How I stopped my Zappi draining my battery

  Рет қаралды 10,258

Tomas McGuinness

Tomas McGuinness

Күн бұрын

In this video I try and explain the issues I had with my Zappi charger draining my home battery.
By outlining how the various CT clamps work, I do my best to run through how the Zappi and Inverter get confused, which results in my battery draining itself into my EV.
I outline the solution I found online, the changes made to the wiring and discuss the end result! Spoiler: it was successful!
Here is the myenergi article - myenergi.info/dc-coupled-batt...
If you want to me to elaborate on anything, please ask in the comments below!
If you found this video helpful, please press the like button and if you want to see more videos, be sure to subscribe!
Buy Me A Coffee
ko-fi.com/tomasmcguinness
Blog
tomasmcguinness.com
Twitter
/ tomasmcguinness
BlueSky
bsky.app/profile/tomasmcguinn...
============
Video notes: The sound in this video isn't great as I was using my iPhone's microphone and was stood too far away. I didn't think to check the sound levels when editing the video together :(
00:00 Introduction
00:46 The problem I had
01:40 My initial setup
04:46 Why the Zappi was draining the battery
11:02 How to rewire to solve the issue
14:37 Rewiring my Zappi
17:02 Success!
19:37 Wrapping up

Пікірлер: 101
@flashback9966
@flashback9966 9 ай бұрын
Very timely video as I'm just adding a battery/inverter to my system. There may be a simpler way to implement your hard wire approach, which I am considering. Simply ask the electrician cut the copper bus bar inside the consumer unit that links the Zappi breaker to the Inverter breaker. Reconnect them with a loop of cable, but run this loop outside the consumer unit, making it possible to fit the Inverter CT.
@tomasmcguinness
@tomasmcguinness 9 ай бұрын
Thanks for sharing that! It might be useful to anyone else considering a change like this!
@flashback9966
@flashback9966 9 ай бұрын
@@tomasmcguinness And thank you for highlighting the hardware fix. Always better than a software compromise! Reminded me of Boeing's MCAS fix for the short comings of the 737 MAX design. A dreadful, but avoidable, tradegy.
@tomasmcguinness
@tomasmcguinness 9 ай бұрын
I always prefer the simplest solutions. In this case, it’s just splitting the live into two.
@19sjaak
@19sjaak 3 ай бұрын
I came to say exactly this, an even more elegant solution with your suggested approach.
@flashback9966
@flashback9966 3 ай бұрын
@@19sjaakWent one step further on this by bringing out two series CT loops. This allowed for a solar priority sequence of: house first, then battery, then zappi car charger, and if any energy left over to heat water via immersion. It was getting a little cramped in the consumer unit, so we upgraded to a much larger one with individual RCBO's. System has been working for about 6 months now with no problems or software issues to worry about. Well worth the effort. I think maybe there maybe a market for dedicated solar consumer units like this.
@cingramuk
@cingramuk 10 ай бұрын
This is what the export margin setting is for. For anyone with this issue, get the installer to set the Export Margin properly before having it rewired. Also make sure your kit has v5 firmware as there was issues with Export Margin on the previous v3 firmware. The rewire trick does work but is more hassle now that firmware has fixed the issue. I had exactly this and was on the beta testing of v5 and it works great now. Depending on your inverter, it can be a bit hit and miss trying to work out what the export margin should be, but start at 50w and increase it until you see the battery not getting drained. For me, I think I settled on 150w on my Victron inverter. You are aiming to get a value as low as possible that the inverter doesnt normally export to before its real excess solar. Inverters will always flip flop a little around the import/export point to some degree, you are trying to find what this usually is with no excess and then set it a little higher on the MyEnergi kit so that it will always wait for that amount of export before starting to take it.
@tomasmcguinness
@tomasmcguinness 10 ай бұрын
You're right and I did try the export margin, putting it up as high as 150W. It just didn't work for me. Now, V5 has just come out in beta at the time, but I decided to press ahead with a solution I *knew* would work. The obvious downside to the export margin is that you end up exporting power that you might otherwise use. Over the 6 hours or so of surplus I get after my battery is full, that amounts to almost 1kWh. Doesn't seem like a lot, but it adds up over time. It's 4 miles of driving or 26 litres of hot water.
@cingramuk
@cingramuk 10 ай бұрын
@@tomasmcguinness fair point. How much does it cost to add the extra board and rewire the Zappi/Eddi? And how much export does that equate to? I guess at todays rates it’s offset a lot quicker but at the typical 4p/kWh it would take a while to be offset (export rates will drop along with import rates and already are heading back down) With v5 you shouldn’t need a high an export margin either as the new algorithm does a much better job of tracking the true excess and not reacting to spikes you get on hybrid battery/inverter setups. Would be ideal if all these devices could use a standard to communicate and do away with these workarounds entirely (MODBUS maybe?)
