Please send me the programming instructions for new pcb.
@muhammadasif92544 күн бұрын
Can we use lubricant to O ring??
@muhammadasif92544 күн бұрын
Can we use lubricant to bring??
@anasdaruwala45085 күн бұрын
Hi,I can learn alot from your videos.Please make a video how to diagnose faulty ventilator fan.
@shubhambadgujar99438 күн бұрын
sir I have a question, this aqua signal ignites the gas boiler but is it a continous signal or just a one time ? the reason i am asking this is , i am doing a project and i have connected a electric heater to heat water but i dont want to run both heaters at same time and want to save my gas money so i figured if i just block this aqua signal , i can stop gas boiler from igniting ! so please if you reply it will be a huge help ! thanks in advance!!
@MHKBuildingSolutions8 күн бұрын
@@shubhambadgujar9943 The aqua sensor is a continuous signal as it keep the boiler on whilst the hot water demands remains on. If the aqua sensor is removed from the turbine, the boiler won't recognise the hot water demand hence won't fire up for hot water. I hope it helps however if you have further questions, drop me a line or search MHK Building Solutions Ltd. and you will find me contact details. Regards
@manwindersingh327311 күн бұрын
thanks for videos👍
@AbdulHalim-io7pd19 күн бұрын
Fantastic explained....one of the best video
@MHKBuildingSolutions19 күн бұрын
@@AbdulHalim-io7pd Thanks Abdul.
@izzyizzy278320 күн бұрын
Ma Sha Allah ❤
@MHKBuildingSolutions17 күн бұрын
Thanks a lot.
@DunkingJaffaCakes24 күн бұрын
Get them to change the batteries in the smoke alarm while you're at it.
@MHKBuildingSolutions24 күн бұрын
@@DunkingJaffaCakes good shout buddy :)
@ijjyahmed2001Ай бұрын
Very informative video 👍
@nathanielthomas8110Ай бұрын
Good video
@MHKBuildingSolutionsАй бұрын
@@nathanielthomas8110 thanks buddy, check the rest of videos when you have a minute please.
@cfgman1Ай бұрын
As usual a clear explanation with good video coverage...well done !
@MHKBuildingSolutionsАй бұрын
Thanks a lot. I am glad you found it informative.
@wittywoo9559Ай бұрын
Had this on a new boiler .. warranty covered , they came & changed the gas valve !!!
@MHKBuildingSolutionsАй бұрын
It's a common fault on these :(
@wittywoo9559Ай бұрын
Good video .. thanks .. how old was that boiler ??
@MHKBuildingSolutionsАй бұрын
This was around 7 years old I believe
@wittywoo9559Ай бұрын
@MHKBuildingSolutions OK thanks .. good content
@e.colemantlpss6406Ай бұрын
"How to calculate Amps". Sorry did I miss that bit?
@MHKBuildingSolutionsАй бұрын
The expectation is to encourage you to work it out. I am sure you would know how to however if you don't then let me know :).
@user-li8gr8ur8lАй бұрын
That was top quality content brother. Keep it up❤. Thank you
@MHKBuildingSolutionsАй бұрын
Thanks brother
@fatzz5800Ай бұрын
Thanks that was really helpful 👍
@MHKBuildingSolutionsАй бұрын
Glad to help:)
@johnmcgiv1Ай бұрын
Excellent video, many thanks.
@MHKBuildingSolutionsАй бұрын
Many Thanks.
@sdgelectronicsАй бұрын
Current could be anything if you don't tell us the power factor.
@MHKBuildingSolutionsАй бұрын
True, call it 0.95
@javediqbal13432 ай бұрын
Another fantastic video from a guru
@MHKBuildingSolutionsАй бұрын
Thanks a lot.
@Bd30sf2 ай бұрын
No
@MHKBuildingSolutions2 ай бұрын
Why not?
@user-du8gr9sh4f2 ай бұрын
Yes
@MHKBuildingSolutionsАй бұрын
Soon :)
@Ghose-jz6ut2 ай бұрын
Masha Allah ❤
@MHKBuildingSolutions2 ай бұрын
JazakAllah kher
@user-li8gr8ur8l2 ай бұрын
Simple yet effective method of making sure there is a good connection. Thanks for that brother❤
@MHKBuildingSolutions2 ай бұрын
My pleasure
@wahabtahir91432 ай бұрын
Very informative video.
@MHKBuildingSolutions2 ай бұрын
Thank you.
@AlanSmith-xu3lo2 ай бұрын
Just want to know what taps to turn of underneath the boiler to isolate the water.
@MHKBuildingSolutions2 ай бұрын
Hi Alan, it depends on which boiler you have. If you can send me a picture of your boiler, I will be able to guide you better. You can get my contact information by searching "Mhk Building Solutions" on Google :).
@cfgman13 ай бұрын
A good introduction to testing harnesses.
