Regulation 26.9 Gas Engineer Safety Checks | NGCFE

  Рет қаралды 41,513

Allen Hart

Allen Hart

Күн бұрын

Regulation 26.9 is a section of the Gas Safety Installation and Use Regulations that provides guidance on what checks an engineer should carry out when working on an appliance. The regulation states the following.
National Gas Centre For Excellence NGCFE
“(8) No person carrying out work in relation to a gas appliance which bears an indication that it so conforms shall remove or deface the indication.
(9) Where a person performs work on a gas appliance he shall immediately thereafter examine -
(a) the effectiveness of any flue;
(b) the supply of combustion air;
(c) subject to sub-paragraph (ca), its operating pressure or heat input or, where necessary, both;
(ca) if it is not reasonably practicable to examine its operating pressure or heat input (or, where necessary, both), its combustion performance;1
(d) its operation so as to ensure its safe functioning,
and forthwith take all reasonably practicable steps to notify any defect to the responsible person and, where different, the owner of the premises in which the appliance is situated or, where neither is reasonably practicable, in the case of an appliance supplied with liquefied petroleum gas, the supplier of gas to the appliance, or, in any other case, the transporter.”
The checks can be easily remembered using the abbreviation FAGS, which stands for flue, air, gas and safety devices.
These checks must be carried out as a minimum when working on an appliance.
Should you wish to attend the centre for training or wish to discuss your needs further, then please contact hello@ngcfe.co.uk or call 01924973260