@tomasmcguinness
@tomasmcguinness 10 ай бұрын
It was £400 to rewire the consumer unit and to add a new supply for the Eddi. The payback will probably be a decade, like the solar panels themselves. My goal is to use all that I generate as I don’t generate that much (30kWh on the best day). You’ve convinced me that I should try the v5 firmware and see if the export margin works. That would be a nice follow-up video I think. As for standards, you’re dead right! It feels like the situation with smart home tech. Each vendor wants to lock you into their eco system. Thankfully that’s starting to change with standards like Matter, but I suspect home utilities have a long way to go!!! Most don’t even offer any form of local control.
@keyserzoom9154
@keyserzoom9154 10 ай бұрын
Came here for battery drain and multiple CT clamps from different vendor equipment. Straightforward solution and well explained. Perhaps one day we'll have defined standards for Smart meters that extend power control into the home... for now it's KZfaq, Henley blocks and software hacks :o)
@tomasmcguinness
@tomasmcguinness 10 ай бұрын
Thank you! I think we're in the same place that smart home stuff was about five to ten years ago. It's taken a long time for Matter to emerge and get adopted by the big players. Maybe we'll see something similar in home infrastructure stuff, like EV chargers and batteries.
@paullawrence8394
@paullawrence8394 6 ай бұрын
Excellent solution
@tomasmcguinness
@tomasmcguinness 6 ай бұрын
Thanks! It’s been working really well.
@stevekarlsen9597
@stevekarlsen9597 7 ай бұрын
Thank you Tom, very helpful, I'm about to get an EV and a Zappi and was trying to figure out a Solution using Solis config only...you can do it that way, but I think I'll go with your option right from install... 😊
@stevekarlsen9597
@stevekarlsen9597 4 ай бұрын
....Thanks again Tom, my Zappi install was done as per your video and all works a treat. Quick question: I'm on Octopus Intelligent GO which integrates to the Zappi through the Octopus app. I get charging slots in the Octopus app as soon as I plug the car in. My question is, with surplus solar, given the car is plugged in and the Zappi on Eco+, will it still push the surplus solar in to the car, my point being, will the Octopus app integration cause any issues? 😊
@davedevonlad7402
@davedevonlad7402 7 ай бұрын
Your solution was exactly the way my electrician put in my zappi. It works perfectly my 4k sola- Solis hybrid inverter and 10kw puredrive batteries run the house and my zappi will use any surplus from the sola and charge from the grid. You have done pretty much exactly the same as me and it works great. I just don't have an Eddi yet but hopefully soon. Thanks for the video it really helped me back up the decision to put in the Henry blocks. Ps: I get the same graph issues the data is pretty much correct but all the colours are wrong.
@tomasmcguinness
@tomasmcguinness 7 ай бұрын
Great! I’m glad this helped confirm your decision!
@marcoferraris6451
@marcoferraris6451 8 ай бұрын
Good job man
@tomasmcguinness
@tomasmcguinness 8 ай бұрын
Thank you!
@briank8584
@briank8584 9 ай бұрын
Thanks for the excellent explanation, really clear. I am having the same problem with the battery draining during the day as soon as it drops below 100% and the Export Margin part does not apply. The Zappi then draws from my panels and batteries and does not stop. In addition at night, no matter what I do I cannot stop the battery discharging. Sadly I cannot see a way to limit the discharge of my battery through my Deye inverter while the car is charging at cheap times of the night. The firmware update has not solved the problem either. As a result, when I watched your video, I thought it would solve my problem, and it would......but it also nearly made me cry!!! When the installer first set up my zappi, it was put, in error, directly onto the mains and separate to the consumer unit. After many calls with them and myenergi, they came back, realised their error and wired it through the consumer unit. Of course, I now realise that leaving it alone would have solved my battery drain issue!
@tomasmcguinness
@tomasmcguinness 9 ай бұрын
Agggggg! That's annoying. Have you tried upgrading your Zappi to version 5 of the firmware? I'm told that will resolve most issues with the Export Margin. I'm going to try this on my own setup when I get a chance, just to see how it works.
