Do not use this type of DC Isolator for your solar power system array! I explain why they catch fire

  Рет қаралды 57,370

Joondalup Electrical Services

Joondalup Electrical Services

Жыл бұрын

In this video I give a real life demo of a solar panel isolator catching fire and explain why it happens, why we have so many rules to adhere to and most importantly why you should engage a professional solar installer for your residential or Off Grid solar project. I made a few verbal slip ups in this video but you certainly get the point. Enjoy!

Пікірлер: 159
@SkypowerwithKarl
@SkypowerwithKarl Жыл бұрын
If you have 250 volts through a low voltage breaker, it doesn’t matter what the amp rating is. It can burn up AFTER you turn off the breaker. DC arcs are crazy powerful. I use 1000 volts breakers on a 250 volt array and pay attention to the polarity marked breaker.
@richardblais6282
@richardblais6282 Жыл бұрын
There is the rated operating voltage too that is very important. As an example, operating a 150v disconnect switch on a 350v array would give the same result.
@rm6857
@rm6857 10 ай бұрын
That breaker is rated for 220V DC
@michenji
@michenji Ай бұрын
@@rm6857 i was about to abandon my project just because i watched this video... but then i wonder if the same would have occured if he used a 1000v 16a double dc bracker on a string that produces 14 amp in short circuit mode like i'm going to do... any opinion about it is very welcome
@rm6857
@rm6857 Ай бұрын
@@michenji It burnt because he used 220V breaker for 350V system. If you use 1000V for 350V, you are fine.
@schrodingerscat7218
@schrodingerscat7218 Жыл бұрын
EE here. I laughed and laughed at the video and the title. Watch me light this pile of hay on fire to prove that hay is a bad idea. So much wrong here, I wouldn't even care to start.
@dianeattaway8733
@dianeattaway8733 Жыл бұрын
For any DC interrupter device, voltage rating is absolutely critical. Larger voltages require an exponentially more robust arc chute control. A 100V disconnect on a 500V circuit at any current is going to be a blast, even at 1A. DC is a completely different animal than AC.
@glenmartin2437
@glenmartin2437 Жыл бұрын
Thank you. I worked on a lot of laboratory equipment. I learned to read and reread the manuals, then ask the company engineers and technicians questions. It eliminated problems and downtime. And I am still alive and have all my fingers, etc.
@isettech
@isettech Жыл бұрын
For those not in Australia, or even those in Australia, there are manufactures of breakers with magnets and arc chutes to quench an arc for high DC interruption. They are designed to open under load and quench the arc. Please note they are polarity sensitive as the polarity determines the direction of the arc blow in the magnetic field. Polarity must be observed to blow the arc into the arc chute instead of away from it. Many breakers for DC have low voltage ratings due to the difficulty in quenching an arc. For panel arrays, ensure the breaker is able to quench the open circuit voltage under load. Other DC disconnect devices have multiple series contacts to break the arc. Large gap knife switches work well as the gap when open is more distance than the current can mantain an arc. Use the type often used for inductive loads such as for a heat pump disconnect switch. Double break and an open distance greater than 1 inch is good to stop the arc. The distance is important the same way cutting the cable broke the arc. You need a large device with the ability to make a large gap when open. For over current protection, use the sand filled multi-element fuse for at least the rated voltage. The sand falls into the arc to quench it.
@electrocomm
@electrocomm Жыл бұрын
it's good to be aware of the risks but this video is incomplete and misleading. no info about the breaker ratings, solar open circuit voltage, if the breaker is wired correct polarity, etc. moreover, those extension solar conductors increase the total inductance and therefore the arc energy which may be beyond the breaker can handle.
@davef.2329
@davef.2329 Жыл бұрын
Just curious, what was the line voltage for this demo?
@NSaw1
@NSaw1 Жыл бұрын
I've tested quite a few breakers here in the US under a DC load. 92 volts DC. Its interesting, because our standard AC breakers like Square D homeline breakers stood up better than the actual DC rated breakers I had. None pf them failed to extinguish the arc. Although the breakers I was using where rated for 5ka but the homelines where rated for 10ka which probably had a loot to do with it. Would be very interesting to see more breakers tested under DC load, even ones that aren't DC rated since that seems to be a thing that is done a lot too.
