Clamp Meters New & Old for Current Measurement

  Рет қаралды 90,120

John Ward

John Ward

Күн бұрын

Clamp meters, how they work and how to use them.
Includes a modern example by Fluke, and two older ones by Sangamo Weston and Ferranti.
Patreon: / jwflame
Contact info, sending stuff in etc.: xo4.uk/?YTT
Website: xo4.uk/?Cmp

Пікірлер: 67
@mikeZL3XD7029
@mikeZL3XD7029 8 ай бұрын
Hi JW, That Ferranti clamp meter brings back some memories. Back when I was a 2nd year apprentice, my boss put me on-call, now I only had an orange set of Duspols and a multimeter, as that was all I could afford on the wages of the day. I was loaned one of them Ferranti clamp meters and one of (I think) the original wind-up 500V Megger test instruments. Even in 1987, these instruments looked like they had been resurrected from the tomb, but hey, not once did they fail me, I sorted out a lot of problems with these two instruments by themselves, until I could eventually afford my own gear. Some months later, a newer apprentice dropped the clamp-meter onto a concrete floor and it shattered into a million pieces, we were all pretty peeved about this, it was like the death of a close friend.
@JahanZeb1976
@JahanZeb1976 7 жыл бұрын
Excellent tutorial on clamp meter which is always needed. Keep the great work up.
@NeilVanceNeilVance
@NeilVanceNeilVance 7 жыл бұрын
I bought one of these 10 years ago and I thought it was faulty as I was testing on multiple wires ie just what you cleared up, LN&E. Silly me! thanks for your great generous videos.
@alanmusicman3385
@alanmusicman3385 2 жыл бұрын
Me too! Now I know.
@mrm5823
@mrm5823 4 жыл бұрын
Clear and instructive, thank you.
@juanbartolome826
@juanbartolome826 3 жыл бұрын
Thanks for the video I had a question on my test about looping 4times in a clamp ammeter this answered my question
@jgdublin
@jgdublin 7 жыл бұрын
thanks again for your good work John
@chrisflynn6474
@chrisflynn6474 4 жыл бұрын
Great video, thanks!!
@rodolfocarrillo1254
@rodolfocarrillo1254 3 жыл бұрын
thankyou!!, I need to simulate very high current in a safe way, looping the wire will will WORK.
@victor7530
@victor7530 5 жыл бұрын
Thanks for the information.
@blow0me
@blow0me 3 жыл бұрын
Any thoughts or tests on the Fluke non contact "clamp" meters ? Like the T6-600 ?
@vinnie7020
@vinnie7020 7 жыл бұрын
could you do a video about grid fused spurs or how to apprach a kitche where multi fused spurs are required. also video on different types of cable and sizes to use for what starting with domestic e.g outdoor indoor use.
@jgwalling
@jgwalling 5 жыл бұрын
Not sure if you know this but fluke makes a clamp on meter now that will read voltage through the clamp part
@donalddodson7365
@donalddodson7365 Жыл бұрын
Very nice. Thank you.
@Bodragon
@Bodragon 5 жыл бұрын
Beautiful
@RaviSingh-xo7my
@RaviSingh-xo7my 6 жыл бұрын
Hey John.. !! kindly help me bro i am gonna for buy Meco 1008 trms clamp multimeter. does it better then UNI-T UT 203 and in same price others ? kindly tell me it's urgent?
@KirbyONeilDJSpeed
@KirbyONeilDJSpeed 2 жыл бұрын
Excellent Tutorial JW , would you have a video on the 2 Pen uni-t ut15c volt tester, wondering if its any Good??
@Paulrogbucksbeach
@Paulrogbucksbeach 3 жыл бұрын
Hi John. Why don't high quality Clamp meters have HRC fuse protection like their multimeter counter parts ? Even fluke doesn't seem to fuse clamp meters even though they measure voltage Any information on this would be excellent
@henryrobinson9837
@henryrobinson9837 5 жыл бұрын
a lot of people would like to see an old simpson meter demo.old electricians didn't have all the tools of today,good video,
@shaunbeard593
@shaunbeard593 6 жыл бұрын
Hi John as I'm not qualified would I be permitted to run cables to position and connect things like sockets or ceiling roses under part p thanks
@jwflame
@jwflame 6 жыл бұрын
Part P is just this: xo4.uk/x/part_p_requirements.png so most people should easily be capable of complying with it. Qualifications are not required, although they may be useful.