@markglanville6495
@markglanville6495 10 ай бұрын
I had exactly the same problem, but solved it in a different way. My AC coupled system comprises of a 3.4kw grid tied solar system, a Sofar me3000sp inverter, Pylontech Us3000c batteries, plus a Zappi and an Eddi. After using 50w thresholds described in the My Energy forum, the flip flopping between components fighting for priority was cured but I still had the issue of the Eddi and the Zappi draining my batteries if either of them were set to use the Octopus Go 9.5p Tarriff between 12.30am and 4.30am. Switching off the batteries on nights I wished to charge the car was not a cost effective or convenient solution. I then discovered the time of use mode from KZfaq, especially the one posted by Rural Electric Systems on 1st May 2021. He was using old Sofar Firmware, version 3 hides the"Time Of Use Mode" under an extra "Work Mode Set" menu. He goes through setting manual override timers which are called "rules" . You can force the inverter to manually come out of auto mode and charge the batteries at given times. You can stack up these timers under rule 1, rule 2 etc. Each for various days of the week and months of the year, enabling them to work in conjunction with each other or alone. This functionality is not described in the manual. Other inverters probably have similar functionality, I don't know. Then the penny dropped, if the batteries are charging they can't be discharged! Initially I disregarded this thought as why charge batteries from the grid and potentially waste solar energy during the day? But Time Of Use mode let's you set the charge rate for each rule. I set the timer to switch on and off at Octopus Go times with the SOC (state of charge) set to 100% and a charge rate of only 100w from Jan 1st to Dec 31st. This works perfectly, 100w for 4hrs only costs arround 4p you could set it lower. The only downside is the house runs from the grid during those 4 hours, in my case the house only consumes about 200w at night, costing me arround 8p on the 9.5p Tarriff. I was then left with one unrelated issue that might be worth mentioning and could be limited to my type of Sofar inverter. Ben Allen in Poole who Carrie's out Pylontech repairs thankfully came to the rescue. My Sofar v3 firmware will only discharge the Pylontech batteries to 20% before switching back to the grid. He sent me a link to the setfirelabs.com website that explains in detail how to upgrade the Sofar me3000sp firmware to v3.06 with a link to the file download. This will enable discharge down to 10% for the Pylontech us3000c's which can cope with only 5%, so there is still a margine of safety. Hope this helps someone!
@tomasmcguinness
@tomasmcguinness 10 ай бұрын
Thanks for sharing that! I had the same problem, which I solved in a similar way, using a long “forced charge” period. Once I had this rewired done, I shortened the force discharge to only 90 minutes, so if the battery has any power, it can continue powering the house during the Octopus Intelligence off-peak period. I also avoid any issues with Octopus charging my car outside the off-peak hours.
@mikesimmonds1916
@mikesimmonds1916 6 күн бұрын
I need to read this several times as this is exactly the issue I'm going to suffer. I didn't upgrade the firmware as I head stories of people wrecking the units so never did anything. I'll look into you advice and carefully adopt it . Thanks so much for posting so fully.
@davidsmith8728
@davidsmith8728 3 ай бұрын
We have the same problem. We have 32 solar panels, generating almost 8kW at peak together with 17.7 kWh of battery storage. Looking at page 26 of the Zappi manual, it says that ... "If the property has a static AC battery system installed, it is possible to get the Zappi to work in harmony with the battery system, PROVIDED A CT HAS BEEN INSTALLED to monitor the battery inverter. Then in the Zappi settings, set it to "Avoid Drain' and this should stop the Zappi draining the battery when using surplus power from solar generation. So we are waiting to get another CT installed as described above and then we will see what happens.
@tomasmcguinness
@tomasmcguinness 3 ай бұрын
If you have a separate inverters for the solar and battery, this would perfectly well, since the Zappi would understand when the battery itself was discharging. As mine is Hybid, it cannot tell the difference between battery power and AC power. I guess Let me know how this works out for you!
@davidt1016
@davidt1016 10 ай бұрын
Thanks for the video .I have the same setup as you ,but I use the battery to smooth out the solar output and keep my car charging , I just monitor the solar output and battery discharge so I can stop the Zappi charging and keep the charge I need in the battery.
@tomasmcguinness
@tomasmcguinness 10 ай бұрын
Thanks for sharing that. How did you achieve that?
@davidt1016
@davidt1016 10 ай бұрын
@@tomasmcguinness I just set the zappi on ECO and adjust the Tesla charging current up or down as I get more or less Solar ,watch the battery % and stop the zappi as and when needed to preserve the amount of battery I need .
@tomasmcguinness
@tomasmcguinness 10 ай бұрын
Interesting. I guess you've automated that?
@bagenzufo
@bagenzufo 11 ай бұрын
Volume a bit low but nice video, got the exact same issue but I am already wired up like your new way, will try moving my CT clamp, thanks for tip
@tomasmcguinness
@tomasmcguinness 11 ай бұрын
First time doing a video like that. I’ll see if I can adjust the volume.
@DenisNolan
@DenisNolan 9 ай бұрын
Nice video. I have the exact same experience. I have export set to 150w and it has been fine most of the time. I've the inverter set to self-consume and once the battery is fully charged, it allows then for the Zappi to run (due to observing export on the grid CT). Once the charge starts with say 2.5Kw of solar from the panels, 2.5Kw of that would be going straight to the car All is fine and works as I would expected. Battery is full at this stage with no discharge. The exact same thing happens that you explained: suddenly a cloud comes over and the solar generated drops, the inverter still thinks the house requires 2.5Kw, so then the inverter starts tapping into the battery to supply that demand. Even though I have export set to 150w, using my shelly EM I see it bounce around. It does try to get back to 150w export, but it is a sea-saw effect. Car charging is steady, but the odd thing is that if the sun is out again after a cloud passing, suddenly the charge is now heading to 3-4Kw. I'm just in this zone where the zappi observes a jump in export and adds that to the demand. I'm sure there is probably some adjustments to make with timings. For the meantime my fix is to set the battery on the solis app to not discharge during the day for a few hours if I have the car plugged in. A bit manual, but besides doing a rewire, it's the only way at the moment for me on a good sunny day to be sure. I may look at something smart with modbus and home assistant, but I suspect the rewire would be the faster approach.