@carlubambi5541
@carlubambi5541 Жыл бұрын
Remember the types of breakers out there .The best breakers are thermal sensing ,current sensing and magnetic tripping .Also operating voltage gives it the ability to extinguish and ARC ,Always she's the load in the panel before you open the main breaker .Same thing with fused disconnects protecting panels .Also there are HP ratings to contend with ,not just current and voltage and ratings AIR and most important .NEMA vs IEC .I'll take NEMA every day over any IEC .Just remember if your short circuit current is 10 amps don't put in a 15 amp breaker or fuse for that matter even if the wire is rated for 30 amps ...As the voltage goes up you will need devices with arc chutes for quenching the arc .Some uses several contacts in series for arc quenching
@budmartin3344
@budmartin3344 Жыл бұрын
Can you provide the full spec of that burnt circuit breaker? What is the Voltage feeding that circuit breaker?
@mythuan2000
@mythuan2000 Ай бұрын
I think its the chinese one cuz there diagram on the right and blank on the left. Probably 240VAc/125Vdc or something. That was why he hid the right side of the the breaker.
@jeroenlodder5838
@jeroenlodder5838 Ай бұрын
@@mythuan2000 even if not Chinese, rating is only 220vdc and it’s not an isolator. It’s a breaker.
@keithshumaker6402
@keithshumaker6402 Жыл бұрын
The whole thing is if you don’t know what you’re doing don’t do it
@chrisparker9886
@chrisparker9886 Жыл бұрын
Yeah, it's pretty much common sense. If you can read and understand what you're reading, you can do it the right way. 😏
@3th1xs
@3th1xs Жыл бұрын
Or do it anyway and learn the hard lesson. Then next time, you might stop to research what you're doing. Eventually you'll learn or run out of money.
@msamour
@msamour Жыл бұрын
This video assumes people can't learn. I understand the concern, but that is a ver elitist view of the world. I built my first system last year after I did about 100 hours of research. I already replaced components that had been recommended, but turned out to be faulty.
@BOGGarage
@BOGGarage Жыл бұрын
Can we please get more details about that breaker?
@dc1544
@dc1544 Жыл бұрын
That is why DC disconnects have large gaps. If you have to turnoff under load no fire will happen. Also not having a large enough disconnect (using a 12 volt disconnect on 310V. All solar disconnects should be rated to 600V minimum. Mine are 1000V 64 amp. Mine shutoff 330V 15 amps . This was a great video thank you. Also I would not use the inverter disconnect first. I would use a wall mounted with fireboard disconnect like you have then turn of disconnect on inverter 2nd. then reverse for on.
@davedave6404
@davedave6404 Жыл бұрын
Wow ! Excellent demonstration. Use of a much higher DC rated breaker, voltage and current, is clearly needed than the installation normally provides. Trouble is in an emergency the isolation switches would always be used so they must be rated for Live switching as well as Isolation. Adds to costs but so would a fire.
@andrewhofmann5453
@andrewhofmann5453 Жыл бұрын
Wow, read the title, came into this video expecting you to be critical, but wow.... Great demonstration. Really making me take a second look at my disconnects.
@joondalupelectricalservice3201
@joondalupelectricalservice3201 Жыл бұрын
Thank you
@rad1876
@rad1876 Жыл бұрын
Excellent demonstration reinforcing the need to implement the correct type of switching device. Until you see how it instantly ignites it’s hard to have an appreciation for the risk.
@whoguy4231
@whoguy4231 Жыл бұрын
Awesome breaker fire. Just love how quickly it lights up and burns. Some breakers due to age will prematurely trip causing the same break under load condition. Was a stupid idea to have them in the first place, hence why it's now obsolete.
@joondalupelectricalservice3201
@joondalupelectricalservice3201 Жыл бұрын
Thanks Brian, yes it surprised me just how quick it went up. And yes your spot on about the breakers simply tripping through age, fatigue, external thermal influences etc. This one was in spec for the application also.
@electromechanicalstuff2602
@electromechanicalstuff2602 Жыл бұрын
My 150vdc midnite solar breakers have worked flawlessly on my 80vdc system. Put too much charge controller on an array and it popped 80 amps repeatedly
@hasger1941
@hasger1941 Жыл бұрын
So what happens when the customer forgets to turn off the AC load before the DC ? Would have thought this would need to be fool proof..
@hardcoreclassicenjoyer
@hardcoreclassicenjoyer 6 ай бұрын
as an apprentice with 2 years of solar installing experience, ive seen the crusty smelly shells of the Zbenny isolators. But to see how quick the switch goes on fire was eye opening ty
@Bushcraft-xz6xd
@Bushcraft-xz6xd Жыл бұрын
I’m sure you meant well with this video but you need to either redo it with the needed information or add the info to this vid. What you are saying is the correctly rated breakers they used to use in PV systems will catch fire if you turn them off under load? Because that is what I got from the video. So the DIY 200 watt 12 volt panel and inverter I have on my shed that uses a similar breaker will burst into flames the moment I switch it off?
