Cooler float valves use a paddle arm that screws to the float valve and adjusts at the pivot point with a screw.
The problem is if the float valve is mounted high above the level of the water, such as on these larger commercial coolers, the float paddle is not resting on the water line properly when you simply angle the arm down for adjustment.
You MUST bend the arm to correct the angle of the float paddle where it contacts the water. This gives the most leverage and force against the float valve (which has water pressure trying to push it open) and will allow the float valve to open more and close more while requiring less water rise.
If the paddle is just bent down into the water, the arm can be adjusted to get the float valve to close (although piss poor) however the progression of the leverage against the valve is increased and there will be less float arm travel as the water drops when the pump starts. When improperly adjusted the arm drops the valve will not open as far and there will be a limited gpm water flow. The cooler may even evaporate so much water that the gpm of flow is not enough and the arm has to drop even more.
And this may even cause the water level to reach the lower section of the pump and cause starvation until the water level rises and the pump can prime.
The level is much better controlled with the paddle flat on the water line.
Only about 1/2" of water drop will be required to get that float valve to open at a higher GPM rate and in reverse only a 1/2" rise will be required to again close the valve completely.

Пікірлер: 51
@erd675
@erd675 4 жыл бұрын
Not much content on these type of issues thanks for showing this.
@Straycurrent
@Straycurrent 4 жыл бұрын
Today in the era of the Fluidmaster fill valve there must be two or three generations who never had the pleasure of fussing with that type of valve in any ordinary toilet. Rounded and oblong, like a football blunt on both ends. Don't miss em at all.
@ryanc8894
@ryanc8894 4 жыл бұрын
Great video , so much of this trade is common sense and simple fundamental principals
@jessicaarbogast3588
@jessicaarbogast3588 4 жыл бұрын
I just can't get my float to stop the water. It continues to overflow. I went and bought a new one and still does not work. What am I doing wrong? It seems so simple. I am very frustrated I hate swamp coolers
@sauljohnson4190
@sauljohnson4190 4 жыл бұрын
Thank you so much for making this video. I have an evaporative cooler and it just didn’t click in my head why the water would not shut off. Your awesome...
@jenniferdarvell5064
@jenniferdarvell5064 2 жыл бұрын
Out of all the videos this one was most relevant to my problem thank you for sharing!!!
@OcRefrig
@OcRefrig 4 жыл бұрын
Good vid ! i Like the Logic behind that thinking. Well , this Old Dog just Learned a New Trick ! Thanks for that hackfree. 39 years in this trade and still Learning new tricks. aint this trade Grand !
@SandySeeley
@SandySeeley 3 жыл бұрын
Thank you for this! Been doing it wrong. Going to readjust it tomorrow!
@hugoreyes1051
@hugoreyes1051 4 жыл бұрын
Thankyou, for showing us!
@kevintdickson
@kevintdickson 3 жыл бұрын
Great insight, thanks
@patmurphy2472
@patmurphy2472 4 жыл бұрын
Nice tip.
@marileelockwood5408
@marileelockwood5408 3 жыл бұрын
Thankyou so much!!!😄
@apctech1
@apctech1 4 жыл бұрын
we dont see those in my state but they must be fun to keep clean
@hackfreehvac
@hackfreehvac 4 жыл бұрын
Making sure the bleed is working can make the difference of whether it turns into a calcium brick or not. Those cell deck pads weigh nothing when new but are as heavy as bricks after they load up. We cut them down to cinder block sized pieces with a Sawzall and they weigh like a cinder block.
@apctech1
@apctech1 4 жыл бұрын
@@hackfreehvac do they actually work better then AC
@hackfreehvac
@hackfreehvac 4 жыл бұрын
@@apctech1 No. The performance is limited to the amount of moisture already in the air. So high humid days mean poor cooling performance. Generally you'll be lucky to get 80 degrees from one once it gets hot and with some humidity. Even warmer with aspen pad types. There are some "indirect evaporative coolers" like Coloado Coolers that do some tricks to drop the dew point further down their water heat exchangers and they get 55 degree supply air temps.
@sageparsely2365
@sageparsely2365 3 жыл бұрын
The same principle would stand for any foat, correct? I'm thinking the same as a toilet tank float. You don't want it partially submerged. Right?