@tomasmcguinness
@tomasmcguinness 9 ай бұрын
Have you upgraded to the V5 firmware on the Zappi? Some people have commented that the new firmware fixes this issue. V5 was in beta when I was looking at a solution. The reviews of it were terrible at the time. I'm told it's fine now :)
@DenisNolan
@DenisNolan 9 ай бұрын
@@tomasmcguinness Yeah I'm on v5 presently. Their latest for both the eddi and zappi. Forgot to say that in my original reply. Mind you I have been having some odd issues with the v5 since the update. Main one that I had a few weeks back was the zappi losing connectivity to the harvi which is less than 10 meters away. A whole system reset did fix that, but I've been dealing with the battery drain since day one. The installer would have wired in the CT to the meter tails, but there is new regulations on what can be installed in the ESB meter cab. I guess main thing is that the car gets charged from some form of free energy.
@tomasmcguinness
@tomasmcguinness 9 ай бұрын
Ugggg, so it’s not as fixed as they claim. I always figured that the issue wasn’t the Zappi, rather it was the inverter. That seems to remain the case!
@lcphotography888
@lcphotography888 5 ай бұрын
Thank you, I have the same problem
@tomasmcguinness
@tomasmcguinness 5 ай бұрын
Did this help?
@lspudpage
@lspudpage 9 ай бұрын
Hi Tomas, thanks for a great video, I'm currently at the stage where I have the solar, Foxx inverter and home batteries plus an Eddie (with Harri), and using the Export Margin I have managed to balance my house battery drain when heating water. I have just got an EV so am now looking to get a Zappi installed, my hope is I'll be ok using the Export Margin tweak in v5 of the firmware to balance my car charging in the day from solar, the worry that I'm posting about is overnight charging of the EV. I want to be able to charge my car from the grid in my Octopus Go period (4 hours early morning), but I worry that this will start draining the batteries first. So as an example the car will start charging at lets say 3kw at 1am, my inverter will see this as house load and will start draining the batteries instead of letting the Zappi just take from the grid. I have heard that the way to overcome this is to set the house batteries to also charge at the same time, but in my scenario I don't want to charge the house batteries overnight, I want those to be topped up by the sun the next day. Could your rewire (which I could get done when having the Zappi installed) be a solution to this?
@tomasmcguinness
@tomasmcguinness 9 ай бұрын
I believe it would. As I understand it, it's about the location of the CT clamps. Adding the Henley block, as I did, means that the Inverter never sees the load from the Zappi or Eddi. If you did something similar, the Zappi could be drawing 7kW from the grid and the inverter wouldn't know and therefore wouldn't discharge the battery to meet the demand. You just need to make sure that the Eddi/Zappi clamp sees *all* the load from the grid. You're also right in that it would be difficult to use the house battery to charge your EV. Have a chat with your installer and they should be able to advise you best!
@thevandwella
@thevandwella 3 ай бұрын
Thank you Tom for the video. If you set the Zappi to fast charge, will the battery discharge into the Zappi ?
@tomasmcguinness
@tomasmcguinness 3 ай бұрын
No, it won’t. The inverter cannot see the load from the Zappi, so it won’t know to discharge the battery. You could set to Eco plus and then force the battery to discharge. The Zappi would see that as a surplus and divert it into the car. Does that help?
@user-uo8bl1wf5p
@user-uo8bl1wf5p 4 ай бұрын
Hi, where is the link to the original myenergi forum? I remember seeing it as it had little diagrams etc? Thanks L
@tomasmcguinness
@tomasmcguinness 4 ай бұрын
Bugger! I didn't realised I never added it to the description. I've rectified that now - here is the link myenergi.info/dc-coupled-battery-drain-hybrid-inverter-and-zappi-t3397.html
@user-of4dk6ts8k
@user-of4dk6ts8k 9 ай бұрын
Thanks Tomas - a really helpful video and nicely explained! I'm fairly new to all this, and just need a bit of help making sense of all these options! I have 4kW solar pv, an 8.2kW GivEnergy house battery, and a MyEnergi Zappi (v2) which I've just upgraded to v5. I'm a relatively low mileage, infrequent EV user and the house is new, all electric and pretty efficient (ASHP etc), though I don't find I'm exporting all that much overall. I'm thinking of getting onto the Octopus Intelligent tariff, so that I can charge the car at cheap rates overnight on those occasions I need to plug it in. And if the car battery is ever empty, I can usually afford to wait 3 nights to get back to a full charge. I've assumed that in winter, I could set the house battery to charge up from the grid during the off-peak hours (and if necessary set it to only discharge outside these hours), and then plug the car into the zappi on any evening I need some charge, set to add - say - 30% on any night between 2330 and 0530h. And in the summer, presumably set an export margin on the zappi, so I can keep the car plugged in during the day to capture any excess solar. Does all this make sense?! I don't think I need the Intelligent Flux tariff, as with my levels of use, I think any little I lose to the grid through low value export would be more than offset by the advantages of 7.5p/kWh off peak for house and car use. Many thanks, if you or others do have time to offer any comment/advice!