@Gallardo6669
@Gallardo6669 Жыл бұрын
Very good comment/ question!!!
@Kirkbdavis
@Kirkbdavis Жыл бұрын
Great content. Thanks for putting this up.
@keything8487
@keything8487 Жыл бұрын
"dont fuck with these" !!!......as a sparky in the states, i can attest, to the lack of knowledge most of them have. especially with DC voltage/currents. thank you for the show !!
@todamnbad
@todamnbad Жыл бұрын
Not enough information provided to explain your situation
@BobCollins42
@BobCollins42 Жыл бұрын
From the title, the poster doesn't care to inform, just scare you to hire him. Not impressed.
@mikesgarage394
@mikesgarage394 10 ай бұрын
Incorrectly wired DC breaker is a fire hazard. Wire it correctly and try again.
@skywave12
@skywave12 Жыл бұрын
Go with 1000 Volt inline fuses. When they open a temporary inert gas is given off inside to assure a voltage breakdown will not occur. Way safer than air breakers. DC has no zero crossing so it is harder to remove a breakdown ark.
@FarmsVilla
@FarmsVilla Жыл бұрын
Year 4 of running my DIY 10kw solar system. No issues at all so far. 🤷🏻‍♂️🙄
@cowboyrides3585
@cowboyrides3585 Жыл бұрын
Really I've been hot 🔥 rodin my shit for years, lol , they don't just catch on fire lol , good luck 🤞
@electromechanicalstuff2602
@electromechanicalstuff2602 Жыл бұрын
What voltage is that breaker rated at? What voltage are you using for the test? How many ka is the breaker rated for?
@rm6857
@rm6857 10 ай бұрын
its rated 220V, and he uses 350V
@electromechanicalstuff2602
@electromechanicalstuff2602 10 ай бұрын
@@rm6857 obviously he's using more than it's rated.
@rm6857
@rm6857 10 ай бұрын
@@electromechanicalstuff2602 Yes, that breaker is good brand with CE rating.
@al2207
@al2207 Жыл бұрын
to protect dc load you must use breaker with proper interrupting capacity at that dc voltage and having number required of poles in series as a representative for the correct number
@_wookie
@_wookie Жыл бұрын
Hello! Really good and informative video but one question: what was the voltage in the system? I am looking the datasheet of Eaton/Moeller PLS6-C16/2DC breaker and there it says it's a proper DC breaker rated to 220V DC. It doesn't say anything about the arc extinction/reduction in the datasheet but I would assume that when used in accordance to the spec it shouldn't just ignite like it was seen in the video. So I am wondering what actually caused it to fail... Was it already broken? Was it some cheap fake? Was it used in the system with much higher voltage than rated for? Something else?
@rm6857
@rm6857 10 ай бұрын
No, he used 350V solar array. That DC breaker is good brand with CE
@SrDelbioLima
@SrDelbioLima 4 ай бұрын
it seems that the dc breaker wasn't good enough or the voltage used was higher than its specs. @@rm6857
@gssrustenburg
@gssrustenburg Жыл бұрын
In my inverter manual it states, never disconnect under load. I guess the same applies to battery disconnect. Would a disconnect fuse be safer as it is manually disconnected ?
@drunk_astronomy
@drunk_astronomy Жыл бұрын
I only use midnight breakers. MNDC breakers marked with polarity in mind because you want the arc to extinguish in the same direction of the yolk. If you wire DC breakers backwards it will actually hold the yolk in the closed condition in some scenarios. That would be bad. The 600 V breaker that midnight solar makes actually has four yolks. thanks for making the video. It’s very important to understand how DC arcs pertaining to these breakers work.
@solargoat
@solargoat Жыл бұрын
Great demonstration!!
@jcschwarb
@jcschwarb Жыл бұрын
Is a fuse better, more sensitive in this use case, acting as sacraficial?
@larrybell4599
@larrybell4599 Жыл бұрын
Wow, that’s an eye opener!!!
@JamesMorris-os7kb
@JamesMorris-os7kb Жыл бұрын
Great demo mate
@Swenser
@Swenser 8 ай бұрын
I have used a DC breaker in that style. 1000v 16amps. No issues switching. Obviously that brand you used has simply not be designed to operate at the voltage and current used or it's a faulty design. A DC breaker of that style should follow it's ratings. What brand breaker was that? was it an AC breaker?
@Mechanical803
@Mechanical803 6 ай бұрын
Is using a higher voltage DC fuse for the holder better in this case than using breakers?
@cjmcay
@cjmcay 6 ай бұрын
Would this huge draw trip the 30 amp inline solar fuse I have on each home run connected to each array?
