Daikin inverter | air conditioner Thermistor Failure Symptom

  Рет қаралды 24,490

Bon Mj

Bon Mj

2 жыл бұрын

Brand : Daikin
model : MKS80QVM
ERROR : No error
Symptom: Running after 45minutes,Fcu auto off and auto on back,outdoor LED 1 & 2 light up.
Cause : Thermistor failure Symptom,thermistor short circuit.
#bonmj #daikin #inverter

Пікірлер: 108
@Techhvac
@Techhvac 2 ай бұрын
Sir .Bon Mj Your technical Video's very useful for technician. Great job Thank you so much 🙏🇶🇦
@BonMj
@BonMj 2 ай бұрын
It's my pleasure
@Achabab
@Achabab 2 жыл бұрын
I never find this problem before😂😂😂, first time some one share this information in KZfaq. You are the best⭐⭐⭐⭐⭐
@BonMj
@BonMj 2 жыл бұрын
Thanks
@vladimirmakhney5407
@vladimirmakhney5407 2 жыл бұрын
Hello. A very good tip, I'm sure many technicians didn't even know about it
@BonMj
@BonMj 2 жыл бұрын
Thanks
@robinsonguanzon8092
@robinsonguanzon8092 2 жыл бұрын
Thanks Sir Bon Mj ❤️ A big help to us technician, A far areas and urban areas..🙏🙏🙏
@BonMj
@BonMj 2 жыл бұрын
Welcome
@JDT738126
@JDT738126 2 жыл бұрын
Bon your videos are excellent! Thank you
@BonMj
@BonMj 2 жыл бұрын
Thanks
@birin.6884
@birin.6884 2 жыл бұрын
Hey, thanks for everything. explain his picture and I'm good.
@carlocurotto7555
@carlocurotto7555 2 жыл бұрын
That’s a great tip thank another fantastic video
@BonMj
@BonMj 2 жыл бұрын
Thanks bro🙏
@jagannath3839
@jagannath3839 2 жыл бұрын
This is very good helpful information thanx sir.
@BonMj
@BonMj 2 жыл бұрын
Thanks
@februaryoakkar938
@februaryoakkar938 2 жыл бұрын
Thank you sir
@linaung127
@linaung127 2 жыл бұрын
Hello sir, nice troubleshooting, thanks
@BonMj
@BonMj 2 жыл бұрын
Welcome
@narayanaya5519
@narayanaya5519 Жыл бұрын
Very useful information
@BonMj
@BonMj Жыл бұрын
Thanks
@estanislauboavidabelo4975
@estanislauboavidabelo4975 2 жыл бұрын
thank you, please continue to upload the video.
@BonMj
@BonMj 2 жыл бұрын
Thanks bro
@khaidang8614
@khaidang8614 Жыл бұрын
@arunramachandrana1025
@arunramachandrana1025 2 жыл бұрын
Very good information
@BonMj
@BonMj 2 жыл бұрын
Thanks
@shreekanay698
@shreekanay698 2 жыл бұрын
Thanks Boss.
@BonMj
@BonMj 2 жыл бұрын
Thanks
@Didik-cq8wy
@Didik-cq8wy Жыл бұрын
Trimakasih bos
@BonMj
@BonMj Жыл бұрын
You Dari mana? Terima kasih banyak nonton video saya
@Blueblurr112
@Blueblurr112 2 жыл бұрын
Great video thank you.
@BonMj
@BonMj 2 жыл бұрын
Thanks
@karimchiu7527
@karimchiu7527 Жыл бұрын
Thank Sir Bon
@BonMj
@BonMj Жыл бұрын
Welcome
@alanwong2761
@alanwong2761 2 жыл бұрын
👏 bravo bro 👍
@sarfarajshaikh4582
@sarfarajshaikh4582 2 жыл бұрын
Nice one bro
@BonMj
@BonMj 2 жыл бұрын
Thanks
@arafteknikac
@arafteknikac 2 жыл бұрын
Thank you so much
@BonMj
@BonMj 2 жыл бұрын
Thanks
@hafeezdaikin2517
@hafeezdaikin2517 2 жыл бұрын
Thank you boos 👍
@BonMj
@BonMj 2 жыл бұрын
Thanks
@user-vz6mu7iu7j
@user-vz6mu7iu7j Жыл бұрын
hi sir im p paul kolkata i lick you video
@aselajayasundara1669
@aselajayasundara1669 2 жыл бұрын
Thank you sir 🙏
@BonMj
@BonMj 2 жыл бұрын
Thanks🙏
@winmaung4558
@winmaung4558 Жыл бұрын
Thank sir
@BonMj
@BonMj Жыл бұрын
Welcome
@JDT738126
@JDT738126 2 жыл бұрын
Hi Bon, could you please provide a source for many of the common manufacturers thermistor resistance/temperature values? I cannot find any for the LG brand.
@karaors8970