@tomasmcguinness
@tomasmcguinness 9 ай бұрын
Thank you for watching! I'm an Octopus Intelligence user (I have a Tesla) and I do pretty much exactly what you describe. At present, I charge my battery to 35% during the off-peak and that will increase as we move into the winter months. For my EV, I use the Zappi schedule to turn it on between 11:30pm to 5:30am. Octopus then control when the car actually charges during that period. Whilst it's a very cheap tariff, it just doesn't play very nicely with the Zappi at the moment. There are two issues: Firstly, when you have set to Eco+ to charge from surplus solar during the day, Octopus will actually tell the car *NOT* to charge, since it's outside the off-peak times! I've lost a lot of kWh of milage because I forgot about that. Secondly, if you get an Intelligence charging schedule that includes times outside the normal window, say 10:00pm to 10:30pm or 6:00am to 6:30am, my Zappi won't be turned to FAST, so the car can't charge during those times. This means you might not hit the charge percentage you've asked for. I find that I have to turn off the Octopus Intelligence control 99% of the time. It just gets in the way. You still benefit from the off-peak pricing. When I know I want to charge the car overnight night, I have to switch the control back on and then just use the normal hours, which is far from ideal! Octopus have been promising Zappi integration since the start of the year, but nothing yet :(
@user-of4dk6ts8k
@user-of4dk6ts8k 9 ай бұрын
@@tomasmcguinness thank you so much - your comments are really helpful! I wasn't sure whether you could switch off the intelligent control, but if so (and still benefit from the cheap rate), then I'm minded to do as you do and work on 'manual' most of the time. Out of interest, couldn't you leave it set to manual (with the zappi schedule active) when you know you want to charge the EV overnight, rather than switch the intelligent control back on? Cheers
@tomasmcguinness
@tomasmcguinness 9 ай бұрын
You can indeed turn off the control. However, in order to keep the tariff, you do need to let Octopus control the car's charge every few weeks/months.
@user-of4dk6ts8k
@user-of4dk6ts8k 9 ай бұрын
@@tomasmcguinness Ah, OK - thanks for explaining that. I hadn't realised :)
@terryjimfletcher
@terryjimfletcher 10 ай бұрын
One of the issues your solar+battery setup has is that they share an inverter, which is great for efficiencies, but means that the Zappi has no idea of whether it's the solar panels providing the excess power (Zappi should consume) or the batteries (Zappi should NOT consume). That's the choice you have to accept with a hybrid solution (unless you can somehow monitor the DC power from the batteries to the inverter! ). Also your setup won't allow you to charge your car from banked solar when you come home at night. Of course if you only intend for the batteries to apply your house then this is moot. Great video!
@tomasmcguinness
@tomasmcguinness 10 ай бұрын
Thanks for watching! I had the Zappi installed before my solar and battery, so the installers probably didn't think about any potential issues with the hybrid inverter. I wasn't really aware of the difference at the time, so had no input. I do have access the inverter's data, so I can see the breakdown of it's output i.e. power from solar and battery's charge/discharge amount, but sadly there is no way to push this into the Zappi. I had some crazy idea about trying to "fake" the battery by simulating a CT clamp, but I've no idea if that could be made to work. I need to understand CT clamps a little bettery And you're right about not being able to charge the car via the battery. That was a conscious decision I made. I believe I could force discharge the battery, but I haven't tried that yet. My inverter software/control is terrible.
@kieranmccreedy271
@kieranmccreedy271 8 ай бұрын
Please tell me the sparky came back with more blanks for the new CU and tidied up the rough CT wiring 🙈
@tomasmcguinness
@tomasmcguinness 8 ай бұрын
Yes. The CT clamp is gone and the CU is closed up. When I took some of the footage, he was mid job :)
@dannymm
@dannymm 11 ай бұрын
Did you try adding an extra CT clamp on the output of your inverter/battery so the Eddi and Zappy can monitor it? It will then show up in the myenergi app as a solar/battery device. That may have been a simpler solution than the re-wire. I have the same setup and use two of the wireless harvi CT clamps. One at the smart meter and one at the inverter/battery output.
@tomasmcguinness
@tomasmcguinness 11 ай бұрын
I did that shortly after installing my Eddi, but it didn’t help. The clamp cannot tell the difference between what’s coming from solar or what’s coming from the battery. It has more accurate information for sure, but battery drain still happened. That’s when I went for the rewire. I didn’t cover that in the video. Probably should have! I guess there are a few different variables at play and the responsiveness of the inverter is one of them. With this change, I won’t have to worry about export margins or anything, so it’s been worth it from that point of view.
@dannymm
@dannymm 11 ай бұрын
I thought you might had tried it. I have a Solis hybrid inverter with battery and i don’t seem to have the same issue with the battery draining.
