15 Minute Tech Talk - 75 kVA Transformer

  Рет қаралды 39,884

Thomas Domitrovich

Thomas Domitrovich

4 жыл бұрын

This session will look at a 75 kVA transformer and select primary / secondary OCPDs as well as primary and secondary transformer conductors.
For more information on Eaton dry-type low voltage transformers please see the following link:
www.eaton.com/us/en-us/produc...

Пікірлер: 50
@geofferyromany4634
@geofferyromany4634 3 жыл бұрын
As a newbie on learning about transformers I was a little confused about the formula you used. After re-reading my text and doing the calculation according to the text, I got approx values for primary and secondary current FLA. Happily, I realized that your formula is a shortcut and accurate (within an approx). I will use it in the future for swift calculations. Thx. Good video for newbies like me. Keep it up
@garbo8962
@garbo8962 3 жыл бұрын
Glad you mentioned selective ampere selection. Retired from a large hospital/research center where they talked about this but never did antyhing on it. Several times a zone mechanic was replacing a 277 volt breaker and caused a short circuit where the 225 amp tripped and not the 20 amp branch circuit breaker. This occured in at least 3 large ( 10 to 14 floor ) buildings.
@TDUNPLUGGED
@TDUNPLUGGED 3 жыл бұрын
Really appreciate the feedback. I have often been told that events like what you described never occur in a hospital. Would love to learn more.
@carlubambi5541
@carlubambi5541 Жыл бұрын
This happened to me at York University Campus .3 phase 600v/347V lighting control circuit rated for 20 amp single phase breaker took out the main 3 phase 100 amp lighting control breaker .Crazy stuff happens with impedance drops and AIR ratings of breakers .
@educationpower1823
@educationpower1823 4 жыл бұрын
Hey Tom. Great job on these tech talks. Robert from Omaha
@joeballard3027
@joeballard3027 2 жыл бұрын
Really like listening to this guy lay down some riffs
@scfc96g
@scfc96g Жыл бұрын
nice i just put in a 75 kva transformer and panelboard, it was a great tech talk
@KevinCoop1
@KevinCoop1 Жыл бұрын
One of Eaton’s competitors makes 250 amp MCB and 250 amp buss panels as a standard for a good reason. Many times if 250 is specified, their competitors, like your company, couldn’t compete with the price. Economics pay a huge role in the decisions. Especially if you are the contractor and designer.
@TDUNPLUGGED
@TDUNPLUGGED Жыл бұрын
Thanks for joining in the discussion @kevinCoop1.
@enriquetrujillo7864
@enriquetrujillo7864 2 жыл бұрын
Incredibly informative video thank you
@LittleOldBoat
@LittleOldBoat 3 жыл бұрын
You got my attention, thanks for your time!
@TDUNPLUGGED
@TDUNPLUGGED 3 жыл бұрын
Glad I could help!
@josecruz490
@josecruz490 3 жыл бұрын
Great video 👍👍
@intheskymusic
@intheskymusic 3 жыл бұрын
Take an hour if you have to brother, great information like always.
@educationpower1823
@educationpower1823 4 жыл бұрын
Your sound is 👍
@lawoull.6581
@lawoull.6581 Жыл бұрын
awesome video
@4abettaworld
@4abettaworld 3 жыл бұрын
Thank you brotha, appreciate you!
@TDUNPLUGGED
@TDUNPLUGGED 3 жыл бұрын
Any time!
@BlackAdam2784
@BlackAdam2784 3 жыл бұрын
**Very good video !!
@carlubambi5541
@carlubambi5541 Жыл бұрын
STANDARD PRACTICE IS WIRE FOR 125% IN CANADA FOR WIRE SIZE AND NOW SOME AREAS WANT OVERSIZED NEUTRAL .All because of harmonics from VFDs And Switch mode power supplies .Ztrap is optional
@TDUNPLUGGED
@TDUNPLUGGED Жыл бұрын
Thank you Carlu for that note. Very good point on oversizing the neutrals!
@nestorporquirino5595
@nestorporquirino5595 11 ай бұрын
LOVE IT 😍🤩👍
@kevinokuku7289
@kevinokuku7289 2 жыл бұрын
Thanks for the video. I have a 30 kva transformer. I need to feed 415vac to the input. I require 240vac at the output and not 120.how do i achieve that?
@AlfredoSuarez-rl3qf
@AlfredoSuarez-rl3qf 3 ай бұрын
On the field we use 125% calculation for primary and secondary OCPD.
@AlfredoSuarez-rl3qf
@AlfredoSuarez-rl3qf 3 ай бұрын
Thanks for this master class.
@TDUNPLUGGED
@TDUNPLUGGED 2 ай бұрын
Sure thing. I agree that 125% is very common. I think a little depth of knowledge helps to understand the why's. You have to love those rules of thumb that get you through some hard parts.
@RonaldJamesR
@RonaldJamesR 3 жыл бұрын
great job. however I would like to see the wiring process. thank you.
@TDUNPLUGGED
@TDUNPLUGGED 3 жыл бұрын
Hey Ronald. thanks for the feedback. I"ll see what I can do on the wiring. going to have to get a video on that in our experience center.
@danielno20
@danielno20 Жыл бұрын
What gauge wire did you use for high and low voltage?
@educationpower1823
@educationpower1823 3 жыл бұрын