@iqtadarali884
@iqtadarali884 3 ай бұрын
Perfect explanation.... Thanks.
@rentabomb
@rentabomb 8 ай бұрын
Did you try putting a strong magnet near it when you threw the switch ? This may pull the arc away and cause it to extinguish.
@odoohub5010
@odoohub5010 6 ай бұрын
What is the difference between the dead short you created and the internal short inside the breaker as a result of turning off the load?
@user-tj5nk7lb8l
@user-tj5nk7lb8l 4 ай бұрын
Very good demo Joon Ive been banging on about how DIY (amateurs) are so casual about dc distribution - but I just a a big yawn from forum members (like Im a party pooper). One thing to note is that an arc can be killed by distance (for a given voltage). Its not possible to sustain an arc at 12vdc from a car battery. Use a 24 v pair and you can do dc welding. But pull the rod away from the work by more than ca 1/2" and the arc goes out. My take is to stay at 24v its much safer. 48v might need a 2" separation (tbc). I believe the very common domestic 63A knife switch (ca $10 us) would do the breaker job very neatly at 24v (48v tbc?). These are all over the far east and solid reliable, as are the Siemens NH style knife fuses ($5us). IMHO there's a massive cartel trying to monopolise the Solar DIY market and its rife with fraudulent parts - fake cable (4mm2 labelled as 6mm2 etc)
@Ranch321
@Ranch321 Жыл бұрын
Can you combine a dissconnect switch and a smoke detector? So if there's smoke in your eletric room it will automatically kill the power?
@kimmogensen5390
@kimmogensen5390 5 ай бұрын
so i have a DC isolater rated for 1000v 63A but i am only running 250v 20A ,,would that one also go to smoke , if i break the circut in high sunlight? i have only turned it off early morning or late night...
@excillisbank2611
@excillisbank2611 4 ай бұрын
superbe test en direct !👌
@stevemiller6237
@stevemiller6237 Жыл бұрын
That went fast, what are the ratings of the breaker?
@ibot_
@ibot_ 11 ай бұрын
Do you check the current direction? Moeller change to Eaton 264902 PL7-C16/2-DC and on it you can see a plus and a minus for the direction of the current. That will be interest for me.
@odoohub5010
@odoohub5010 6 ай бұрын
What if there is no load, but only batteries that are being charged. Can you still turn off the isolator while the batteries are being charged? Since the battery is like a load. Or do we need to turn off the breaker for the battery before turning off the isolator for the pv array.
@clarke6436
@clarke6436 Жыл бұрын
Great video, please make other videos with safety tips as there are a lot of diy solar people out there.
@PhilippeCJR
@PhilippeCJR Жыл бұрын
What is de voltage and amp spec of that breaker?
@CadeBrazil
@CadeBrazil Жыл бұрын
Just use fusels instead breakers for DC and that's it. Of course, you have to be using the correct Amperage and solved. No fires, no problems.
@johannholtzhausen895
@johannholtzhausen895 Жыл бұрын
Actually these so-called dc circuit breakers are not designed for dc at all. A proper dc switch or breaker will be physically a lot larger, have proper arc shields and arcing horns all built in. What is currently used is a re-branded ac breaker. It can still be used with dc, provided you wire up a "snubber" circuit in parallel with the circuit breaker. This should consist of a resistance in series with a decent size capacitor and the arcing problem is solved.
@stem_saving1644
@stem_saving1644 Жыл бұрын
Your breaker needs to meet not only current loads as well as break voltages. If your sized correctly, then your over current protection device isn't an over current protection device.
@coolmalli8293
@coolmalli8293 3 ай бұрын
Hi there does Growatt inverter has in built isolator
@_Miner
@_Miner 4 ай бұрын
I hope by now you remembered to speak with Todd
@BlueSky-cy5nw
@BlueSky-cy5nw 7 ай бұрын
Moral of the story: Do not disconnect solar when it is under load, whether it is breakers or MC4 connectors.
@teddycunningham7568
@teddycunningham7568 9 ай бұрын
New subscriber. I now no why my breaker failed luckily without fire . May go to a giant Frankenstein knife switch instead. LOL
@mark7362
@mark7362 7 күн бұрын
Thank you for making this video, this is very very helpful, might even save some lives! Just curious, do you think it's safe to say that all Cbreakers with that similar design (possibly rebranded) are equally as bad as this one in the video?
@joondalupelectricalservice3201
@joondalupelectricalservice3201 19 сағат бұрын
Depends on the application but I wouldn’t trust them beyond say 12volts
@markpate4295
@markpate4295 9 ай бұрын
That jumper doesn't seem right? All the schematics I have looked at show 2 methods on battery side going in. 1324 and or 1234? I am glad I haven't screwed anything up yet. I am waiting on some 4/0 cable and some DC cutoffs. Resetable 300 amp breaker. Lug crimp. Stuff. Everything is so expensive.