@tomasmcguinness
@tomasmcguinness 11 ай бұрын
I have a Solax inverter and battery. I tried tweaking the export margin, but once it started discharging the battery, nothing stopped it. A feedback loop of sorts!
@MrKlawUK
@MrKlawUK 10 ай бұрын
@@tomasmcguinnessyep we had this - added a harvi (ran out of CT clamp slots) to clamp the battery/inverter output. That appears as a ‘dumb’ battery on the myenergi app and you can set the zappi up to ‘avoid drain’ so it adds that CT clamp to its excess calculations. All seems fine so far.
@tomasmcguinness
@tomasmcguinness 10 ай бұрын
That's good! Unfortunately, that didn't work for me. Once the feedback loop started, the battery always ran down.
@davidfarrell1062
@davidfarrell1062 9 ай бұрын
Im looking at a huawei solution for inverter and batteries and with launch of new huawei 7kw charger am i better off to wait to gain from better potential integrations than using seperate manufacturers and trying to come up with workarounds.
@tomasmcguinness
@tomasmcguinness 9 ай бұрын
I'm not familar with Huawei's stuff, but I would still say that having an integrated solution would be best as it should give you complete control. Recently myenergi launched their Libbi battery and it gives you full control over its charge and discharge behaviour when working with Zappi and Eddi. I would imagine the Huawei would provide similar control. The app looks great!! Of course, if you enjoy building workarounds, cobble something together :) Have a chat with your installer and they should be able to provide you more details and maybe give you a demo?
@jayp913
@jayp913 9 ай бұрын
Tomas great video. Would this be an issue with a three phase zappi? I am guessing it would?
@tomasmcguinness
@tomasmcguinness 9 ай бұрын
I expect so, but there might be other differences that affect it.
@maverlk7
@maverlk7 10 ай бұрын
Hi, great explanation of the issue! I have a similar set up: 7kw solar, 5kw solar edge inverter, zappi, eddi and a tesla powerwall 2. I initially had the same issue, but the export limit and setting priority order for surplus solar to: house, eddi, battery, zappi completely solved the issue. The only remaining issue is the frequent stop starting of solar surplus to the car due to british weather. I worry as to what impact this constant charge cycling will have on car battery life and also the wear and tear of constantly stop/starting may have. I intend to solve this by going on to Octopus Flux tariff and charging my car and tesla powerwall only in the 3 hour night window; letting amost other surplus solar go to export. At 20p for export and 18p for import during the night window, this makes financial sense and means my car has a nice, level, regular charge of about 21kwh per night which will cover my 250 mile per week use (car averages 3.1 miles per kwh so needs 70 kwh per week of charge). Hopefully my solution makes sense? I might also flip to octopus go for a few months in winter when solar production crashes and back timo flux in March.
@tomasmcguinness
@tomasmcguinness 10 ай бұрын
Thank you! That's a good point with the start/stop of the charger. I hadn't really given it much thought. Have you seen any studies or data on the impact of it?
@maverlk7
@maverlk7 10 ай бұрын
@@tomasmcguinness I haven’t and I can’t find any data, but my one year old 9000 mile BMW iX is in the workshop right now for a warranty repair on a failed charge port. It could be coincidence, but it is a nagging thought that all that stop start and variable charge rates may be a factor here. A switch to octopus flux would allow me to have a fixed charge for 3 hours a night and focus solar on export and then in winter, with no solar, a flip to octopus go would offer the same nighttime charge window for 4 hours.
@tomasmcguinness
@tomasmcguinness 10 ай бұрын
Interesting about the charge port. We're always told that repeated charging of your phone etc. degrades the battery. I wonder if it's the same for car battery. I moved from Octopus Go to Octopus Intelligence a few months back. You get a longer window and a slightly cheaper rate. Would be worth checking if you can avail of it.
@maverlk7
@maverlk7 10 ай бұрын
@@tomasmcguinness I looked at octopus intelligent, but did not like the idea of handing over charging control and have concerns that a daytime charge triggered by them would be at the ‘boost’ rate and may take a blend of battery and grid power. I am currently crunching numbers on all 3 options (go, intelligent and flux) as my current ‘go’ tariff ends on 3rd august
@tomasmcguinness
@tomasmcguinness 10 ай бұрын
With Intelligence (for EVs) you get cheap power between 11:30 and 5:30 regardless. When the car is plugging in, it might get scheduled to charge outside those hours, but that power is off-peak too, so you don't have to worry. People try and trick it by saying they need their car at 100% by 4AM. I've seen examples of them scheduling charges at 9pm and people putting their washing machine on etc. The only downside with solar, is that I need to keep the control turned off most of the time, otherwise it won't charge on surplus solar. They are supposed to have support for the Zappi charger coming soon, but I've been waiting a long time. They do have a new tariff called Intelligent Flux coming soon, which you might be interested in - octopus.energy/press/smarter-cleaner-cheaper-octopus-launches-new-smart-tariff-to-unlock-solar-and-storage/
@gtlscot1151
@gtlscot1151 3 күн бұрын
Can I ask and apologies if I missed is your battery DC? I am sure my inverter and battery on a different CU what difference if any would this make? I am even happy to have all battery and solar excluded from Zappi as it is a small array. Last still works the same boost charging?
