How to find a refrigerant leak in an air conditioner?

  Рет қаралды 225,066

Taddy Digest

Taddy Digest

Жыл бұрын

Join this channel to get access to perks:
/ @taddydigest
Wanna Learn more about hvac? Check out my hvac tips for technicians playlist.
• HVAC Tips for Technicians
Diversitech 800-002 Pro-2000 Leak Detector Spray - 1 Quart
amzn.to/3SI2SjI
Fieldpiece DR58 - Heated Diode Refrigerant Leak Detector
amzn.to/3y1KvP0
‪@DiversiTechCorp‬

Пікірлер: 300
@francom6230
@francom6230 5 күн бұрын
Many techs don't bother to actually find/fix the leak.. My friend Matt is the best at finding leaks.. even w/o dye,, feel for oil is a very good start.
@dalemihocik4732
@dalemihocik4732 Жыл бұрын
I like how you gave the customer options and didn't judge him on what he chose. I need to find an independent contractor because these company guys are driven to force service contracts and high end equipment down your throat at every given opportunity. Maybe I'll get lucky and find a guy like you.
@TaddyDigest
@TaddyDigest Жыл бұрын
Thank you yeah I just want my customer to be happy. I offer my advice and it's always just what I would do if I had their situation. I agree with you A lot of companies are just driven to make a sale and they don't care about the customer
@ronniehvac653
@ronniehvac653 Жыл бұрын
Hey Dale, I hear ya brother. I work for a company in the Hudson valley in NY. A lot of competition but countless number of times I'm servicing equipment with the competition's sticker on it. I always try to be as transparent as possible. I've learned that once you lose a customers trust, you've lost their business.
@Minimarshi
@Minimarshi Жыл бұрын
@@TaddyDigest I have the same issue, lost about a pound in a year. Have had 3 companies come out only to not pinpoint the leak, guessing it's probably on the back of the evaporator coil like this one. What did you recommend replacing, the coil or the whole handler?
@ronlarson6530
@ronlarson6530 Күн бұрын
Inficon ❤ I have used them for detecting vacuum leaks with heium for decades 😊 They make high quality instruments!
@ParabellumX
@ParabellumX Жыл бұрын
I use Fieldpiece's DR82 Infrared Leak Detector. It's freakin awesome! I do a 3-hits-it's-a-leak check, but I really don't have to; if it goes off, there's a leak (or I accidentally bumped the tip on something). Probably the greatest feature about this particular leak detector is the fact that it gives you three signs to let you know that there is a leak: there's the audible sound, the flashing of the tip, and a vibration throughout the leak detector itself. That's awesome! So it doesn't matter if you're blind, deaf, or dumb, you will find a leak if there is one!
@garygullikson6349
@garygullikson6349 Ай бұрын
AC guy found our 2008 out of warranty system was out of old type refrigerant. Checked outside unit, no leaks. Plans to check for leaks on inside unit, weld leak if doable, install "stop leak", and new type refrigerant. If systems loses refrigerant, he will deduct charges from total price for new inside unit (or replacement coil) . I was told that old type refrigerant is very expensive, new type is about 95% effective in cooling.
@shk2564
@shk2564 Жыл бұрын
“Three dead mice…three dead mice…see how they spin around the blower motor.” 🎶 😂
@robertchavez5137
@robertchavez5137 15 күн бұрын
About to get the popcorn. Wondering where this leak is!
@dioramaworldcustoms
@dioramaworldcustoms 11 ай бұрын
You are the best teacher on here! I’ve been thinking about going to school for my H-Vac license. Texas is so hot during the summers! I liked & subscribed!
@TaddyDigest
@TaddyDigest 11 ай бұрын
Thank you so much
@seadogharris2102
@seadogharris2102 Жыл бұрын
Great information. Just ordered Webb Coil Cleaner from Lowes.