@UK100Adam
@UK100Adam Ай бұрын
I take it that the polarity was the wrong way round? Please confirm.
@captain1butterworth712
@captain1butterworth712 Жыл бұрын
Well done, is that from solar for wombats.
@Mike-01234
@Mike-01234 4 ай бұрын
This is why roof top solar requires rapid shutdown devices that will reduce the voltage.
@bialy100k
@bialy100k 4 ай бұрын
Sad we are not sure about polarity of the test connection. Usually power source is connected from the top, and load is down.
@quitequiet5281
@quitequiet5281 5 ай бұрын
Excellent scary example.
@batterynerd8779
@batterynerd8779 Жыл бұрын
That‘s why i dont use breakers at all. Although i only have 200 watts of solar. I dont know why i would want to disconnect my solar panels? I just remove the cable from the charge controller. Also the voltage isn‘t dangerous in my case
@pepermintpilot1694
@pepermintpilot1694 Жыл бұрын
I'm not a PV installer or even a "spark" but my understanding was that in PV panels the Voltage remains constant and the Current changes due to light conditions. Please be mindful if you reply, I'm a mechanical engineer not electrical!
@flatfoot
@flatfoot Жыл бұрын
Except at dwan & dusk, that's broadly correct
@vylbird8014
@vylbird8014 Жыл бұрын
Mostly. Only complication is that the open-circuit voltage is a fair bit higher than the optimal operating voltage, so you need to rate your components accordingly. A panel sold as '12V' will usually be able to output 20V under no-load conditions.
@CollinBaillie
@CollinBaillie Жыл бұрын
@@vylbird8014 22 or more.. 18v at maximum power point. They sold as "12v" panels, because that's the target nominal battery voltage. You need somewhat higher voltage than the battery charge voltage (~14.4v on a nominal 12v battery). Just adding info to your already informative comment, for others.
@electrocomm
@electrocomm Жыл бұрын
the dry air has a breakdown voltage of 3kV/milimeter, if the air is wet, this value is lower. if the distance between the contacts is 1 milimeter and there is an arc between them, it means the voltage is already kV. due to the parasitic inductance of all the wires where the current flows in a closed loop system, if you open the loop, the parasitic inductor tries to resist current change and it will increase the voltage creating an arc until all energy of the inductor is dissipated and the voltage returns to that of the PV panel/string. if you want to minimise the arc, keep the wires as short and thicker as possible.
@Gallardo6669
@Gallardo6669 Жыл бұрын
No sh*t ! Wow. Thanks for the video!!!
@rm6857
@rm6857 10 ай бұрын
What was voltage of this solar system?
@joondalupelectricalservice3201
@joondalupelectricalservice3201 10 ай бұрын
Hi Around 350v from memory. I will be doing the experiment again soon with more detail.
@rm6857
@rm6857 10 ай бұрын
@@joondalupelectricalservice3201 Why experiment, this is trustable brand dc breaker, its rated for 220V DC so you are more than 150% of its rated voltage. Do you have any education in electrics? or you just try experiments if breakers burn or not?
@joselito7776
@joselito7776 6 ай бұрын
Is that not circuit breaker?
@koborkutya7338
@koborkutya7338 Жыл бұрын
it is a great heads up but the title is a totally stupid approach. You could help a lot of people to address the critical points and demonstrate how to avoid the pitfalls. If you make a series doing just that I would even subscribe. Saying "DYI and Off-grid is a bad idea" will just alienate viewers and for sure nobody who would otherwise be willing to build a solar system by themselves will say "oh this video said it was a bad idea so I will call an installer to charge me an arm and a leg for pointing at a decent isolator". Whoever is up to the challenge (like myself) is totally interested in the possible issues and the right approaches to avoid them but will definitely not be scared by the fact that wrong connections can cause fire - no sane person in the world will assume it is safe to connect electricity the wrong way. You could and should say everyone should do their homework, research the subject and may guide them to some reliable sources of knowledge. You can absolutely warn viewers that if they screw it up it will burn like this and even worse (you did not even talk about lithium battery fires). "why DIY solar and Off Grid is a bad idea" - it just looks like a contractor trying to secure more job. Which btw I don't really think you want but it looks very close.
@seafire157
@seafire157 5 ай бұрын
oh my...i plan to install 100w panel so i need highier amphere swiich braker for 100watts d.c output
@carnaud
@carnaud Жыл бұрын
16 amps DC is kinda small… 🤷‍♂️. Seems to me they should have never been used for the application.