@tomasmcguinness
@tomasmcguinness 2 күн бұрын
Do you have an “island” to provide power from your battery in the event of a power cut?
@trisknight9430
@trisknight9430 3 күн бұрын
So my tails go into a Henley block in the meter cabinet and the zappi is taking power from there into a separate consumer unit for the zappi. I’m having solar and battery next month and wonder if this will prevent my zappi from discharging my battery
@tomasmcguinness
@tomasmcguinness 2 күн бұрын
Yes, that arrangement sounds like what I ended up. The trick is where the inverter’s CT clamp goes. If the CT clamp doesn’t “see” the load from the Zappi, it won’t discharge the battery to feed the Zappi.
@Paramonos
@Paramonos 6 ай бұрын
I solved this by writing some software off a Raspberry PI that controls the Zappi, my Tesla M3 and sets the Zappi to Eco mode to only charge when the Tesla Powerwall reaches 98% and stops charging when it gets to 95%. This deals with any fluctuation in use/generation and ensures that the Powerwall is at least at 95% at the end of the solar day. I can then run it in a different mode that sets the Zappi to 7kw between 11:30 and 5:30 (Octopus cheap tariff) and the Powerwall is set to not discharge during these hours. The Raspberry PI is then controlled using a 'front-end' UI off my phone (the RP is programmed using NodeRED). I was doing all of this manually for a long time but decided to set it up this way so that is was easy for the wife to use. It also ensures that I don't export at all during the year (as long as I keep space in the M3 for charging).
@tomasmcguinness
@tomasmcguinness 6 ай бұрын
Nice!
@peterbee8892
@peterbee8892 3 ай бұрын
I have a zappi and 2 solar inverters and a battery with inverter. I'm experiencing battery drain when octopus intelligent gives me non standard mid afternoon charging slots . I can fix by manually setting new battery charge times but want a better solution. Any ideas
@tomasmcguinness
@tomasmcguinness 3 ай бұрын
Hi. Sounds like you have an amazing solar setup. As I understand it, it's all about the location of the CT clamps, but in your situation, you must have at least four clamps on your main live/neutral. To prevent the Zappi from discharging the battery, you would need to do like I did and hide the Zappi from the battery. Open a ticket on the Zappi support forum and post the link here. If you could include a simple diagram with your current arrangement and location of the CT clamps, I can have a look!
@DTech101
@DTech101 8 ай бұрын
Yeah I’ve just finished commissioning my Victron system I’ve designed it with a Hager split board so just moved the EV circuit grid side and moved the CT for the Victron after the EV circuit and then the EV CT to the grid so it can load balance and grad the solar before the grid gets it after the batteries have charged. Hardwire over software everyday! Ever want a different charger your in the same boat design the system to incorporate all or most scenarios, rather than relying solely on software.
@tomasmcguinness
@tomasmcguinness 8 ай бұрын
Good point about changing chargers!! Hadn’t even thought of that!
@richardstamper5630
@richardstamper5630 Ай бұрын
That sounds about the same situation I was experiencing, however, I did notice you were charging the car at 3.5kwh but surely the Zappy can deliver 7kwh, why?
@tomasmcguinness
@tomasmcguinness Ай бұрын
It can. Typically, when at home, I charge at a lower speed. I believe this helps prolong the life of the battery.
@lordstevewilson1331
@lordstevewilson1331 10 ай бұрын
Could you not have used Harvi with 1 ct on main and 1 ct on inverter?
@tomasmcguinness
@tomasmcguinness 10 ай бұрын
I added a CT clamp to my inverter, connected to my Eddi. unfortunately, the problem remained. Once the battery started discharging into the car, it didn’t stop.
@BAC_Mono
@BAC_Mono 9 ай бұрын
I've had this issue as well, the best solution depends on what you want to achieve. If your main aim is to use as much of your solar electricity without exporting then I don't think you need to do this. If you have your Zappi set on eco+ and the batteries set to only discharge during. the day it shouldn't drain the battery but only export excess. In the evening your batteries power your house and then your car can charge at night draining the battery if you want?
@tomasmcguinness
@tomasmcguinness 9 ай бұрын
You're right, it shouldn't drain the battery when set to eco+. That wasn't my experience :( I'm told that the v5 firmware version resolves most of the battery drain issues by improving the Export Margin, but this way I don't need to reply on the firmware. At the moment, I'm charging the battery up to 35% on the off-peak tariff. This covers the house until the sun comes up and the panels start producing power. The battery then charges, and we use that power at night. I just don't see the benefit of discharging the battery into the car. Either way I'll be paying for that power, so just charging the car from the grid makes the most sense to me.