@vitron01
@vitron01 2 жыл бұрын
So I have a similar cooler on my roof at home. But have never seen the little black cover that you put over the valve itself. What is it called, and where can I find some. I go through 1 or 2 floats every summer here in Las Vegas, NV Thanks ZERO702
@hackfreehvac
@hackfreehvac 2 жыл бұрын
Those are just splash guards to keep stray streams of water from squirting into the fan or out of the sump
@vitron01
@vitron01 2 жыл бұрын
@@hackfreehvac So can I buy them most anywhere, or online? I've been running swampers for decades now but have never seen them sold with the other regular yearly maintenance parts? I go through 2 floats a summer and I'm lucky if my main pump gets me two seasons worth. My purge pump has hung in there for the most part. I think instead of Lowes and Home Depot's Chinese pumps, I'm going to see what Grainger has this summer. What kind of pump do you recommend on a master cool 220V Thanks for your time, ZERO702
@hackfreehvac
@hackfreehvac 2 жыл бұрын
@@vitron01 yeah like Ace Hardware etc should have them in the cooler section They might be smaller than these larger commercial ones
@the1gonzo1
@the1gonzo1 2 жыл бұрын
Thank you
@danielavaldez1413
@danielavaldez1413 3 жыл бұрын
I can not find an answe. Whst if the thing connected to float and unit is broken.
@Heavy_metal_rulez
@Heavy_metal_rulez 4 жыл бұрын
Looks like i have been doing it wrong all of these years. Im gonna start doing it this way for now on
@sageparsely2365
@sageparsely2365 3 жыл бұрын
You're doing it wrong ! 😜😄
@omarbernal2408
@omarbernal2408 3 жыл бұрын
I put it on a new one. Installed it to existing valves But the little patch inside to small... Guess wont block the water once it raises up. Wich is the whole point of the floater. Now gotta buy another one.
@Arizona-.Native.Joshua
@Arizona-.Native.Joshua 3 жыл бұрын
If the water is low the float will open the water on until the float is level then it will stop
@hackfreehvac
@hackfreehvac 3 жыл бұрын
Usually the valve and float is sold together. It's the valve part that fails the most often. The water trickling through with the minerals is like rubbing sandpaper against the seal.
@omarbernal2408
@omarbernal2408 3 жыл бұрын
@@hackfreehvac Yea bought it and broke it to make it fit into existing valve that i could not take out because its really hard to take out, Almoust seems welded than screwed. This was a "heavy duty" metal one. New one is plastic.
@hackfreehvac
@hackfreehvac 3 жыл бұрын
@@omarbernal2408 The old valves can be tough to take apart. You learn ways after a while. Such as digging out that fiber washed with a small screwdriver first to loosen it up. Another common thing you learn to do is to buy a new float mount bracket when you buy a float valve and you remove the entire bracket with the old valve on it and toss it.
@burtburtist
@burtburtist 3 ай бұрын
these float valves make me feel stupid lol, theyre so easy to break while adjusting in tank, im going to try again with an offset but i still cant really figure out why their actual valve is just a little rubber pad attached to a thin sheet piece of brass when if it came to a point like a cone it would be much more robust, i've already gone through 2 of these, i need to stay in my lane and never touch water, il stick to wires.
@hackfreehvac
@hackfreehvac 3 ай бұрын
If they used a water sensor and a solenoid valve to open when the water gets pretty low then stop at a full mark therefore running the valve full open and full closed with reduced cycle rate, they would last for years! I think they do sell them but people won't pay for them. The savings in labor would cover the cost.
@sketchartist1964
@sketchartist1964 Жыл бұрын
My cooler is just like this one. My water line on the roof to the cooler sprung a leak, how do I shut it off?
@hackfreehvac
@hackfreehvac Жыл бұрын
Are you speaking of a residential house or a commercial building? This is a large unit on a commercial building and the water shut off valves are right where the water stubs out from the roof. If you have are speeking about a cooler at a home then the water shut off could be anywhere depending on who installed it. Usually where ever they tapped the water line.
@sketchartist1964
@sketchartist1964 Жыл бұрын
@@hackfreehvac Thanks, yea it's a house.
@hackfreehvac
@hackfreehvac Жыл бұрын
@@sketchartist1964 Usually the shut off is where they connected the water lone. Outside at the main water, near a hose bib, at the water heater, etc.
@geemontoya1712
@geemontoya1712 4 ай бұрын
Follow the water line and turn the knob off
@danielavaldez1413
@danielavaldez1413 3 жыл бұрын
On 2:44 where that hole that is a quarter size. Mine fell off. Like broken completely. It is not a commercial one just a home unit. Can anyone please tell me if i would be able to just use it without that. I can take pictures if as anyone is willing to help.
