Watch Fieldpiece Instruments’ Tony Gonzalez do a total external static pressure test in the crawl space of a 130-year old home using the JL3KM2 Dual Port Kit and the Job Link® System App.

Пікірлер: 67
@sknight0391
@sknight0391 4 жыл бұрын
Dang, Tony went above and beyond the call of duty to shoot that video! Good man not even acknowledging all the mouse 💩 on top of that furnace. #GettingDirty 😁👍
@alejandrovazquez4060
@alejandrovazquez4060 4 жыл бұрын
fieldpiece...best tools for hvac techs...
@920HVAC
@920HVAC Жыл бұрын
🤝 good work man! That was a raw environment.
@texasstarniles5
@texasstarniles5 4 жыл бұрын
Thank you very Much Tony for your Video Tony !!
@cindymann3448
@cindymann3448 4 жыл бұрын
That is AWESOME AND TONY IS THE BEST
@jonhvac
@jonhvac 4 жыл бұрын
Very good video guys. Thanks for keeping it real with the rat poop 🐀😄👍💯
@sknight0391
@sknight0391 4 жыл бұрын
I love how he didn't even acknowledge it. 💩👍
@mpugliano
@mpugliano 4 жыл бұрын
Sold I'm buying it Tony!
@rm20235
@rm20235 Жыл бұрын
Is anyone else noticing all that mouse poop in the furnace lol
@gary4645
@gary4645 3 жыл бұрын
Great Job Tony. Remind the customer that some rat poison might be recommended.
@J5NJAX
@J5NJAX 4 жыл бұрын
You the man tony
@Goobermint
@Goobermint 4 жыл бұрын
you can also take the pressure after the coil to see the restriction on the evap coil only, maybe its plugged, gl fixing that on that unit. or maybe their supply registers are all closed. Usually static pressure comes mostly from the negative side. i bet their evap coil is matted up.
@dissociativecat7495
@dissociativecat7495 Жыл бұрын
I don't do hvac, just interested. would like to know if the furnace is in cooling or heating or do you do both ?
@JavierChaparroM
@JavierChaparroM 4 жыл бұрын
You know its real cause of the Squirrel poop lol
@charmedlife6933
@charmedlife6933 Жыл бұрын
Thank you, great presentation…in a tight space, lol
@jessewolfe4136
@jessewolfe4136 Жыл бұрын
So this procedure also helps me but It’s not just kinked duct work, it’s usually undersized duct work (return). Too fast or too slow of blower speed, and or air restriction on evap coil . Because the systems they’re putting out now not only blows more torque(ecm), but they also need more cfm on return.
@FieldpieceProducts
@FieldpieceProducts Жыл бұрын
Thank you for the tip!
@BasketballAve
@BasketballAve 3 жыл бұрын
All the units in the world and you pick the one in “Hades” 😂 great info anyways
@charlylan
@charlylan 4 жыл бұрын
When I check the TES Pressure and I have 0,8 or more...Which is the blower velocity (Low, Medium, or High) that should I set when I do the testing?
@kennethdean4349
@kennethdean4349 3 жыл бұрын
The blower setting should be the one that produces the air flow needed by the system. Compare the TESP to the blower chart and adjust as necessary. A typical cooling system needs between 350 and 400 CFM per ton.
@willskora2055
@willskora2055 2 жыл бұрын
If we want low or no restrictions for the system to work properly why do we give the home owner the ability to create an inefficient system the minute they close a heat/cooling vent?
@grantshvac
@grantshvac 4 жыл бұрын
Interesting to see all the data on the app. I am guessing there are psychrometers installed as well? I didn't see them in the video.
@chrisfrench932
@chrisfrench932 4 жыл бұрын
For that test you don't need the psychrometers, but we do have them in Job Link Probe form. They come in a kit or as individuals. www.fieldpiece.com/products/detail/jl3kh6-job-link-probes-charging-and-air-kit/job-link-probes/
@abnergarcia6252
@abnergarcia6252 4 жыл бұрын
Great video! What did you find that was causing the high static pressure ?
@chrisfrench932
@chrisfrench932 4 жыл бұрын
That's for the next video. Haha.