@michaelagnew7825
@michaelagnew7825 4 жыл бұрын
Maybe a childish question here but at what point does the N become without voltage in a circuit. Assuming the are 2 present loads on a single circuit and I took a reading of N and E after the second would that then be zero voltage
@ianharrison6597
@ianharrison6597 7 жыл бұрын
Nice one. That Ferranti 'tong' meter meant business. Easily safe for Cat. VIII (!) Even with the plug-in devices available, it's a pity that no one seems to have found a way of measuring the current in a flex containing both L + N conductors. Unless it just isn't considered to be worth the R & D.
@ianharrison6597
@ianharrison6597 7 жыл бұрын
Strange. With magnetic coupling to sense a current and then power electronics to track the rise and fall of that current, it seems (that is should be) quite possible to calculate the value of the current anywhere on the sine wave, positive, or negative. Obviously a suitable timebase value needs to be used to be able to track whatever the frequency of the AC being measured is. We've done without for this long; so I guess a properly working device isn't going to happen soon.
@jwflame
@jwflame 7 жыл бұрын
The problem is having something which can detect the magnetic field from one conductor while ignoring the opposing field from the other conductor. In a flex or cable the two conductors will be very close together so it is exceptionally difficult to design a device to measure only one of them.
@ianharrison6597
@ianharrison6597 7 жыл бұрын
I think that this is just one of those 'challenges' that provides some thinking exercise for those quiet moments. :-) With the availability of plug-in measurement devices for mains-powered equipment, I guess that manufacturers just don't see any worth in R & D spending to overcome the cancellation-effect caused by the proximity of the conductors in a normal flex. Give me the rest of my life and I'll give it some thought!
@Deebz270
@Deebz270 3 жыл бұрын
@@jwflame And those condustors are usually helically wound within the flex itself.
@andreim841
@andreim841 7 жыл бұрын
How accurate are these devices taking into account that the magnetic permeability differs from wire to wire depending on the type and thickness of the isolation used? Thanks!
@warrengray610
@warrengray610 7 жыл бұрын
Hi John, how do I contact you with bits and pieces, you doubtless have noticed I be tended to contact you via the video comments section, is there another way? I actually have a question if I might seek your opinion, kind regards Warren
@jwflame
@jwflame 7 жыл бұрын
kzfaq.infoabout
@warrengray610
@warrengray610 7 жыл бұрын
John Ward Hey John the link you sent doesn't work
@Deebz270
@Deebz270 3 жыл бұрын
John also has a Facebook page... Which I've already messaged him on, though I'm still awaiting a reply, but he's obviously a busy guy and it is the Xmas break.
@derektodd4126
@derektodd4126 7 жыл бұрын
where is best to get a uk line splitter or monitor tool suitable for clampmeter and small currents.
@astrazenica7783
@astrazenica7783 2 жыл бұрын
I bought cheapest single gang extension socket and exposed a section of split wires carefully. Purpose built splitters are expensive and only really a single model still being made
@uk_prepper6775
@uk_prepper6775 6 жыл бұрын
What would you need to use a clamp meter for in a domestic installation? really great videos, thanks for taking the time to make them.
@jwflame
@jwflame 6 жыл бұрын
Current measurement for a single circuit, or the entire installation. The main advantage is that you don't have to disconnect any wires to measure the current.
@dasy2k1
@dasy2k1 4 жыл бұрын
Especially with the ones that have a minmax function (which most better ones do now) it's the sort of thing that you might leave on someone's meter tails for 24h to see the max demand to know of their incoming supply needs upgrading before any additional circuits are added (such as an electic car charging point which can draw significant current )
@Deebz270
@Deebz270 3 жыл бұрын
@@dasy2k1 Which is similar to the Energy Efficiency Module that is supplied by British Gas and other ESPs... Only that is a permanent installation and does not give readings in amps, only watts.