@chadriddle3517
@chadriddle3517 Жыл бұрын
Excellent information in this video! Man I appreciate that for people like me that watches KZfaq to learn for homeowner use . Subscribed
@TaddyDigest
@TaddyDigest Жыл бұрын
Glad to hear the information was helpful thank you so much for watching
@robsimmons7650
@robsimmons7650 2 ай бұрын
H10Pro by Bacharach for leak detectors. Always check the service port caps with electronic before getting the gauges out of the truck and before touching the caps.
@OcRefrig
@OcRefrig Жыл бұрын
Good video ! But Here’s some tips from a Guy doing it for 42 Years. 1) if System has at least 1lb of liquid refrigerant in it. ( 410a systems ) Just pull the disconnect. Wait 5 min for system to equalize. Equalized pressures on 410a system at 60 degrees outside with liquid in it will be 170Psig. Higher if its hotter out. See pt chart. 170 is plenty to find a leak with a H10-leak detector or any decent leak detector. 2) Most Leaks are in evaps. 75% of the time. Start there first. 3) Rarely have i needed to pressure test over 150 psi to find a Leak with a Ge H10 leak detector.
@stevenross9271
@stevenross9271 Жыл бұрын
I have been doing refrigeration and air conditioning for over 45 years. I am partial to my Inficon select. I spent 30 of those years behind a desk as a service manager. I diagnosed techs problems over the phone. Always look for a leak if the unit is low. To just add gas is not performing your job.
@stevenross9271
@stevenross9271 Жыл бұрын
The G.E. H-10 with a cord is without a doubt the best leak detector you can get your hands on.
@eethridge4065
@eethridge4065 Ай бұрын
That rare time is that dang ice machine that passes the pressure test twice and has a fan switch that doesn't leak until it hits 275 psi high side....ugh
@benb3928
@benb3928 10 ай бұрын
"I will keep you cool if you let me!" ..clever tag line earned my sub.
@TaddyDigest
@TaddyDigest 10 ай бұрын
Thank you brother
@RollingThunder808
@RollingThunder808 11 ай бұрын
CPS leak detector is the best. We had a leak on the R114 plant and it was like chasing a ghost. We put soap on the area and it took about five minutes and the bubbles were so small it looked like shaving cream. That's how small the leak was.
@srobeck77
@srobeck77 Жыл бұрын
The common census for leak checking is to raise the pressure no higher than the highest rating on the low side. Its to avoid damaging the internals of the system.
@rwood1995
@rwood1995 11 ай бұрын
That makes it hard to sell them those items though dont it?? 🤑 JK LOL
@g-lato9791
@g-lato9791 3 ай бұрын
Does that also apply to the heat pump tho , since it is reversible and they both use the high pressure
@srobeck77
@srobeck77 3 ай бұрын
@@g-lato9791 incorrect. This is a lack of understanding right here. In a heat pump, the high side just alternates between the evaporator and condenser but is still same high side pressure reading to go off and you should not exceed that number.
@terrimcglothin2230
@terrimcglothin2230 2 ай бұрын
If I can't find a residential leak with an electronic & sonic leak detector within 30-40 minutes , I like to add fluorescent dye while I add refrigerant. This provides comfort cooling until we can reschedule the leak inspection, and let the dye have time to show up After 35 yrs in residential, if I can't find the leak in a half hour or so on most units, then I know it is going to be a tricky one. The uv dye really helps to pinpoint the problem. Owner operators.. Remember, dye is a tool to help you. You dont need to make a fortune on the dye. Be fair to your customers. You will earn a fair profit during the repair or replacement of the coil.
@TaddyDigest
@TaddyDigest 2 ай бұрын
Excellent advice 👍
@GApawpawandnana
@GApawpawandnana Ай бұрын
I wish I could get y’all’s service in NW Georgia. I was told you can’t fix a leak. You have to have a new unit. I get refrigerant added twice a season or use window units.