Nice job Tom as usual. I thought you needed to supply ocpd to the load possible regardless...
@TDUNPLUGGED
@TDUNPLUGGED 3 жыл бұрын
Thanks Robert. Yea, that primary OCPD is tricky because you have that pesky little detail called inrush :)
@rabindranauth1235
@rabindranauth1235 3 жыл бұрын
Do you have troubleshooting videos for these transformers
@demetriotizcareno980
@demetriotizcareno980 2 жыл бұрын
Thanks
@how2diy123
@how2diy123 3 жыл бұрын
So if I am installing a 75kva Step Up i can just use all the info you just provided but just flip info on primary and secondary ?
@TDUNPLUGGED
@TDUNPLUGGED 3 жыл бұрын
step up transformers are a little different beast. Make sure the transformer is listed for back feeding and as far as I can tell you make the same calculations. Inrush on that will be a little different too. I'll do some research and put a program together as this could be a good discussion on the program.
@marktheunitedstatescitezen185
@marktheunitedstatescitezen185 Жыл бұрын
Thanks , you really know what you’re speaking ! Any and all advice is welcoming! “ My breaker box in my house is 100A / 120v 2 Phase - I’m installing for electrical back~up only a 5KVA Solar Inverter 230v charge controller 48v PWM what I see is the inverter 230v One Phase the L1 is 115v & the Neural is Hot line of 115v & the ground is a ground ! What’s you’re idea of using the L1 = 115v & the Neutral = 115v into a 20A Double Pole breaker to back-feed my breaker box all One Phase of 115v & the inverter at 5KVA is 86A and my house per month uses between 3-3,500KW a month and I’m going to use a SIEMENS Transformer MTO100A 480-220 input One Phase & Output 240-110 Two Phase ~ Off my Order inverter to the 20A Double Pole breaker . Sounds good ?
@aten9754
@aten9754 9 ай бұрын
Wth are you talking about. Better call electrician
@presicionturning5672
@presicionturning5672 3 жыл бұрын
so can i run a 3phase cnc machine from 1phase power source using this type of transformer? thanks
@TDUNPLUGGED
@TDUNPLUGGED 3 жыл бұрын
That would take a bit more than just this transformer.
@nisuquayum7817
@nisuquayum7817 Жыл бұрын
for the secondary time i would put 250 amps panel broad
@TDUNPLUGGED
@TDUNPLUGGED Жыл бұрын
Thanks for commenting and adding the value of the video. I agree with you. There are so many options in these applications.
@sungkim16
@sungkim16 2 жыл бұрын
Why is the optimum ocpd 100amps and not 115A
@TDUNPLUGGED
@TDUNPLUGGED 2 жыл бұрын
sungkim1189, I would agree that a 115A OCPD would be the appropriate solution for that application.
@KevinCoop1
@KevinCoop1 Жыл бұрын
115A is not a standard OCPD rating. Standard ratings are 100, 110, 125, and 150 amps. For 35 years, I used 125 amps on 75Kva rated primary.
@nisuquayum7817
@nisuquayum7817 Жыл бұрын
.9 is the efficiency of the transformer
@TDUNPLUGGED
@TDUNPLUGGED Жыл бұрын
Thanks for commenting and adding to the value of the information!
@emmanueltsey3417
@emmanueltsey3417 Жыл бұрын
Please I needed to do a house wiring of both 110v and 220v after it all it was 30 socket in number for the 110v and I want to know the type of the step down transformer to use in order to power the entire room.thank you
@ricsalsa
@ricsalsa Жыл бұрын
x the equation i think u will mixt up people more than anything lol u should put all the numbers on the screen maybe it will help...maybe lol.
@alammd4673
@alammd4673 Жыл бұрын
😜
15 minute Tech Talk - August 4, 2020 - 30kVA Transformer
18:03
Thomas Domitrovich
Рет қаралды 10 М.
100 Days of Article 100: Separately Derived System
7:15
Ryan Jackson
Рет қаралды 24 М.
Каха заблудился в горах
00:57
К-Media
Рет қаралды 3,1 МЛН
Mama vs Son vs Daddy 😭🤣
00:13
DADDYSON SHOW
Рет қаралды 36 МЛН
A closer look at Padmount Transformers
10:15
Bobsdecline - Lineman blogger
Рет қаралды 644 М.
Where Does Grounded Electricity Actually Go?
19:36
Practical Engineering
Рет қаралды 5 МЛН
120/240 and 120/208 Volt Transformer Secondaries
14:41
Dave Gordon
Рет қаралды 280 М.
BYD: Factory Tour & Full Range of EVs | FULLY CHARGED
22:41
Fully Charged Show
Рет қаралды 850 М.
How 3 Phase Transformers Work - why we need them
24:24
The Engineering Mindset
Рет қаралды 480 М.
Power & Distribution Transformer | What are the differences | TheElectricalGuy
10:30
Gaurav J - TheElectricalGuy
Рет қаралды 9 М.
Installing 3 phase transformer | Starting a Machine Shop 17
12:09
Erik Cortina
Рет қаралды 42 М.
Transformer Protection Basics
59:53
Electrical Engineering Knowledge Sharing
Рет қаралды 6 М.
Я купил первый в своей жизни VR! 🤯
1:00
Вэйми
Рет қаралды 2,5 МЛН
iPhone, Galaxy или Pixel? 😎
0:16
serg1us
Рет қаралды 1,3 МЛН
Это - iPhone 16 и вот что надо знать...
17:20
Overtake lab
Рет қаралды 132 М.