@rhys406
@rhys406 Жыл бұрын
Being a heating engineer I normally use mine to prove immersion heaters are working
@garethatkinson7765
@garethatkinson7765 7 жыл бұрын
if you measure line and neutral and get a reading isn't that a sure sign of current leakage? as they aren't canceling each other out?
@jwflame
@jwflame 7 жыл бұрын
Yes, and that is one method of detecting earth leakage. It does need a clamp meter which can accurately measure in the 1mA range - many do not, including the Fluke one in the video.
@Ogma3bandcamp
@Ogma3bandcamp 7 жыл бұрын
Thought you were going to take it one step further John and show the new ones that measure DC current.
@blow0me
@blow0me 3 жыл бұрын
I've used a cheap UniT clamp meter for DC for a few years for automotive stuff. Seems to work fine. Although can see a bit of drift at low currents, device always needs reset before use. No idea how accurate it is, but seems ok for a quick test
@tomcardale5596
@tomcardale5596 3 жыл бұрын
@@blow0me Even expensive DC clamp meters need to be zeroed before use. I've got a 5 year old Uni T and a much newer Appa/Amprobe/RS components one which is a much nicer meter to use, but they read about the same.
@Equiluxe1
@Equiluxe1 7 жыл бұрын
Some of the old clamp meters were just a moving iron movement, the magnetic field of the wire did all the work. I used to have two like that one went to 30 amps and the other was 400 and 800 the ranges were made by a stand off bracket on the back of the meter the furthest out being the higher range. Might still have them in the shed somewhere.
@jusb1066
@jusb1066 7 жыл бұрын
i used to have 2 ones for car use, one that measured 30 a and one 600a, to measure alternator and starter current, very simple, measured into the postive and negative so you always got a measurement. just lay on the battery wire to see how your alternator is coping etc
@astrazenica7783
@astrazenica7783 2 жыл бұрын
I'm a newbie, recently bought the cheapest most useless single gang extension plug with no actual extension. Just enough to remove enough insulation and split the wires for a clamp. I did for a second think the meter was faulty when I tried it on full power cable. Didn't take me long to realize in fairness
@ThomasHaberkorn
@ThomasHaberkorn 6 жыл бұрын
General question: On a DC clamp meter, does shielding around the wire influence the measurement?
@1bigsyd
@1bigsyd 7 жыл бұрын
How do the open ended meters work
@jwflame
@jwflame 7 жыл бұрын
Hall effect sensor, there is usually a line or mark where the sensor is which is also where the wire must be placed for accurate readings. On the Fluke ones, it's at the bottom of the U shaped slot.
@richie5629
@richie5629 Жыл бұрын
When measuring DC,why do u get two different readings if u turn the clamp meter around?
@jwflame
@jwflame Жыл бұрын
DC clamp meters must be zeroed before each use and after moving them to eliminate the effect of the Earth's magnetic field and any other magnetic fields nearby. Moving it without zeroing again will give incorrect results.
@richie5629
@richie5629 Жыл бұрын
@@jwflame ohh, ok thanks much. Was measure short circuit current from a pv module and was getting like 6.6A and when i flipped the clamp meter i was getting around 2.1A.
@astrazenica7783
@astrazenica7783 2 жыл бұрын
Why can't you use a single probe like the clamp but smaller range. Contact probe so it's maximum closeness not conducting to circuit. Are 2 probes always required for bridging circuit. Couldn't pass load in and out of single probe in single contact point
@tonyb83
@tonyb83 5 жыл бұрын
I'm setting up a DIY woodwork shop and want to measure the current each machine is drawing. I was thinking of getting a clamp meter like the one in this video BUT at 8.14 in this video you referred to 'one of those monitor things you can just plug in....because they are fairly readily available'. If that is what I need to get, please let me know what it is. Thanks
@jwflame
@jwflame 5 жыл бұрын
One random example: www.screwfix.com/p/energenie-ener007-energy-saving-power-meter-socket/3477h , many similar ones available.