@carolync9408
@carolync9408 Ай бұрын
I was told leaks could t be fixed period! Dye was added no leak found I was told it must be the unit leaking and that can’t be fixed. The Heil United is 2 years old.
@biometal770
@biometal770 11 күн бұрын
@@GApawpawandnana that is false. In car ac systems, refrigerant leaks are diagnosed with fluorescent dye, electronic leak detector, soapy water, and other methods. All these methods can be used for residential systems as well
@caru3257
@caru3257 3 ай бұрын
Three dead mice would be a great name for rock band.
@godfreyappliance5585
@godfreyappliance5585 11 ай бұрын
I use accu trak ultrasonic. I have used it for a little over 10 years. Works great. It is not a sniffer. Sniffer will go off with anything that burns.
@jefflemberg645
@jefflemberg645 Жыл бұрын
How many clowns just fill up your freon and try to sell you a new unit when it all leaks out again?
@HippieMosquitoQuatro
@HippieMosquitoQuatro 6 ай бұрын
Yes.
@waynegent2263
@waynegent2263 5 ай бұрын
My boss gets upset at my sales bc their so low. I always find the leak and make sure customers get repairs pricing and unit price depending on warranty. He hates it but keeps up withit
@leestebbins5051
@leestebbins5051 2 ай бұрын
Freon? Old timer.
@AfiOyeTheNurse
@AfiOyeTheNurse Ай бұрын
Yeeeees! That's why I'm watching this video because we got new unit last year, and the man done put freon in it twice and it's still messed up. He didn't even tell us we had a leak.
@southside6924
@southside6924 Ай бұрын
@@AfiOyeTheNurseoh lord that’s not good at all
@thomasglessner6067
@thomasglessner6067 7 ай бұрын
Great video. Thank for sharing your knowledge and skills. Im subscribed.
@martinheatingcoolingmartin4693
@martinheatingcoolingmartin4693 Ай бұрын
Excellent work! Thanks for a better understanding on the process. I love learning more and more about my trade.
@carolync9408
@carolync9408 Ай бұрын
And that makes for a great contractor, love to hear that. Some ppl are quick to just make money vs actual saving customers a few dollars.
@carolync9408
@carolync9408 Ай бұрын
I have a question does refrigerant have to be in the unit to use the nitrogen?
@carolync9408
@carolync9408 Ай бұрын
Watching this video tells me why most are saying get a new unit. SMH! Gratitude to you sir for loving and perfect your skills. So appreciated.
@maryschultz645
@maryschultz645 2 ай бұрын
thanks for the vid Tad !
@dyershvac5884
@dyershvac5884 Жыл бұрын
Great job Tadd!
@TaddyDigest
@TaddyDigest Жыл бұрын
Thank you my friend
@RocisBigBroSavage
@RocisBigBroSavage Жыл бұрын
Great quality content. Keep it coming!
@TaddyDigest
@TaddyDigest Жыл бұрын
More to come!
@TonyRodriguez-ok2ix
@TonyRodriguez-ok2ix Ай бұрын
when it leaks fast condenser side. when it leaks slow evaporator side.but it all depends on the size of the hole.
@jmead6121
@jmead6121 4 күн бұрын
wow infocon ive had one but long since replaced by H 10 & cant remember the other brand but its called the leak seeker & 500 max nitro id guess ....i usually do 350 max 145 on old R 22 coils w/ trace Refrigerant with bird dog 1 st then bubbles to pin point ..Thanks as always
@peterman8058
@peterman8058 Ай бұрын
Nice work!
@calabamian
@calabamian 11 ай бұрын
Is there anyone cool and honest like you in San Diego?
@TaddyDigest
@TaddyDigest 11 ай бұрын
not sure my friend
@ronniehvac653
@ronniehvac653 Жыл бұрын
Hey, Tad. I use the yellow jacket sniffer. But I also use the Superior Accu Track ultrasonic leak detector. You could have heard those mice fart before they died.