Пікірлер: 39
@AllenHart999
@AllenHart999 2 жыл бұрын
ngcfe.co.uk/
@robwoods8160
@robwoods8160 2 жыл бұрын
Great presentation. Should have the customers watching this. Especially the penny pinching landlords.
@raul835
@raul835 2 жыл бұрын
SUGGESTION: Gas fires. How to recognise the different types. To this day, I don't really know if I'm looking at a radiant, dfe, inset or whatever else. Fires are my Achilles heel Lol.
@jamstar116
@jamstar116 2 жыл бұрын
I really enjoy this type of videos, good job guys
@edmetcalfe8974
@edmetcalfe8974 2 жыл бұрын
What would be really useful is a video explaining how to proceed if the gas rate is not within -10% and +5%. A lot of these gas courses cover how to gas rate but don’t really go into how to classify when it’s not within tolerance and also how to rectify.
@rjv9858
@rjv9858 Жыл бұрын
Upsize / downsize pipe to achieve gas rate
@edmetcalfe8974
@edmetcalfe8974 Жыл бұрын
@@rjv9858 assuming the problem is with pipe sizing. Lots of things can adversely affect gas rate.
@rjv9858
@rjv9858 Жыл бұрын
@@edmetcalfe8974 what like? All got to do with the gas pipe itself, either too big, too small, blocked, too many bends etc if that’s what you mean? all boils down to pipe though
@j.j8114
@j.j8114 Жыл бұрын
@@rjv9858 Could also be faulty regulator at the meter causing low pressure, distance from meter to appliance, pipe size, gas escape on system, bad gas valve? many reasons.
@ukgasengineerssolutions
@ukgasengineerssolutions Жыл бұрын
​@@j.j8114your standing pressure would have clarified a faulty governor
@jockster5525
@jockster5525 2 жыл бұрын
Great video thanks for your efforts lads ..
@tomstrutton4351
@tomstrutton4351 2 жыл бұрын
These videos really are good Allen
@smithersjones3018
@smithersjones3018 Жыл бұрын
Great video. Cheers
@mikeportch8725
@mikeportch8725 4 ай бұрын
Another great video allen
@petermcdonagh6669
@petermcdonagh6669 2 жыл бұрын
Thanks Allen top video
@yaminhetingplumbingleicesteruk
@yaminhetingplumbingleicesteruk Ай бұрын
great presentation
@KS-we8ov
@KS-we8ov 2 жыл бұрын
Yesss Allen done and dusted...but great video to learn from 🙏
@tommyblackman7119
@tommyblackman7119 2 жыл бұрын
Great video.. Can how about a video on gas fires on 26.9 checks
@sergiofernandez3725
@sergiofernandez3725 2 жыл бұрын
Have you seen that some manufactures of boilers are stating the type of circuit breaker that is needed? I saw on a recent discussion board that a type B was needed? It also went on to state that they recommend a SPD (surge Protection Device) in the fusebox/fuseboard/CU to protect the sensitive equipment on the PCB of the boiler
@hvacgas5292
@hvacgas5292 2 жыл бұрын
Good video.👍...when you gas rate cooker ,do the oven and grill have to be switched on as well?
@theheatingdoctor
@theheatingdoctor 2 жыл бұрын
Great video but you ideally want to spray LDF generously around the isolation tap of the gas under boiler once disturbed, not just the isolation screw. When disturbing the ECV by moving it also wanna spray around the handle, spray the anaconda and the two nuts in and out of the meter for peace of mind. Great video tho, nice and informative. Video suggestion would be safe electrical isolation, safe to touch test and checking the polarities etc on the boiler and the house. Many a time do I have a chat with engineers and they just don't do it. An idea mate :) Checking the voltages across live and switch live on diverter valves is another idea mate, allowing newcomers to establish correct functioning (or incorrect) of the switch itself.
@tomadams94
@tomadams94 2 жыл бұрын
All true however this has nothing to do with tightness tests or meters other a than gas rating so you are really only going to use ldf on the appliance iso and / burner pressure test point
@theheatingdoctor
@theheatingdoctor 2 жыл бұрын
@@tomadams94 true, just popping a few extra safety things in there in case a new starter sees something they wanna pick up; if they anything like I was back in day they will be watching everything and reading everything :)
@tomadams94
@tomadams94 2 жыл бұрын
@@theheatingdoctor no it’s good practice a lot of people don’t spray valves after touching them! 👍🏻
@SuperWayneyb
@SuperWayneyb 2 жыл бұрын
🤘😎🤘
@theplumber4934
@theplumber4934 Жыл бұрын
Can you clarify the 5% above and 10% under as TB 141 states that under BS297 & BS EN 483 the 5% and 10% are tolerances during manufacture of the appliance for CE approval. However there is no specific tolerance stated anywhere that is applicable to gas rating at the time of commission or servicing. I think this is possibly a rule that has got mixed up as it has been past down from person to person since 2012 when it came out.... Thanks
@xudongpeng2729
@xudongpeng2729 Жыл бұрын
Can I ask If the gas rate I got lower than manufactory book how can I do thanks.
@milkman100001
@milkman100001 Жыл бұрын
didnt check your analyser for O2 before testing the boiler. and then no flue integrity was done either.
@kevj1964
@kevj1964 2 жыл бұрын
11.50 :- 3 burners on a hob to Gas Rate ? is'nt 3 burners on a hob to check for working/operating pressure?
@michaelhunt848
@michaelhunt848 2 жыл бұрын
Yes mate. Slip of the tongue. Well spotted.
@maximuswong3092
@maximuswong3092 8 ай бұрын
Allen, PLEASE PLEASE do i video on regulation 26.2 nobody talks about this regulation.
@AllenHart999
@AllenHart999 8 ай бұрын
I will look into it. Thanks.
@davidhallas9063
@davidhallas9063 6 ай бұрын
why didn’t he start gas rate test at the rite point on the gas meter ?
@garytreverton-black3693
@garytreverton-black3693 2 жыл бұрын
No flue integrity test?
@martynlewis9020
@martynlewis9020 2 жыл бұрын
Isn’t that only if the flue is in void?
@traian23us
@traian23us Жыл бұрын
1097:31=35.38 kW gross a shorter way of doing it
@Ash-fy2mn
@Ash-fy2mn Жыл бұрын
It’s a shame these rules only apply to certain engineers, national gas supplier contractors exempt according to Gas Safe! How does that work? One rule for us and another for them, surely NG has the same risk whoever works on it? No wonder people leave this trade.
@anthonygreenwood4486
@anthonygreenwood4486 Ай бұрын
Why do the Big Gas companies only do a tightness test on a landlords, But private households just bring fault code up on a boiler and don’t do mini tightness? KZfaq warriors don’t want to talk about it
@Purebeltersteve
@Purebeltersteve 2 жыл бұрын
Personally if your a gas engineer and you dont know 26.9 checks, your not competent and should never be doing gas.
Carbon Monoxide Alarm Activation Guidance | NGCFE
15:37
Allen Hart
Рет қаралды 25 М.
How To Fill Out A Landlord Gas Safety Check CP12 GGIUR 26.9
38:42
Happy 4th of July 😂
00:12
Pink Shirt Girl
Рет қаралды 60 МЛН
MEGA BOXES ARE BACK!!!
08:53
Brawl Stars
Рет қаралды 36 МЛН
路飞被小孩吓到了#海贼王#路飞
00:41
路飞与唐舞桐
Рет қаралды 68 МЛН
- А что в креме? - Это кАкАооо! #КондитерДети
00:24
Телеканал ПЯТНИЦА
Рет қаралды 5 МЛН
ACS GAS TRAINING / CONTROLS | NGCFE
34:40
Allen Hart
Рет қаралды 26 М.
Tech Talk - Episode 1 - Gas Safe Register
14:09
Gas Safe Register
Рет қаралды 1,9 М.
Gas Rates Everything You Need to Know
29:16
Pass Your Gas
Рет қаралды 5 М.
ACS Gas Training - What's involved in your ACS Gas Assessments.
34:30
Flame Rectification | How To Test | ACS Gas Learning NGCFE
13:59
The Most Confusing Part of the Power Grid
22:07
Practical Engineering
Рет қаралды 1,3 МЛН
You Won't Believe What This Boiler service uncovers! THIS WILL SHOCK YOU
14:14
Blue Bulldog Plumbing
Рет қаралды 17 М.
How to start your ACS gas assessment
11:32
Pass Your Gas
Рет қаралды 7 М.
Рыбаки в шоке. Рыбалка. #рыбалка  #shorts
0:20
Жизнь Рыбака
Рет қаралды 10 МЛН
ВЕЛОСИПЕД ЗАГОВОРИЛ
0:15
KINO KAIF
Рет қаралды 15 МЛН
Сумасшедший бассейн с волнами в Китае
0:16
Короче, новости
Рет қаралды 9 МЛН
Il n'a pas aimé la technique 😂 #firefighter
0:13
Remi Ragnar
Рет қаралды 14 МЛН
Choose my outfit 💕
0:16
Valerie Lungu
Рет қаралды 23 МЛН