@karaors8970 2 жыл бұрын
Thank you bro
@BonMj
@BonMj 2 жыл бұрын
Thanks bro
@peramaraj2763
@peramaraj2763 11 ай бұрын
Normally daikin compressor discharge thermistor range 13 to 15 kilohms right ?
@mdtuhintalukder5012
@mdtuhintalukder5012 2 жыл бұрын
Thank you....
@BonMj
@BonMj 2 жыл бұрын
Thanks
@tabresztabu562
@tabresztabu562 2 жыл бұрын
Tq Boss 🙏
@BonMj
@BonMj 2 жыл бұрын
Thanks🙏
@jamestan7901
@jamestan7901 2 жыл бұрын
👍 👍 👍
@azadabduellahal8116
@azadabduellahal8116 Жыл бұрын
Same can happen Mitsubishi system
@antoinetuyongo6527
@antoinetuyongo6527 2 жыл бұрын
Bonjour , comment je pourrais avoir la version française
@alembattlerealmsgamefowl6631
@alembattlerealmsgamefowl6631 4 ай бұрын
sir inverter daikin 1.5hp ,indoor fan motor stay in low speed what maybe the reason o the problem ? even we changes to high speed in the remote fan speed still low,thanks for the reply
@BonMj
@BonMj 4 ай бұрын
Any coil choke
@MrRandyj72
@MrRandyj72 2 жыл бұрын
That would be hard to find on the system unless its in cooling mode developing condensation at the time you are checking. Did the error code send you in the direction to check the thermistors? Last question did you full change the harness or just dry and seal the bad thermistor?
@BonMj
@BonMj 2 жыл бұрын
Just happen after running 45minutes. Only outdoor LED 1&2 on when stop running,indoor auto off and will auto on back after for awhile. We replace the new harness.
@Achabab
@Achabab 2 жыл бұрын
@@BonMj thank you share your knowledge 🙏🙏🙏god bless you
@BonMj
@BonMj 2 жыл бұрын
@@Achabab welcome
@ThesecretS_a_n_3_1
@ThesecretS_a_n_3_1 2 ай бұрын
Daikin Indoor fan motor no running a6 alarm coming I replace indoor motor and indoor PCB board also but still have a6 alarm ? What is problem
@BonMj
@BonMj 2 ай бұрын
Check thermistor
@errantpmd3765
@errantpmd3765 Жыл бұрын
Sir. My aircon.. cut in compressor n fan for 30min for 3 room. Is it thermistor of outdoor? I saw your ismike series, u change the indoor thermistor... May I know if is the same logic? Mine are toshiba
@BonMj
@BonMj Жыл бұрын
What is your setting temperature
@errantpmd3765
@errantpmd3765 Жыл бұрын
@@BonMj sir.. even in the lowest also the same.
@errantpmd3765
@errantpmd3765 Жыл бұрын
@@BonMj correction sir. Is 30sec..not min.
@BonMj
@BonMj Жыл бұрын
@@errantpmd3765 may be outdoor pcb problem
@errantpmd3765
@errantpmd3765 Жыл бұрын
@@BonMj sad.. :( Thought is some thermistor...
@narayanaya5519
@narayanaya5519 Жыл бұрын
If short thermistor what could happen PCB
@BonMj
@BonMj Жыл бұрын
For this case intermittent blinking, pcb ok.
@zse0118
@zse0118 2 жыл бұрын
Hi Sir! What's the reason you put the thermistor in the water and than you checked the countinity again?
@BonMj
@BonMj 2 жыл бұрын
Put in the water just show the thermistor is short circuit when water go in to the parts. When the thermistor locate at suction pipe,the water will go into the parts after gas pipe condensation.
@zse0118
@zse0118 2 жыл бұрын
@@BonMj Thank you so much for your answer.
@arasanairconsolution4u9
@arasanairconsolution4u9 2 жыл бұрын
Hai sir ,vrv 3 Daikin system one outdoor 3 indoor ,all running good but , standard compressor Haven't run even one FCU haven't achieve room required temperature.please advise
@BonMj
@BonMj 2 жыл бұрын
May be already by pass. Check mode2