@richardsandwell2285
@richardsandwell2285 Жыл бұрын
I have done my own offgrid, I used DC rated isolation switches and everything is in a durable metal enclosure, to be fair I have heard of plenty of professionally installed installations catching fire, and the classic stupid mistake is installing inverters in lofts. This stresses the electronics in hot weather, also people have been known to pile old bed linen and Christmas decorations around these inverters, leading to even greater thermal stress and fires.
@carlubambi5541
@carlubambi5541 Жыл бұрын
Rule of thumb 10kw inverter for every 7kw of demand ..Leaving 3 meters of space around your inverter is essential .Also the same rules apply for the derating of conductors based On ambient temperatures .You drop your ratings if your inverters ambient temperature is at 50°C like in attics and lofts in summer .Derate again for that and you may be only able to run 5 kw on a 10 kw inverter .Adding fans for cooling is essential and fresh air. in many cases the attic temps are much higher than outside .More fans !Or water cooled heat exchangers
@scottwilliams5196
@scottwilliams5196 Жыл бұрын
Same here, I did my own and it's been working great. Why scare people away from solar? Isn't an unreliable power grid more alarming?
@carlubambi5541
@carlubambi5541 Жыл бұрын
@@scottwilliams5196 there is no such thing as free energy or green energy .This is the problem going from a reliable power source to one that is not .Solar has its uses so long as you have the ability and space to provide more power than what you need and the ability to store enough surplus to operate for 1 to 2 weeks .Let's face it we have many cloudy and overcast days and at times for weeks in a row .It's not a reliable power source but a means of augmenting a power system .All you are doing is off setting the carbon foot print to a later date .They are highly toxic ,have a relatively short life span in some locations and have issues with maintenance and need to be cleaned to keep efficiency up .I like solar,don't get me wrong but it has its issues and has limitations and they do harm the environment from manufacturing ,disposal and the change in temperature in the area they operate .So do wind mills ,they kill wild life and redirect air flow and introduce noise that can be harmful to animals and humans .Basic laws of physics .(Energy Can't be Created, Only Transformed From One Form To Another )And that's that !You can't get something for nothing .Everything has a cost
@scottwilliams5196
@scottwilliams5196 Жыл бұрын
@@carlubambi5541 my tool box has many tools. I don't reject a tool because it can't do everything. Solar has been a great tool for me. Wind would be a good tool as well. Grid is a good tool. My panels will long outlast me and probably the next person that comes along. I replace batteries in my solar like I do in my cars, truck, mower, generator and power tools. We all do that. Not complicated. If you don't want alternative power, cool for you. Enjoy that choice, but don't dump on others who try to think outside the box.
@carlubambi5541
@carlubambi5541 Жыл бұрын
@@scottwilliams5196 yes I agree it has many uses ,it's a tool like anything else .It's has its uses and limitations,and should not be promoted as a be all and end all and cure for an imaginary enemy nor as a cure to solve an energy problem that does not exists .You see the more energy is produced the cheaper the price ,the problem becomes at what point will it be profitable for the produces .Eh Pickering nuclear plant produced electricity at a cost of 4 cents per Kwhr over its life span .This cost includes the building and maintenance .Distribution is another head ache and cost .The end user was paying about 6 to 8 cents per kWhr .they now privatized electricity and now we are paying as much as 10 times .for the same electricity .We are paying between 50 to 80 cents per KWHr for solar and Wind .!Something is seriously wrong . If I had the space I could put in about 4 kw of solar .The cost would be too high and the recovery too long 20 to 30 years before you break even .I have 400 watts on my shed to charge my tools and lawn mower and supply security lighting .It would cost me $3k + to run a wire from my house to the shed .So I spent$1500 for a stand alone solar system .The batteries are the biggest cost at almost $400 each .I use 2 RV marine lead acid batteries and a 1500w inverter .That's more than enough for a stand alone power system .When the power does go out I use a back up generator .
@solartime8983
@solartime8983 Жыл бұрын
Yes🌻If you're not 99% confident in your ability to safety build, do Not do DIY!! BEST to Hire a PRO...🗽🌅
@lotechgreg
@lotechgreg Жыл бұрын
Isn't this why "No arc"DC breakers are used? .. It's why I used them....
@clomads
@clomads 4 ай бұрын
Bro you just got duped into buying an AC breaker that’s labeled as a DC breaker and compared it to a clearly more expensive variant. There are literally arc suppressors in proper DC breakers.
@paulf1157
@paulf1157 Жыл бұрын
Nice to have money to pay for contractors' big pickups
@richardt4824
@richardt4824 Жыл бұрын
So the home owner can inadvertently mess up the shut down procedure and burn the house down ,Great !
