Many firmware bugs. FW 6024 and 6026 (no difference)
Problems seem to occur when gen port is selected as micro inverter input.
After 2 years mail conversation, still existing problems:
1. ignore grid setpoint: always grid consumption.
2. ignore "no solar sell"; micro inverters keep feeding the grid.
3. when offgrid and cloud is passing the sun, you get a voltage drop from 230 to 182V AC.
4. max charge amps from grid is also the limiting the current when charging with solar.
5. not able to feed grid from battery, when grid peak shaving is set.
6. every morning the hybrid deactivates the gen port (micro inverter input) for 5 to 10 seconds.
7. inverter indicate 0,3V more than in real time is measured.