@BAC_Mono
@BAC_Mono 9 ай бұрын
@@tomasmcguinness yes I understand My perspective is to use as much of the solar ourselves and not export and so I like to make sure that the battery has enough space each day to absorb the solar together with the water heater and the car when I am parked at home some days We’ve been using 84% of our 8kWP system this way and the rest is from the w grid
@craig4442-si2gm
@craig4442-si2gm 10 ай бұрын
Hi Tom, great video, you have come to my rescue after being a bit unconvinced by the myenegi solutions. Had my install for a month and have been having the same issues. Does the solution cause any issues with night time scheduled grid charging of either the EV through the Zappi or home batteries through the inverter. Will it restrict any of the charging capacity through the zappi or inverter. New to all this and still in communication with the instllers so hopefully they will sort. Cheers Craig
@tomasmcguinness
@tomasmcguinness 10 ай бұрын
Hi Craig, Thanks for watching my video. The rewiring doesn't change anything in terms of capacity or scheduled charging. It simply allows me to put the inverter's CT clamp so it ignores the power being used by the Zappi and Eddi. Since making the changes, my battery hasn't discharged unexpectedly and more of the solar power gets put into my hot water and car. When I was using the grid excess setting of 150W, it meant I could lose almost 1kWh of generated solar over 6 hours. I hope your installer can sort this out for you! Tom
@sassasins031
@sassasins031 13 күн бұрын
So you are constantly drawing from the grid for your Zappi, when random cloud cover etc, to charge up your car at a slower rate. You don't want a 100% renewable energy strategy? Wouldn't it be better to get an additional battery and then use more renewable with a faster charge rate?
@tomasmcguinness
@tomasmcguinness 13 күн бұрын
At this moment in time I charge my car using grid power alone.
@sassasins031
@sassasins031 13 күн бұрын
@@tomasmcguinness Is that for the best financial gain for yourself rather than using your stored energy instead?
@tomasmcguinness
@tomasmcguinness 13 күн бұрын
@sassasins031 yeah. I get 15p for every unit exported and I pay 7.3p to import during the off peak. As the car is under Octopus control, I’m trusting they charge when electricity is as green as possible.
@briankirk2995
@briankirk2995 7 ай бұрын
High Thomas.. sorry Fella but you are to guiet….see how Rosie Barns comes over in you tube, here’s hoping we will see you again with better audio…..Brian
@tomasmcguinness
@tomasmcguinness 7 ай бұрын
Yeah, I know! I was using my phone microphone and was stood too far away. I’ve since picked up a better microphone and my later videos are much better!
@mikeh9446
@mikeh9446 9 ай бұрын
Solax Batteries, when charging the car overnight on GO reduce Solax battery charge to less than 50% if you do not need a battery charge, good for summer in winter battery system charged to 100% works for me as I do have solax master and slave 11.6kwh charge times same for EV on Go Off Peak.
@tomasmcguinness
@tomasmcguinness 9 ай бұрын
Thanks!
THE ONLY Zappi video YOU need to see!!
13:06
SOTA Electrical
Рет қаралды 11 М.
Should I get more battery capacity? - Is it worth the cost?
18:12
Tim & Kat's Green Walk
Рет қаралды 10 М.
ХОТЯ БЫ КИНОДА 2 - официальный фильм
1:35:34
ХОТЯ БЫ В КИНО
Рет қаралды 2,2 МЛН
OMG 😨 Era o tênis dela 🤬
00:19
Polar em português
Рет қаралды 9 МЛН
ДЕНЬ РОЖДЕНИЯ БАБУШКИ #shorts
00:19
Паша Осадчий
Рет қаралды 2,3 МЛН
Are You Calculating Maximum Demand Correctly?
12:08
eFIXX
Рет қаралды 26 М.
The IMPOSSIBLE Job...I Didn't Know If It Would Work.
13:35
SOTA Electrical
Рет қаралды 32 М.
Configuring the GivEnergy All in One
11:28
Speak to the Geek
Рет қаралды 12 М.
Home Storage Battery emptied overnight. How to stop it draining
12:04
How to prolong a battery's lifetime - Prof. Howey | Battery Podcast
34:45
Battery Generation Podcast
Рет қаралды 16 М.
Reconnecting Zappi (v2) to property WiFi router
7:21
Peter Guilliatt
Рет қаралды 4,9 М.
5 Reasons To Get A (Bigger) Home Battery
22:07
Gary Does Solar
Рет қаралды 259 М.
Why have I fitted a Zappi Smart Car Charger ?!
22:28
Petrol Ped
Рет қаралды 60 М.
Венозные Руки 🤯
0:25
MovieLuvsky
Рет қаралды 1,4 МЛН
NUESTRA HISTORIA ❤️ @Layaraoficial  @
0:20
Santi
Рет қаралды 20 МЛН
CRAZY MOM VS GOOD DAD
0:20
JULI_PROETO
Рет қаралды 4,8 МЛН
ФОТОШОП СВОИМИ РУКАМИ (@photoscapesbyclare - IG)
0:30
В ТРЕНДЕ
Рет қаралды 14 МЛН