@carlbrown5150
@carlbrown5150 7 ай бұрын
There are different Breakers for ac and dc. Dc has a longer ark arrestor ac does not. Don't confuse them things can go south Quickley.!!🤨
@asiasmells71
@asiasmells71 Жыл бұрын
So what's the solution?
@sang3Eta
@sang3Eta Жыл бұрын
The latest inverters have arc detection and PV disconnect switch.
@Bushcraft-xz6xd
@Bushcraft-xz6xd Жыл бұрын
@@sang3Eta Oh I see, so get rid of all our older inverters and spend thousands on new ones?
@sang3Eta
@sang3Eta Жыл бұрын
@Bushcraft1974 You can fit an external DC switch to your DC in cable. You can also put an arc fault detector in your fuse box. In the UK we also only use serial string inverters with lower Amps higher Volts which also helps eliminate arcing.
@xsauce3858
@xsauce3858 Жыл бұрын
It's not a bad idea if you know what you are doing.
@unSTEVOED
@unSTEVOED 3 ай бұрын
Shit that was fast
@666dualsport
@666dualsport Жыл бұрын
its a dead short circuit??
@joondalupelectricalservice3201
@joondalupelectricalservice3201 Жыл бұрын
Yes and no, thats how solar panels function.
@Mike80528
@Mike80528 Жыл бұрын
People need to cautious about buying cheap crap on Amazon or eBAY. Too many people try to go cheap in the worst places. If the electrical device doesn't provide *complete* specs, you are taking a risk. Also, people need to understand the difference between a breaker and disconnect. They server VERY different purposes. A breaker needs to be rated for the minimum capacity of the line (it give out first for safety), but a disconnect needs to be OVER RATED. If you want current *protection* you need a BREAKER (or fuse) and not simply a disconnect. I put disconnects at the panels and *breakers* inside closer to the system. You cannot use AC rated devices on DC at the same load (get DC rated). Also, you point about load is important. Shed your load before disconnecting loads at the power source.
@Gallardo6669
@Gallardo6669 Жыл бұрын
What you mean by saying shed the load?
@Mike80528
@Mike80528 Жыл бұрын
@@Gallardo6669 You don't want to just trip a main breaker with multiple appliances/loads operating. It puts way too much stress on the breaker and risks a failure. You trip your individual lines one at a time to disconnect smaller loads sequentially and then trip the main when there little or no load on it.
@Gallardo6669
@Gallardo6669 Жыл бұрын
@@Mike80528 i thought so, but thx for clarifying.
@nemethakos75
@nemethakos75 9 ай бұрын
Nem tudom, úgy gondolom ez nem terheléskapcsoló vagy szakaszoló
@rv10flyer84
@rv10flyer84 10 ай бұрын
Diagonal cutters will break the circuit.
@cotandiet6096
@cotandiet6096 10 ай бұрын
Just to mention this to everyone. By the code here in USA, DC wires must be inside a metal raceway and connected to a metal enclosure. PVC conduits and plastic boxes are not allowed.
@dennisgoldman7160
@dennisgoldman7160 2 ай бұрын
this is misleading due to the fact that the voltage source needs to be connected to the top of the breaker ....yes this is a perfect example of what can happen if your installer does not know what he is doing and hooks it up incorrectly
@SalvationStudioZA
@SalvationStudioZA Жыл бұрын
Non Polirised MCB? ASs this is an Polirised MCB
@panospapadimitriou3498
@panospapadimitriou3498 7 ай бұрын
if breaker is the turning one with chamber for poles inside isnt it harder to maintain any ark ? ? ? this was soooooooo entertaining but no motivating !!!!! even 70v array can do such firecracking things!!!!!!!
@agusm20856
@agusm20856 Жыл бұрын
Learning by doing, made mistake good improvement.. don’t do anything we are not learning anything
@HotRockCentral
@HotRockCentral 9 ай бұрын
It must be the brand you have is junk. I have all my panels on similar chinese dc breakers & often shut them down under load & never had an issue like you showed.
@texasoffgridguy8749
@texasoffgridguy8749 Жыл бұрын
Don’t let this video scare you from going off grid of course a fire will happen if you jump the negative to positive like you did in this video
@unionse7en
@unionse7en 9 ай бұрын
You missed the point (it happens ;-) ), no fire happened during the short circuit. The fire happened when the short was *disconnected*/opened and the resultant arc was not interrupted . Solar panels can be shorted indefinitely as the cabling is rated for that , and panels can't supply more than that (unlike most batteries). Solar panels can't only supply a limited current to their loads , a short is no different than a heavy load, they will just max out to their Isc amp rating and that's it (voltage will drop). However when you interrupt it under max load.....that what we see in this video.