@peramaraj2763
@peramaraj2763 11 ай бұрын
​@@BonMjalready bypass how to find ? Bro
@randypatcho6051
@randypatcho6051 Жыл бұрын
How to apply your company sir
@ManojKumar-zu2yz
@ManojKumar-zu2yz Жыл бұрын
Sir daikin vrv3 modal rxyq12pry6 error code p4 Cheng master PCB
@janshaw5472
@janshaw5472 2 жыл бұрын
这种情况好难被发现!感谢老师!contiuniry中文是什么?
@BonMj
@BonMj 2 жыл бұрын
谢谢你。去了两次才发现
@BonMj
@BonMj 2 жыл бұрын
Continuity 是联系的,比如wire用meter 量continuity 。
@gothandaraj860
@gothandaraj860 2 жыл бұрын
Hi sir vrv 3 Daikin AC e2 error and E3 error how to make rectify
@BonMj
@BonMj 2 жыл бұрын
E2 may earth leakage E3 high pressure sensor/high pressure switch
@abidshirhatti6815
@abidshirhatti6815 2 жыл бұрын
Hi sir my wathsup no not going for comment
@mycountrymyvlog1
@mycountrymyvlog1 2 жыл бұрын
i need job i am air conditioning and refrigeration mechanic
@govindarasugovindarasu7440
@govindarasugovindarasu7440 2 жыл бұрын
Hi sir I have problem is Diakin air conditioning vrv system celling saspanded units have the error UF this error what is the problem sir thanks
@BonMj
@BonMj 2 жыл бұрын
You change indoor pcb?
@govindarasugovindarasu7440
@govindarasugovindarasu7440 2 жыл бұрын
@@BonMj no sir
@BonMj
@BonMj 2 жыл бұрын
@@govindarasugovindarasu7440 check indoor all fcu voltage or pcb faulty
@nagarajvenkat8476
@nagarajvenkat8476 2 жыл бұрын
Hi sir I have problem daikin package unit error E 32 how to rectify this problem sir
@BonMj
@BonMj 2 жыл бұрын
Check Compressor 1
@nagarajvenkat8476
@nagarajvenkat8476 2 жыл бұрын
Thanks sir
@azizullahkhanpathan2693
@azizullahkhanpathan2693 2 жыл бұрын
Hello sir I am Aziz. I have a Daikin 1.5 ton inverter split AC. My AC is showing C3 error code. Can you please tell me what C3 error code is and how to solve it . Model no FTKZ50U
@BonMj
@BonMj Жыл бұрын
Try check i door thermistor. Actually this error is water level sensor problem
@azizullahkhanpathan2693
@azizullahkhanpathan2693 Жыл бұрын
Thank you for your reply sir 👍
@azizullahkhanpathan2693
@azizullahkhanpathan2693 Жыл бұрын
I will check
@azizullahkhanpathan2693
@azizullahkhanpathan2693 Жыл бұрын
@@BonMj Hello sir my AC is Daikin inverter split AC it is showing C3 error code will you please confirm what is the issue in it C3 means?????
@azizullahkhanpathan2693
@azizullahkhanpathan2693 Жыл бұрын
In the split AC water level sensor will be there ?????
Harley Quinn's revenge plan!!!#Harley Quinn #joker
00:59
Harley Quinn with the Joker
Рет қаралды 5 МЛН
ROLLING DOWN
00:20
Natan por Aí
Рет қаралды 9 МЛН
小蚂蚁被感动了!火影忍者 #佐助 #家庭
00:54
火影忍者一家
Рет қаралды 53 МЛН
路飞太过分了,自己游泳。#海贼王#路飞
00:28
路飞与唐舞桐
Рет қаралды 43 МЛН
Daikin | How to rectify (error code J5)
7:29
Bon Mj
Рет қаралды 29 М.
THERMISTOR Operation and Testing! Inverter and Mini Split Training!
5:41
AC Service Tech LLC
Рет қаралды 111 М.
Daikin VRV3 | error E4 | LPS switch
8:43
Bon Mj
Рет қаралды 19 М.
How Air Conditioner Works And What We Have Inside
14:42
Electronoobs
Рет қаралды 365 М.
Daikin L8,L9 and L5 Error codes
19:15
Arista Air Conditioning Training Videos
Рет қаралды 2 М.
DAIKIN Air Conditioner NOT HEATING 🥶
13:58
Mitch Attwood
Рет қаралды 12 М.
Daikin | How to rectify error code JA
9:12
Bon Mj
Рет қаралды 22 М.
Harley Quinn's revenge plan!!!#Harley Quinn #joker
00:59
Harley Quinn with the Joker
Рет қаралды 5 МЛН