@TaddyDigest
@TaddyDigest Жыл бұрын
Very cool ronnie
@buddybeachboy
@buddybeachboy Ай бұрын
Great video .
@NytefogNJ
@NytefogNJ Жыл бұрын
I use the Testo 316-4 for R410a systems and the Testo 316-3 for R22, but the Inficon Tek Mate is also great option for r-22 systems ( I also have a Inficon tek mate). The Testo 316-4 is probably the most sensitive electronic leak detector I’ve used for r410a.. and I’ve can’t even start to tell you how many electronic leak detectors bought then sold trying to find a good model. Do a Search for NathanHVAC electronic leak detector sensitivity test. He has tested most of the leak detectors I’ve purchased. He has made spreadsheet of the leak detectors and their sensitivity for R22 and R410a refrigerants. I’m trying out Ultrasonic refrigerant leak detector this spring/summer to see if that can help pin point small leak’s faster.
@MrDeviousdom
@MrDeviousdom Жыл бұрын
I've used several ultrasonic leak detectors and found that they were useless when trying to find small leaks. See what the return policy is on the tool just in case. A good way to test it is by using a calibration vial.
@renaissanceman5847
@renaissanceman5847 Жыл бұрын
I feel for the home owner... but the best thing to do is have some window units ready... 3 units are more than enough to keep you comfortable enough when SHTF with the main AC. they cost $150 each. Then with an older system, especially one approaching 20 years... just get the full install. else with and older system you may find yourself spending more money over the long term vs a new system plus the inconvenience (they always break on a Friday afternoon ) constantly fixing issues as its dies. At least you can get a warranty on installation and equipment that will cover you for a year or more. I also recommend insisting they inject UV dye into the system upon installation or even service. that way its easier to find the leak should one creep up at any point due to installation errors or aging.
@Byepolarchaos
@Byepolarchaos Күн бұрын
I was never offered the opportunity to do a leak test quite frankly, wasn’t even aware of that possibility. Pumped 5 pounds of gas Into the unit and the unit failed within six months
@hectordaniel30
@hectordaniel30 Ай бұрын
I joined. Like your videos very thorough .
@TaddyDigest
@TaddyDigest Ай бұрын
Thank you so much for joining. Here is my email tadfuller1@gmail.com
@sonnguyen-ve7gn
@sonnguyen-ve7gn 9 ай бұрын
Great video !
@TaddyDigest
@TaddyDigest 9 ай бұрын
Thanks!
@thecurious6721
@thecurious6721 Жыл бұрын
Thanks for the tip 👍
@TaddyDigest
@TaddyDigest Жыл бұрын
Any time!
@ricardoa4322
@ricardoa4322 11 ай бұрын
I use the yellow jacket infrared leak detector works great
@danceaway2nite
@danceaway2nite Жыл бұрын
Bow tie.... mustache?!!! 😂 too cute!!! 😊😊
@kylehennen
@kylehennen Жыл бұрын
My man’s got a bow tie on his lip!
@michaelfesta9289
@michaelfesta9289 2 ай бұрын
Great video very Informative And very easy for Me the weekend warrior to follow
@TaddyDigest
@TaddyDigest 2 ай бұрын
Great to hear!