@pedrocastano6410
@pedrocastano6410 3 жыл бұрын
They only know how to check static pressure and that's all they know, i honestly think they don't even know what's causing the issue, they only do videos for views, and here i am 😂😂😂
@Brokefootchuck
@Brokefootchuck 2 жыл бұрын
Rat turds and Tony's breathing. That s always affects the supply side.
@CarterQuillenP.E.
@CarterQuillenP.E. 4 жыл бұрын
That was an "authentic" historical house with rat turds on the AHU and all.
@inertiaspinner555
@inertiaspinner555 4 жыл бұрын
😂
@josedavidlopez5922
@josedavidlopez5922 3 жыл бұрын
Do these measure air temp as well?
@zeinktm8317
@zeinktm8317 2 жыл бұрын
It's a old comment but I'll still answer it, they don't the only thing this great tool do measure gas pressure/ static/ and pressure switchs however note that for the pressure switchs they can't pressurize a pressure switch, for doing so you need a different type a manometer to do so.
@T-Bone-nk1ng
@T-Bone-nk1ng 3 жыл бұрын
Lol just remarkable that they figured this was a good spot to film a tutorial video. "No lighting? Check. Hot af? Check. Hunched over sitting in the dirt? Check. Rat turds? Check. Alright let's get after it."
@ddwalkerjr
@ddwalkerjr 3 жыл бұрын
This is the absolute best comment I've read in a very very long time
@T-Bone-nk1ng
@T-Bone-nk1ng 3 жыл бұрын
@@ddwalkerjr 😂
@75thshootist
@75thshootist Жыл бұрын
I mean it's real life
@notanewbie1718
@notanewbie1718 4 жыл бұрын
The manufacturers should provide a hole for the furn outlet. What would that cost?
@sknight0391
@sknight0391 4 жыл бұрын
Carrier is the only manufacturer that I've ever seen do that.
@donchaney3
@donchaney3 4 жыл бұрын
Shannon Knight HVAC Trane has holes on the side for the probes.
@jrsmyth9761
@jrsmyth9761 2 жыл бұрын
How do you justify this as a dual port kit? Each probe is a SINGLE port, unlike the Testo version. So, because there are 2 single port manometer probes it is considered a dual port kit?
@jrsmyth9761
@jrsmyth9761 2 жыл бұрын
@@FieldpieceProducts Or you could have ACTUAL dual port manometers by Testo that do the same thing. Your set up is 2 single port manometers. Your very own website description of 1 of these makes that point.
@logancook4790
@logancook4790 2 жыл бұрын
@@jrsmyth9761 there is also an actual dual port fieldpiece manometer that also tests pressure switches this setup is just more convenient for certain applications
@munawarsoomro8958
@munawarsoomro8958 2 жыл бұрын
Ok, I am buying a set based on your video.
@FooDaki
@FooDaki 2 жыл бұрын
thx god we dnt have those systems intalled like that in florida lol
@jimwhite9483
@jimwhite9483 Жыл бұрын
Just found this one. What do you mean "we don't have those installed like that in FL"? I have four clients on PCB where the air handler is under the house. Three of those are installed with the panels facing away from the scuttle hole and no room to crawl over. I have crawl to the lowest spot and squirm over old flex to leak check coil or troubleshooting heat or blower issues while laying in the dirt. Gotta get a skinny youngster on the payroll for those, or pass on the customer to someone else
@andreasgeorgantakis4980
@andreasgeorgantakis4980 2 жыл бұрын
Couldn't your "high" positive pressure be caused by a dirty heat exchanger? Second question, Isn't the positive pressure measurement supposed to be taken 12 inches away from blower?
@jkDLux1
@jkDLux1 Жыл бұрын
No and no
@Brokefootchuck
@Brokefootchuck 2 жыл бұрын
I think tony is working too hard!
