Жыл бұрын
I drilled a hole into the cabinet.
@andycross3409
@andycross3409 Жыл бұрын
Hey Bert, I have never seen an evaporator coil with a static across it of only .1 if I understood what you said.
@jessetesterman2271
@jessetesterman2271 Жыл бұрын
👍🏻 ok. What type units you working on? I’ve only taken this measurement on a few residential units over the years. .1 seams to be a common read I have on new clean coils
@stillwill1808
@stillwill1808 Жыл бұрын
Probably because hes referring to a pressure drop on a brand new, dry, coil only. Only reason to check coil only in the field is to confirm airflow restriction so I wouldnt expect to static that low. Its decent baseline for comparison.
@jackdowning3101
@jackdowning3101 Жыл бұрын
0:20 .... Furnace is totally air-conditioning !
@rojobandito318
@rojobandito318 6 ай бұрын
Wow this vagrant really knows static pressures
@naoumhalamoutis1960
@naoumhalamoutis1960 Жыл бұрын
resistance???
@bryanswanson5007
@bryanswanson5007 Жыл бұрын
yes, resistance. what about it?
@MichaelHernandez-lc2wb
@MichaelHernandez-lc2wb Жыл бұрын
For a start, he draws much better than you Bryan😂
@josecornell293
@josecornell293 Жыл бұрын
This one was too basic. I feel like it could of been done in 5 minutes. manual D is the best when it comes to this type of things.
@jessetesterman2271
@jessetesterman2271 Жыл бұрын
Great feedback 🙏❤️
@rickjames9256
@rickjames9256 Жыл бұрын
How do you check a static on a front draw over the water heater style air handlers?
Static Pressure and Manometer Basics
32:33
HVAC School
Рет қаралды 165 М.
Accumulator Facts & Tips
24:44
HVAC School
Рет қаралды 119 М.
Osman Kalyoncu Sonu Üzücü Saddest Videos Dream Engine 170 #shorts
00:27
Khó thế mà cũng làm được || How did the police do that? #shorts
01:00
Using a Digital Manometer to Set Furnace Natural Gas Pressure
15:11
Air Flow Diagnostics w/ Joseph C Henderson
48:40
HVAC School
Рет қаралды 34 М.
How to use Static Pressure to Measure and Set Air Flow
1:34:29
HVAC School
Рет қаралды 233 М.
Restaurant Air Balance problem
11:10
HVACR VIDEOS
Рет қаралды 77 М.
How to Evacuate an AC system, Full Vacuum Procedure
27:35
HVAC School
Рет қаралды 1,1 МЛН