@Deebz270
@Deebz270 3 жыл бұрын
I'm sure that AVO brought out an 'add-on' clamp module that could be plugged into the ampere terminals of a standard multi-meter. . Very simple device to contstruct really and totally safe to use. Also the British Gas - Energy efficiency display module, that is available to anyone, but comes free with a contract, uses the same technology, as one has to place a current sensing coil around the line tail from the house meter to the consumer unit. This coil, in turn, feeds a wi-fi transmitter, that talks to the display module. The display does not show amperes however, but gives a reading in watts. . Many (uninformed) have been caught-out trying to read the current flow in a multiple conductor AC flex...lol
@tim62744
@tim62744 Жыл бұрын
Ya made that mistake John thought it would tell me what power in plug wire to tools
@robbieaussievic
@robbieaussievic 7 жыл бұрын
....... Ferranti stolen from Dr. Frankenstein's lab.
@seandempsey9396
@seandempsey9396 3 жыл бұрын
Save your money and buy one from uni-t they are the same and just as good as well as a dam lot cheaper I have used uni-t test instruments for seven years now with out any problems and I will not be going back to the big brands any time soon
@godgameplay2361
@godgameplay2361 3 жыл бұрын
Sir plz can you say how to check that the neutral coming from transformer is weak or strong?🙏🙏🙏
@georgedavall9449
@georgedavall9449 18 күн бұрын
J.W. !!!!!!!!!!!!!!!!! Crackin video mate, but slow down and enunciate a little clearer, Sir, Thank You 🙄
@joelund655
@joelund655 3 жыл бұрын
Just use common SENCE PEOPLE think about that a while
@aigleblanc3966
@aigleblanc3966 6 жыл бұрын
how much do you pay ????
@aigleblanc3966
@aigleblanc3966 6 жыл бұрын
Ah thast's not true you too ???
@Deebz270
@Deebz270 3 жыл бұрын
Who are you replying too?
@markdudley3831
@markdudley3831 Жыл бұрын
Analo Analogue = style .... digital maybe more accurate but = Zero ....
How to use a multimeter like a pro, the ultimate guide
12:55
James Gatlin
Рет қаралды 1,7 МЛН
Measuring VFD's with Clamp Meters
19:34
MultiMeter Channel
Рет қаралды 88 М.
OMG😳 #tiktok #shorts #potapova_blog
00:58
Potapova_blog
Рет қаралды 4,3 МЛН
He sees meat everywhere 😄🥩
00:11
AngLova
Рет қаралды 10 МЛН
когда повзрослела // EVA mash
00:40
EVA mash
Рет қаралды 3,8 МЛН
Osman Kalyoncu Sonu Üzücü Saddest Videos Dream Engine 170 #shorts
00:27
Fault Finding Electrical Circuits - Electrician Life
24:57
Artisan Electrics
Рет қаралды 376 М.
Types of Earthing System for Electricity Supplies (UK)
18:00
John Ward
Рет қаралды 464 М.
Cheapest Multi-meter comparison, Which is the Best Value?
12:28
How a AC/DC Clamp-Meter works
20:48
KainkaLabs
Рет қаралды 52 М.
Fluke 323 clamp meter, When only the best will do!
29:03
Dan’s Pro Shop
Рет қаралды 5 М.
Earth Fault Loop Impedance Test & Prospective Fault Current Test
16:50
City & Guilds Electrical
Рет қаралды 675 М.
Fluke 325 Electricians Meter Clamp Meter Review
10:30
Tools4Sparks
Рет қаралды 66 М.
GVDA GD166B clamp meter test and teardown
18:41
DiodeGoneWild
Рет қаралды 19 М.
Спутниковый телефон #обзор #товары
0:35
Product show
Рет қаралды 2 МЛН
Main filter..
0:15
CikoYt
Рет қаралды 14 МЛН
Choose a phone for your mom
0:20
ChooseGift
Рет қаралды 5 МЛН