@WiSeNhEiMeR-1369
@WiSeNhEiMeR-1369 Жыл бұрын
HOWdy J-E-S, ... Thanks my ECO-WORTHY Combiner-Box has a 63 Amp "DC" rated circuit-breaker ... COOP the WiSeNhEiMeR from Richmond, INDIANA ...
@carlubambi5541
@carlubambi5541 Жыл бұрын
Those breakers are not approved for disconnecting DC power .They are so bad.Use inline fuse holders to protect the breakers.Shedding the load is standard practice on ACor DC equipment
@flatfoot
@flatfoot Жыл бұрын
and what do you think the fuses will do?
@electro2606
@electro2606 Жыл бұрын
@@flatfoot disconect
@carlubambi5541
@carlubambi5541 Жыл бұрын
@@flatfoot open the circuit .In large DC drives we use fuses in series with breakers to protect the breakers .Common practice for us in plastic extrusion in machines using DC motors driving screws .Eventually we replace the DC motors with AC motors with VFD
@flatfoot
@flatfoot Жыл бұрын
@@carlubambi5541 fuses on a DC single PV string will never do anything. The fault current is no larger than the operating current. How does the fuse know when there's a fault condition?
@carlubambi5541
@carlubambi5541 Жыл бұрын
@@flatfoot .There are time delay thermal sensing fuses .they sense temperature and open up .They have a fuse link that has a spring on one side and a little pot of low temp solder that pulls open when it starts to melt because of the spring tension ..Now if the fault Current is only 15 amps then put in a 10 amp d type fuse .Also use UCC fuse holders and a disconnect so you have an extra method of disconnecting means ...These problems can be reduced .We get so much equipment from Europe with those breakers .We remove them and put in Mersen UCC Ultra safe fuse holders .Read the use specifications on the breakers .Most are only good for communications equipment.tehre is an AIR rating on fuses and breakers to consider as well as their voltage and their ability to quench an Arc.Some motor starters/manual motor starters have the ability to add quenching Chutes when used at higher voltages to extinguish the Arc .Or the use of multiple contacts in series to quench an arc .As this current does not exceed the breakers trip current temperature sensitive breakers are available (Magnetic ,thermal and overload sensing in one package .Fuses come with short circuit or thermal overload sensing
@ForwardEngineering
@ForwardEngineering Жыл бұрын
This title is wrong and has a off logic mentality. It should be said "Another example of why you over build instead of under build" DIY solar is the best option for the majority of people. If your not capable then yes pay to have the system installed.
@joondalupelectricalservice3201
@joondalupelectricalservice3201 Жыл бұрын
Agree, the title could be better. My motive however is to make people aware of the dangers of diy and solar.
@cowboyrides3585
@cowboyrides3585 Жыл бұрын
Lmfao
@mosesarzu7670
@mosesarzu7670 Жыл бұрын
You probably hookup something wrong or you got cheap components
This Cost Us THOUSANDS - Lightning Destroys DIY Off-Grid Solar System
17:46
О, сосисочки! (Или корейская уличная еда?)
00:32
Кушать Хочу
Рет қаралды 7 МЛН
Dynamic #gadgets for math genius! #maths
00:29
FLIP FLOP Hacks
Рет қаралды 18 МЛН
格斗裁判暴力执法!#fighting #shorts
00:15
武林之巅
Рет қаралды 81 МЛН
SOLAR ISOLATOR WIRING (for a DIY camper van)
6:35
EXPLORIST life Mobile Marine & Off-Grid Electrical
Рет қаралды 55 М.
I-Team: Hidden cameras reveal dark side of solar power
6:21
FOX 5 Atlanta
Рет қаралды 4,4 МЛН
Fuses, Breakers, and Basic Safety in your Solar System
12:33
Lupo DIY
Рет қаралды 75 М.
How to ensure safe and effective solar grounding
15:56
EnergyUME
Рет қаралды 16 М.
Solar Panel isolator catches fire. Why DIY solar power on your home is not a good idea!
5:39
Earth Grounding Solar Panels
6:19
Land to House
Рет қаралды 21 М.
Solar Training - Dangers of Series & Parallel Arcs
7:17
SolarPVOutlaws
Рет қаралды 19 М.
Do you REALLY get enough out of your solar panel?
21:01
Tech Ingredients
Рет қаралды 431 М.
Does my 13kW Offgrid Solar System require Grounding? Is it Grounded?
5:46
DIY Solar Power with Will Prowse
Рет қаралды 151 М.