@MHKBuildingSolutions3 ай бұрын
Thanks
@user-li8gr8ur8l3 ай бұрын
Jzk brother. That was interesting. Thanks for the tip❤
@MHKBuildingSolutions3 ай бұрын
You are welcome brother
@Royalgasyork3 ай бұрын
Yes
@MHKBuildingSolutionsАй бұрын
Soon :)
@hussainkhan66303 ай бұрын
very good video they getting better.
@MHKBuildingSolutions3 ай бұрын
JazakAllah kher brother
@user-li8gr8ur8l3 ай бұрын
That was a top vid brother❤. Better than the heat exchanger.😂
@MHKBuildingSolutions3 ай бұрын
Thanks a lot brother 😄
@russellthomas93913 ай бұрын
Good work - I would have replaced the flow and return pipes - those rubber hoses are problematic as you may already know
@MHKBuildingSolutions3 ай бұрын
Yes mate good call. One for the next time :)
@CommercialGasEngineerVideos3 ай бұрын
Totally agree, didn't think the were still around
@AsadAli-mv7si3 ай бұрын
Main k Karan honr
@MHKBuildingSolutions3 ай бұрын
Kujh bhi nai dost bas Dua Kara ker
@paulvickers77093 ай бұрын
Enjoying the videos can you do a boiler sequence of operation please
@MHKBuildingSolutions3 ай бұрын
Very soon mate.
@trusay83383 ай бұрын
Thanks for making this video .. could you please make a video explaining the simple way to carry out a boiler service. Thanks.
@MHKBuildingSolutionsАй бұрын
Yes soon.
@user-li8gr8ur8l3 ай бұрын
That was a cracking video. This looks like a pain of a job. Not the best boilers to work on
@MHKBuildingSolutions3 ай бұрын
Yes it was slightly tricky however the customer insisted to have the old boiler fixed so we complied.
@user-li8gr8ur8l3 ай бұрын
Nice job. A plumbers best friend hair drier to the rescue.❤. Thanks for that it was very useful
@MHKBuildingSolutions3 ай бұрын
I am glad you enjoyed the video:)
@macpatel78103 ай бұрын
Not a simple service then 😊. How much was the cost of that repair ? The burner door seal and electrodes are also quite pricey on these ..
@MHKBuildingSolutions3 ай бұрын
The price climbed up to £400 including parts.
@ryandow39543 ай бұрын
Great video!
@MHKBuildingSolutions3 ай бұрын
Thanks buddy
@adija123 ай бұрын
Surprised you didn't change the insulation pad on burner
@MHKBuildingSolutions3 ай бұрын
That will be done on the next service:)
@BriandJ-nl7pr3 ай бұрын
Salam Alaikum Brother, these videos are very informative. Keep them coming please.
@MHKBuildingSolutions3 ай бұрын
I am glad that you guys are finding it informative. I will try to continue.
@BriandJ-nl7pr3 ай бұрын
Selam Alaikum brither. This was very informative, especially for new gas engineer. Please follow up in more detail about the cylinder stat. And also other controls such as Heatmiser ( for underfloor heating ) and definitely on in depth video on opentherm wiring and it’s benefits. May Allah reward your efforts. This was fantastic. 🤲
@MHKBuildingSolutions3 ай бұрын
W sallam. Keep an eye out and press the bell icon so you get a notification for the future videos inshAllah
@CommercialGasEngineerVideos3 ай бұрын
Was hoping for an Amp test and microfarad test but maybe that's in part 2. Keep up the good work
@MHKBuildingSolutions3 ай бұрын
I was afraid that it would become too much to absorb but yes defo in part 2 :)
@cfgman13 ай бұрын
Excellent video ...quite an innovative method of teaching ! You have a natural ability to teach sir.
@MHKBuildingSolutions3 ай бұрын
Many thanks
@cfgman13 ай бұрын
Useful information for all heating engineers
@MHKBuildingSolutions3 ай бұрын
Thanks for your comment. Please check my other videos when you get a minute.
@cfgman13 ай бұрын
Good video
@MHKBuildingSolutions3 ай бұрын
Thank you. I am glad you enjoyed it.
@davidtwist92423 ай бұрын
Great video hopefully more to come x
@MHKBuildingSolutions3 ай бұрын
I am glad you found it good. Please check my other videos.
@Patent2473 ай бұрын
Hello mate, had this exact same fault sequence. Changed the gas valve & all good for a couple of months, then started throwing the same faults again but managed to clear it and all good at the mo. 🤞. Seems to be common problem on these... Pcb next or scrapping tbh 😂
@MHKBuildingSolutions3 ай бұрын
I would say buy a refurbished PCB from eBay and change it if it gives you the fault again. These are very reliable boilers so worth keeping tbh.
@cfgman13 ай бұрын
Probably the most comprehensive explanation I gave come across as you deal with both gas and electric issues...well done. Keep up the standard This fault was due to the gas valve and is a known design fault on the vaillants pros and plus which was kept quiet for many years.
@MHKBuildingSolutions3 ай бұрын
@@cfgman1 Thanks for your kind comments.
@user-sw2jb1lz2c3 ай бұрын
Mashaallah Yr explanation Is very good may Allah put brakat for u .