@stansummers6259
@stansummers6259 Жыл бұрын
Great video buddy
@TaddyDigest
@TaddyDigest Жыл бұрын
Thank you my friend
@kabsatofficial
@kabsatofficial 8 ай бұрын
Thank you ted
@jmead6121
@jmead6121 4 күн бұрын
costs to do an full fledged leak search vary depends how far we have to go to isolate Coil from line set to outdoor unit but can get quite costly quick ...depends but its the only way to find , fix or replace the correct component
@joelbell9082
@joelbell9082 Жыл бұрын
If it's a large leak in an air conditioning system it's usually on the high side of the system To check the condenser hook up your high side and low tide gauges turn off the power remove the condenser fan motor from the top of the unit Turn the unit power back on checking the high side pressure with condenser fan motor not working the high side pressure will increase to a point where you might be able to locate the week much easier Do not exceed momentarily 400 PSI Turn off the power check With an electronic leak detector You can also use an UltraViolet leak detector After injecting and allowing the fluid to circulate throughout the system One other method is using nitrogen to build up the pressure to see if we could find a slow leak using a Ultra Violet leak detector after injected fluid All these methods MUST only be performed by specially trained air conditioning service technicians with years of experience Absolutely no homeowners should ever attempt these leak detection procedures which could cause permanent bodily injury or possible death Leave it to the professionals
@dgair5635
@dgair5635 10 ай бұрын
I am just doing some research to learn more. My techs are taking 4 hours to do a leak check after putting dye in the week before :)
@TaddyDigest
@TaddyDigest 10 ай бұрын
You can do it!
@southside6924
@southside6924 Ай бұрын
I being hearing good things about the inferred leak detector
@TonyRodriguez-ok2ix
@TonyRodriguez-ok2ix Ай бұрын
safety first. safety meetings every 10 business days
@thecreaturesdancedlikeus3922
@thecreaturesdancedlikeus3922 Ай бұрын
Another great, helpful video! Very nice 👍🏽, very mice 🐁
@TaddyDigest
@TaddyDigest Ай бұрын
Thank you very much!
@joshuaseaton7002
@joshuaseaton7002 Жыл бұрын
Hey Tad. What's the 1 to 98 countdown when the wind free units shut off after cooling?
@SteveM-426
@SteveM-426 Жыл бұрын
Dye is Best! Hands Down.
@MetalDetectingwithCZkidd
@MetalDetectingwithCZkidd Жыл бұрын
I would not recommend to anyone to go 500psi on a leak test. I, like Oc have been doing it a long time. Never pressure tested that high, even on the commercial side of things. Can get dangerous. Usually there are operating max pressures listed, I would not exceed those. There is a leak detector that works via sound. I had one of those as well, no matter how small the leak, it would sound like a hurricane in your ears. Nice vid.
@MrDeviousdom
@MrDeviousdom Жыл бұрын
500+ psi is where a 410a system is operating during the summer.
@MetalDetectingwithCZkidd
@MetalDetectingwithCZkidd Жыл бұрын
@@MrDeviousdom where? If so, clean the coil. Maybe in AZ. Not in FL.
@MrDeviousdom
@MrDeviousdom Жыл бұрын
@@MetalDetectingwithCZkidd In hot areas. I don't understand the point of your comment.
@epeterson711
@epeterson711 Жыл бұрын
Agreed! I have never heard of anyone EVER going to 500 psi!
@MrDeviousdom
@MrDeviousdom Жыл бұрын
@@epeterson711 well, I'm in AZ and it does all the time on rooftop units.
@AfiOyeTheNurse
@AfiOyeTheNurse Ай бұрын
Great video! I feel like people are scheming us and we live in Florida and our AC unit broke 3 times in the last year and we got it new last year. Weird
@TaddyDigest
@TaddyDigest Ай бұрын
It's hard to find Honest companies.
@sbnatomicrecords
@sbnatomicrecords 4 ай бұрын
Great info. Its a shame when you have guys add more freon and try to sell it to the customer knowing there is a leak. Smh
@johnharrisonschulz
@johnharrisonschulz Ай бұрын
500 PSI! The most I ever use is 300 psi for R410A and 150 psi for R22.
@RodneyThomas-qk8ce
@RodneyThomas-qk8ce Ай бұрын
Put your finger in there and see if theres some oil in there lmao classic 😅
@TheStantony
@TheStantony 8 ай бұрын
Hi. What are the resons if frequently happen leakage in condenser coil bends
@flint7777
@flint7777 Жыл бұрын
Good guy
@twolfe4295
@twolfe4295 Жыл бұрын
I use the same detector that you have and maybe it would have found the leak if you had used it.
