Auxiliary Grounding Electrodes [250.54], NEC 2023, (10min:54sec)

  Рет қаралды 5,142

MikeHoltNEC

MikeHoltNEC

3 ай бұрын

Grounding electrodes that are not required by the NEC are called “auxiliary electrodes” and are connected to the equipment grounding conductors. Since they serve no purpose related to electrical safety, they have no NEC requirements. Watch this video where Mike and the team discuss the “non” requirements of NEC section 250.54.
This video is extracted from Mike Holt's 2023 Bonding and Grounding Video Library, for more information visit www.MikeHolt.com/Bonding or call 888.632.2633.
For decades, Mike Holt Enterprises has been the go-to resource for electrical training. Our mission is to empower electrical professionals like you to master the Code, excel in exams📝, and elevate your electrical knowledge..
👉 Explore Exam Preparation Tips and Training at www.MikeHolt.com/examprep
🚀 Find Electrical CEU courses at www.MikeHolt.com/CEU
⬆️ Level Up your school's electrical training program with Mike Holt Enterprises at www.MikeHolt.com/Instructors
Whether you're gearing up for an exam or looking to enhance your electrical knowledge, we've got you covered. We offer instructor and curriculum support, a variety of continuing education options, free videos, graphics, and a wealth of valuable resources.
📌 Stay Connected:
/ mikeholtenterprises
/ mikeholtenterprises
/ mike-holt-enterprises-inc
🔗 www.mikeholt.com
✅ Don't miss out on the latest updates and exclusive content. Subscribe to this channel now - Click here to subscribe: www.youtube.com/@MikeHoltNEC?...

Пікірлер: 19
@ChrisBlaneyOfficial
@ChrisBlaneyOfficial 3 ай бұрын
I had a customer just last week get upset with me that I did not connect his new Generac generator to the ground rod he drove beside it. I tried to explain this very point but I don't believe he understood it. What are the odds this video comes out a few days later! Thanks for another great explanation of the code!
@MikeHoltNEC
@MikeHoltNEC 3 ай бұрын
You are most welcome.
@hgbugalou
@hgbugalou 3 ай бұрын
I like superfluous better because it really puts a pin in how unnecessary it is.
@clems6989
@clems6989 2 ай бұрын
I'll add that in industrial electronics, grounding is a type of black magic...
@MikeHoltNEC
@MikeHoltNEC 2 ай бұрын
You are so correct!
@clems6989
@clems6989 2 ай бұрын
Yes, the adding a ground rod near the equipment originated with trying to mitigate noise issues in a poorly laid out system. When these high speed electronics hit the market, and all the high speed switching and harmonics thereof, was a new animal and there was little understanding of them at first. Hopefully we have since learned more about them and understand them a little better.. Well hopefully..... :)
@MikeHoltNEC
@MikeHoltNEC 2 ай бұрын
Excellent comment.
@Icehso140
@Icehso140 2 ай бұрын
Not needed as per code is similar to the EIA/TIA standards that restrict pipe bends to 180 degrees and disallow conduit bodies for communication cables. We had to follow specs on equipment with electronics. Installed them per specs, did not violate code, got paid, went home.
@jeffl3506
@jeffl3506 3 ай бұрын
In the video you discussed how you thought that the auxiliary electrode was not a good idea for the generator example but I was hoping you would expound this to the light pole as its very common requirement for an auxiliary electrode to be driven at a light pole especially when there is also lightning protection on the light pole. So does an auxiliary ground at light poles help or is the same as the generator example, it causes more problems? This has been an ongoing debate about how to keep the surge from a lightning strike on light poles from getting back to the electrical panel feeding the light poles. Any advice here?
@MikeHoltNEC
@MikeHoltNEC 3 ай бұрын
Driving a rod or not will not reduce any surge backfed current. But maybe having SPD on the circuits to the outside pole lights would be helpful.
@jeffl3506
@jeffl3506 Ай бұрын
Thanks Mike, that is what I was thinking was going to be the answer. May not save the pole that gets the direct strike but at least minimize the damage to equipment inside.
@MikeHoltNEC
@MikeHoltNEC Ай бұрын
@@jeffl3506 a ground rod serves 'no' purpose at a metal light pole and doesn't protect the wiring inside the metal pole (Faraday Cage).
@bryanz5904
@bryanz5904 3 ай бұрын
So if the outdoor electrical equipment sets an Auxiliary Grounding Rod, a good additional design is also setting an SPD at the Pannel, to protect the EDS inside the building. SPD should based on the 10/350 test wave.
@MikeHoltNEC
@MikeHoltNEC 3 ай бұрын
Surge protection in this example would not make a difference from the induced current from the lighting. SPD are always a good idea. Please watch the entire video, not just the short. Click on the link embedded on the bottom of the short.
@bryanz5904
@bryanz5904 3 ай бұрын
@@MikeHoltNEC Ye, thanks Mike:)
@jimmceachern8967
@jimmceachern8967 2 ай бұрын
But what about a bonded neurtral generator with gfci? Wouldn't that need a three pole transfer switch to switch both hot legs and your neutral therefore your generator would need its own electrode system correct?
@MikeHoltNEC
@MikeHoltNEC 2 ай бұрын
Yep, per 250.30(A). Wow... you are one sharp cookie...
@chauvinemmons
@chauvinemmons 2 ай бұрын
Mike what about lightning supresion systems and more then one grounds that are not connected. My first asumption is never connect this to the main panel ground.
@MikeHoltNEC
@MikeHoltNEC 2 ай бұрын
@@chauvinemmons Lightning protection systems are required to be bonded to the building grounding electrode system in accordance with 250.106.
Grounding, System and Equipment [250.4, 2020 NEC]
33:35
MikeHoltNEC
Рет қаралды 100 М.
AFCIs, Clearing Series and Parallel Arcing Fault
17:47
MikeHoltNEC
Рет қаралды 6 М.
Children deceived dad #comedy
00:19
yuzvikii_family
Рет қаралды 8 МЛН
Дибала против вратаря Легенды
00:33
Mr. Oleynik
Рет қаралды 4,9 МЛН
LOVE LETTER - POPPY PLAYTIME CHAPTER 3 | GH'S ANIMATION
00:15
The Most Confusing Part of the Power Grid
22:07
Practical Engineering
Рет қаралды 1,3 МЛН
2020 NEC Grounding & Bonding Course- Grounding Electrodes Sample
58:43
Suitable Wiring Methods [110.8], 2023 NEC, (6min:45sec)
6:45
MikeHoltNEC
Рет қаралды 9 М.
Grounding, Auxiliary Grounding Electrode [250.54, 2020 NEC]
13:40
Grounding, Objectionable Current [250.6, 2020 NEC]
18:15
MikeHoltNEC
Рет қаралды 23 М.
Connecting Solar to the Grid is Harder Than You Think
18:48
Practical Engineering
Рет қаралды 1 МЛН
Grounding Versus Bonding (26min:26sec)
26:26
MikeHoltNEC
Рет қаралды 246 М.
How Surge Protective Devices Function
10:41
MikeHoltNEC
Рет қаралды 8 М.
Earthing vs. Bonding: What's the Difference?
6:38
eFIXX
Рет қаралды 67 М.
Pushmatic Panels & Breakers - ARE THEY DANGEROUS?
9:48
Electrician U
Рет қаралды 50 М.
Children deceived dad #comedy
00:19
yuzvikii_family
Рет қаралды 8 МЛН