@hackfreehvac
@hackfreehvac 3 жыл бұрын
Are you talking about where the float arm connects to the float valve? The float valve assembly is generally sold as one piece. ACE HARDWARE etc will sell them. It is a normal wear and tear device. Lucky to last one year sometimes. LOL
@rb3263
@rb3263 4 жыл бұрын
Dope
@anthonygonzalez7488
@anthonygonzalez7488 3 жыл бұрын
Odd video. If you have broken the device of your subject matter, then how can you show a demonstration of the proper way to adjust such device ?
@hackfreehvac
@hackfreehvac 3 жыл бұрын
I'm not sure what you're asking? The old float was being replaced regardless because the valve seat was worn (typical). The context of the video were examples of buoyancy and lever action as it pertains to float valves. As for servicing coolers with old valves, I'd they are so corroded that you can't touch them to adjust, then they are clearly worn out.
@jeromesena5967
@jeromesena5967 3 жыл бұрын
You need to maintenance that evaporative cooler better than what you have been. The water looks filthy probably stinks and you haven't treated the base of the swamp cooler.
@hackfreehvac
@hackfreehvac 3 жыл бұрын
This is a "How to set a cooler float" video. Not a "how to clean it". Also I don't believe I said that I've been doing the maintenance. The techs clean them at the end of the summer. But fat chance they are going to make them clean enough to eat off of. Especially when these are football field sized rooftops and they are given dozens to do at a time. When you get a call to fix a broken float and it's 110 degrees and a 500 foot walk to the cooler, you're not there to drain, scrub and coat the cooler. Just get the bastard to work again. Must be a residential DIY thinking techs got 3 hours to clean a cooler 😆
@geemontoya1712
@geemontoya1712 4 ай бұрын
Poor techs, try roofing, nuff said.
@vitron01
@vitron01 2 жыл бұрын
IDIOTS DO THE SAME ON TOILETS TOO I BET. I'M JUST A COMMERCIAL ELECTRICIAN. IDK
@gerry.shafer6101
@gerry.shafer6101 Жыл бұрын
U. BENT. THAT. ARM. AT. THE. BOTTOM. SO. U. HAVE. LESS. WATER. IN. THE. PAN. !! THATS. GOOD. AS. THE. WATER. WILL. BE. COLDER. U. SHOULD. SHOW. HOW. U. BENT. THAT. !! IM. GOING. TO. TRY. AND. BEND. MINE. THE. SAME. MAY. NEED. A. VICE. AS. THEY. COME. PRETTY. STRAIGHT. WITH. LITTLE. BEND. !!
@hackfreehvac
@hackfreehvac Жыл бұрын
The intended adjustment is way up at the pivot point on the valve via a screw. The problem is the angle down into the water causes the water level to have to rise up vertically enough to finally give any buoyancy too lift the arm with enough leverage. So I bend the arm to keep the float paddle horizontal to the water so that the water immediately conta to the entire bottom and has better bouyancy. Then the water level has to rise less to have the leverage to close the valve and likewise does not have to drop as far to open the valve quicker for fill. There is nothing to show really. The arm simply bent by hand to get the paddle parallel to the water and the fine adjustment for water depth is still adjusted as always.
@isaacsharp9026
@isaacsharp9026 Жыл бұрын
Its more progressive 😂
Secrets to Fixing Your Swamp Cooler
12:08
Mr Fred’s DIY Garage School
Рет қаралды 16 М.
SWAMP COOLER LEAK!!! + ICE TRICK (VLOG)
9:11
Seth James DeMoor
Рет қаралды 56 М.
娜美这是在浪费食物 #路飞#海贼王
00:20
路飞与唐舞桐
Рет қаралды 3,9 МЛН
What will he say ? 😱 #smarthome #cleaning #homecleaning #gadgets
01:00
Ik Heb Aardbeien Gemaakt Van Kip🍓🐔😋
00:41
Cool Tool SHORTS Netherlands
Рет қаралды 9 МЛН
Bonaire Swamp Cooler Water Float Valve Replacement
6:24
Your Streaming TV
Рет қаралды 29 М.
Swamp cooler pump replacement
5:45
NGHC
Рет қаралды 6 М.
Adjusting a Swamp Cooler float
6:04
The Crappy Carpenter
Рет қаралды 4 М.
Swamp/Evaporative cooler rebuild and start up for the summer.
10:55
ulitepilot aka Zombie Dave
Рет қаралды 21 М.
How To Repalce A Swamp Cooler Float
2:55
Your Streaming TV
Рет қаралды 75 М.
HVAC 166  Evaporative cooler how it works inside
19:09
Love2HVAC with Ty Branaman
Рет қаралды 35 М.
娜美这是在浪费食物 #路飞#海贼王
00:20
路飞与唐舞桐
Рет қаралды 3,9 МЛН