Fire alarm design - smoke detectors at ceiling with beam construction

  Рет қаралды 6,952

All about Fire Protection

All about Fire Protection

Күн бұрын

This explains the installation of smoke detectors at ceiling with beams. For basics, fundamentals and design guidelines for fire alarm design please follow below links:
Part 1 - • Fire Alarm Installatio...
Part 2 - • Fire Alarm Installatio...
Part 3 - • Fire Alarm Installatio...
Disclaimer: This video is made for educational purposes only. No copyright infringement intended for the information used from NFPA standards. It was only used as a reference/guideline for designing.
#firealarm
#firedetection
#smokedetector
#Design

Пікірлер: 27
@hlhl5962
@hlhl5962 5 ай бұрын
very clear and practical, thank you.
@jidowu6019
@jidowu6019 3 жыл бұрын
Thank you for your hard work and effort into developing these informative and educational videos on fire alarm system design. I would like to donate money as a token of my appreciation. You will never realize how priceless your channel is and how much I value your work. Your work is thorough, organized, and presented in a rudimentary "easy to understand" manner. I am highly impressed and grateful! Thank you so very much!
@AllaboutFireProtection
@AllaboutFireProtection 2 жыл бұрын
Thank you very much!
@jidowu6019
@jidowu6019 3 жыл бұрын
If you have Cashapp, I can donate, or I can donate in any other manner that you desire. I feel like I am doing you injustice by soaking up all of this priceless knowledge.
@AllaboutFireProtection
@AllaboutFireProtection 2 жыл бұрын
Thank you for your support. I don't have a cashapp, but I appreciate that you're willing to help. With those words, it's more than enough to inspire me more to vlog and it's priceless.
@lognum4155
@lognum4155 14 күн бұрын
what is it's not a beam? what if it's a soffit?
@leojk4321
@leojk4321 8 ай бұрын
It's US based Regulations. Not applicable to UK. UK has completely different numbers and parameters.
@dingcolarte6131
@dingcolarte6131 4 жыл бұрын
Thank you for the video...What are the requirements by installing the smoke detector above the false ceiling and in the sub-floors, the rooms are data center and computer room.
@AllaboutFireProtection
@AllaboutFireProtection 4 жыл бұрын
Hi. Thank you for your query so everyone will be aware of the requirements too. Like what I had explained in my tutorial here in this link kzfaq.info/get/bejne/mJqGaa-Cqde5l2Q.html, the requirements of having a fire alarm system or your fire detection varies depending on the type of the occupancy of the building and which code you are going to refer or if there is a local code in your country. However, there is a specific requirement especially for data center like in your example. For the protection of IT equipment from risk of fire, you may consult the requirement from NFPA 75. Refer to clause 9.2.2 of NFPA 75 2017 edition, above false ceiling and sub floors are required to be provided with automatic detection systems. You may need to consult NFPA 75 also for the fire extinguishing system requirement especially for this critical room.
@markusplaytime3191
@markusplaytime3191 4 жыл бұрын
Thank you. This is very informative 💟
@AllaboutFireProtection
@AllaboutFireProtection 4 жыл бұрын
Thank you..
@aravindmuruga
@aravindmuruga 3 жыл бұрын
Hi 👋very useful video. Could you please explain pathway class designation and Building pathway survivability
@AllaboutFireProtection
@AllaboutFireProtection 3 жыл бұрын
As a designer, we have an option to select from the Pathway class available from NFPA 72 if our locally accepted standard is NFPA or if our project specs require. Pathway class operates and summarize in the following manner when abnormal conditions exist within the circuit of IDC, SLC & NAC: Class A Provide redundant path Reports trouble signal from any single open, ground & single fault Circuit continue to operate from single open, ground & fault Class B No redundant path The circuit does not operate at any single open. Reports trouble signal from any single open & ground fault. Class X Same as Class A except that it can also operate at any single short circuit and reports trouble signal. The circuit can operate at a combination of open & ground faults. Pathway survivability requirements will depend on your local fire code or any code adopted by your country. Designers have an option from pathway survivability 0 - 2. This is basically an added protection aside from mechanical damage but also from fire attacks. Pathway survivability must have the following conditions: 0 - No requirement for pathway survivability. 1 - Any or more of the ff: 2-hour fire-rated circuit integrity (CI) cable 2-hour fire-rated cable system 2-hour fire-rated enclosure or protected area 2-hour performance alternatives approved by the authority having jurisdiction 2 - If the building is sprinklered, any of more of the ff: 2-hour fire-rated circuit integrity (CI) cable 2-hour fire-rated cable system 2-hour fire-rated enclosure or protected area 2-hour performance alternatives approved by the authority having jurisdiction
@aravindmuruga
@aravindmuruga 3 жыл бұрын