@danielvallejo9120
@danielvallejo9120 3 ай бұрын
I like that they filmed in a real location but can't help but to feel sorry for this guys who obviously has spent too much time recently in a air condition office. I keep thinking he needs some water and a oxygen tank😄
@FieldpieceProducts
@FieldpieceProducts 3 ай бұрын
Tony Gonzalez is Director of Training at Fieldpiece Instruments! Not only was he selected as one of the Top 25 Most Influential HVACR Instructors/Trainers of 2024 during the HVAC Excellence Education Conference in Las Vegas, but he is always out on the field testing equipment and training others.
@aaronmiller112
@aaronmiller112 2 жыл бұрын
Watch out for snakes
@MyBallzGotShocked
@MyBallzGotShocked 2 жыл бұрын
I had to put a respirator on just to watch the crawl space part.
@munawarsoomro8958
@munawarsoomro8958 2 жыл бұрын
Nice video, but dang you're out of breath bro. By the way you look much younger on your 2022 videos than 2020 videos.
@yammietits5040
@yammietits5040 9 ай бұрын
I like the technology but for some reason the way the test was performed doesn’t look right… suppose it depends what unit your testing 🤷🏿‍♂️
@FieldpieceProducts
@FieldpieceProducts 9 ай бұрын
Thank you for sharing. We’ll absolutely look into this!
@IamHimathy420
@IamHimathy420 Ай бұрын
Right, the unit me tested said .5 total static pressure and that's what he tested for. He placed the probes according to that unit. What exactly do you mean?
@gordonquickstad
@gordonquickstad 2 жыл бұрын
No pristine lab setup for this video! Nothing like getting down and dirty in the rat turds to keep it real!
@famousdude1239
@famousdude1239 2 жыл бұрын
If there was a duct leaking in a tight/enclosed crawlspace, a supply air leak or a return air leak into the duct...the zeroing would be a worthless measurement. Your entire reading would be bogus.
@75thshootist
@75thshootist Жыл бұрын
I am assuming he started with the furnace off.
@gary4645
@gary4645 3 жыл бұрын
Tony why were you so out of breath going under that house? I'm 55 and fat your not man!
@pedrocastano6410
@pedrocastano6410 3 жыл бұрын
He doesn't even know what he's talking about, 120° to 130° in the crawl space?
@Brokefootchuck
@Brokefootchuck 2 жыл бұрын
Rat turds and marlboros baby. Always bad for tesp. Just ask my cat.
@speckulator7516
@speckulator7516 Жыл бұрын
@@pedrocastano6410 in an attic maybe but not a crawl space.
@HVACShopTalk
@HVACShopTalk 4 жыл бұрын
That system ain't looking too good
@themrmoy40
@themrmoy40 3 жыл бұрын
I don't care about the beautiful historic home !! get to the point !
How to Checkout Blower Settings Using a Manometer
7:06
HVAC School
Рет қаралды 20 М.
Mama vs Son vs Daddy 😭🤣
00:13
DADDYSON SHOW
Рет қаралды 46 МЛН
Secret Experiment Toothpaste Pt.4 😱 #shorts
00:35
Mr DegrEE
Рет қаралды 35 МЛН
A teacher captured the cutest moment at the nursery #shorts
00:33
Fabiosa Stories
Рет қаралды 51 МЛН
JL3KM2 - New Job Link® System Dual Port Manometers
4:20
Fieldpiece Instruments
Рет қаралды 10 М.
Tech Tips: Static Pressure Testing
8:19
Able Distributors - Your HVAC Solutions Delivered!
Рет қаралды 27 М.
Static Pressure Testing and Mapping Demonstration
11:05
Home Performance
Рет қаралды 316 М.
HVAC Static Pressure Testing
4:59
Althoff Home Services
Рет қаралды 90 М.
How to Charge by Superheat With the Fieldpiece Joblink Probes
10:07
TruTech Tools, LTD
Рет қаралды 34 М.
Static Pressure
5:55
Lennox Learning Solutions
Рет қаралды 15 М.
Gas Pressure Test on a GENERAC Generator
7:34
Repair It Don't Wreck It
Рет қаралды 26 М.
Furnace air flow & BTU's using static pressure
16:09
Mitchell Bailey
Рет қаралды 6 М.
Easy Ways to Lower HVAC System Static Pressure
11:05
HVAC Shop Talk
Рет қаралды 24 М.