@@AllaboutFireProtection thanks for your kind information. Some thing I get it from your reply. 😊 I will study ...
@aravindmuruga
@aravindmuruga 3 жыл бұрын
@@AllaboutFireProtection I have an more doubt.. 1.What is the reason for non using any clean agent systems at substation/Battery room and indoor dry type transformer areas. 2.What is the requirement (height) of detector installation of bottom of the raised panel (false flooring) 3.Detectors installation Requirement of the cable trench area and substation basement. Please clarify about this
@AllaboutFireProtection
@AllaboutFireProtection 3 жыл бұрын
@@aravindmuruga Hi Aravind, it's nice to hear from you again. In my response to item 1, the requirement of provision for fire protection always depend on which code and occupancy we intend to design. If it's already known that let's say sprinkler is required and we opt for an alternative solution like gas suppression system in the rooms you mentioned to avoid damages and business continuity disruption, we can always go for gas suppression system as it is intended to protect class C fire too. However, they are also not applicable in some applications where it is reactive to some chemicals and those are written in the manufacturer's manual so you should take care. Fire in Battery room like using lithium-ion where thermal runaway occurs cannot be protected by a gas suppression system unless there is a specific test conducted by the manufacturer that they can be used. Transformer room is excluded in sprinkler protection depend on the code you use and if the conditions are met like, min. 2 hrs fire-rated construction, provided with detection etc...(2) Detector can be mounted in any orientation shown in NFPA 72 for underfloor installation. (3) Check your code if fire alarm is required in that particular occupancy, obviously cable basement & trench are the part in a substation where we have a lot of combustibles like a group of cables hence this is the reason most designers propose to put detector in those areas.
@aravindmuruga
@aravindmuruga 3 жыл бұрын
@@AllaboutFireProtection thank you very much 😊🙏
@lc1288
@lc1288 4 жыл бұрын
nice content
@AllaboutFireProtection
@AllaboutFireProtection 4 жыл бұрын
Thank you luzzy..
@Su-nf8oq
@Su-nf8oq Жыл бұрын
May I know which country standard?
@AllaboutFireProtection
@AllaboutFireProtection Жыл бұрын
Hi most of the topics I discussed are about NFPA standards.
@user-uv9zp1bh7t
@user-uv9zp1bh7t 2 жыл бұрын
I have a question, there is beam ceiling with height of 5.5 m and the beam depth is 1.1m and distance between beams 1.6 m (this case is not as mentioned in the code so how to locate heat detector? Sorry another question related to integration between smoke and heat detector in one beam ceiling as my case above?
@AllaboutFireProtection
@AllaboutFireProtection 2 жыл бұрын
Your spacing for heat and smoke detector for ceiling with beam construction are totally different in requirement. In your situation above, since the beam depth is more than 460mm but less than 2.4 mtrs, the spacing of heat detector at right angle to the direction of beam travel shall be 2/3 *listed spacing. While for smoke, since your beam depth is more than 10% of height which is 5.5mtrs and spacing between beam is less than its 40% of its room height, then smooth ceiling spacing can be used within each beam pocket while 1/2 of its spacing in direction perpendicular to the beam.
@mdtutulhasan9079
@mdtutulhasan9079 Жыл бұрын
Are these guidelines compliant with nfpa-72?
@AllaboutFireProtection
@AllaboutFireProtection Жыл бұрын
These guidelines are actually from NFPA 72.
@joserodriguezjr.6422
@joserodriguezjr.6422 2 жыл бұрын
That intro is way to Long lol. Great video though . Yes I know I can scroll past it lol
@AllaboutFireProtection
@AllaboutFireProtection 2 жыл бұрын
Thank you for watching.
Fire alarm design - Battery Calculation #Design #Batterycalculation
18:46
All about Fire Protection
Рет қаралды 10 М.
There are two types of smoke alarm. One of 'em ain't so good.
24:56
Technology Connections
Рет қаралды 2,1 МЛН
Fortunately, Ultraman protects me  #shorts #ultraman #ultramantiga #liveaction
00:10
Happy birthday to you by Tsuriki Show
00:12
Tsuriki Show
Рет қаралды 11 МЛН
Smoke Detector Spacing Requirements Part 1
21:31
Pyrotex Systems
Рет қаралды 21 М.
Heat Detector Spacing Requirements
20:29
Pyrotex Systems
Рет қаралды 8 М.
Fire Alarm Installation Training - Design tutorial Part 3/3 #Firealarm #Design
1:32:55
All about Fire Protection
Рет қаралды 12 М.
Smoke Detector Spacing Requirements Part 2
22:16
Pyrotex Systems
Рет қаралды 7 М.
Fire Alarm Installation Training - Design Tutorial Part 1/3 #Firealarm #Design
31:50
All about Fire Protection
Рет қаралды 47 М.
NFPA 72 Requirements for Duct Smoke Detectors
12:00
Pyrotex Systems
Рет қаралды 7 М.
Fire alarm design - Duct smoke detector #Firealarm #ductdetector
12:54
All about Fire Protection
Рет қаралды 1,2 М.
Xtralis OSID Beam Detector Demonstration (2017 Seminar - Part 17 of 17)
13:24
What is a Fire Alarm System?
11:06
RealPars
Рет қаралды 2,1 МЛН
Class 6 | Smoke Detector Spacing per NFPA 72
4:44
Irfan CFPS
Рет қаралды 1,7 М.
Fortunately, Ultraman protects me  #shorts #ultraman #ultramantiga #liveaction
00:10