@StevenSchoolAlchemy
@StevenSchoolAlchemy 11 ай бұрын
tell us about the stop leak additives.
@williambirt914
@williambirt914 23 күн бұрын
nice job tad, what do youcharge for a leak survey? also if a mouse works its way into the main blower squirrel cage it will sound like thunder in your duct work. simply remove and clear sailing.
@jonswisher8796
@jonswisher8796 Жыл бұрын
Most refrigerant leak detectors are incredibly sensitive. If you add any refrigerant you should always do a leak search. A basic leak search only takes 10-15 minutes to make sure you don’t have a good size leak. You don’t have to reclaim the gas and add nitrogen, the refrigerant is the gas you are looking for, and soap bubbles will also blow bubbles regardless if there is nitrogen, as long as there is pressure, don’t complicate it. You can’t give the customer the choice you are supposed to make as a trained technician when it’s such a simple move and avoids callbacks
@craigmarshall40
@craigmarshall40 Жыл бұрын
You have some good prices 😮
@alderoth01
@alderoth01 10 ай бұрын
What does it mean when the copper tubing, the one inside by the unit is warm to the touch, even the copper outside?
@user-cb4qd5fc1x
@user-cb4qd5fc1x 5 ай бұрын
😮 damn mans a pro
@tonyrandall6261
@tonyrandall6261 Жыл бұрын
Homeowner must have picked the platinum package, all that he took loose
@ericwilliams3407
@ericwilliams3407 8 ай бұрын
Taddy digest have you ever worked on farm equipment ac units I’m a mechanic an have been fighting with one of are equipments ac units I’ve done replaced an fixed where the leak was but it still is leaking down can you help us out
@williamlangley2044
@williamlangley2044 Жыл бұрын
I use dish soap water paint brushes and spray bottle, the leak detector gives me a general idea of the leak is.
@SovereignTroll
@SovereignTroll Жыл бұрын
I was told dish liquids (Dawn, Joy, etc) have lye in them and are corrosive to copper. Use an approved something if you don't want to pay for Big Blue etc.. Also chlorine sterilizer in condensate drains can attack furnace parts, use vinegar. Yet in reach-ins salad dressings and tomato products seem to eat coils. Who is right?
@user-ni2gf8gb9x
@user-ni2gf8gb9x 6 ай бұрын
I have had hit or miss with Electronics. It often goes off (all brands) if its near water in the pan , My Inficon goes off in light wind, My field piece just goes off because field piece. lol I almost always have better luck with Nitro and visual with soap bubbles.
@bruceelias2732
@bruceelias2732 Жыл бұрын
Thank you sir
@TaddyDigest
@TaddyDigest Жыл бұрын
You're welcome my friend
@gregstewart8654
@gregstewart8654 27 күн бұрын
When you have a fast leak it can be anywhere
@wow1022
@wow1022 5 ай бұрын
the 3 blind mice met their doom 😂
@StevenSchoolAlchemy
@StevenSchoolAlchemy 11 ай бұрын
look for oil on the tubing
@thejimmyrig
@thejimmyrig Жыл бұрын
I have a system from the mid 90s that hasnt run in a few years due to a leak and the refrigerant being super expensive. can a system like that be repaired and retrofitted? or would it be a wash in cost and better to just update?
@TaddyDigest
@TaddyDigest Жыл бұрын
I would probably upgrade
@craigmarshall40
@craigmarshall40 Жыл бұрын
H10 with the long probe
@kabsatofficial
@kabsatofficial 8 ай бұрын
500psiig...bro it will not break the system?
@9to5techs
@9to5techs 5 ай бұрын
is goodman heat pump GSZB404210A good for 2014 mobile home? in amarillo texas , r19 walls, r25 roof, r 30 floor, singal pan widows, 1216 sqft home. not air tight it has leaks. temps below 20 is like 8 days during heating seanson. i set termostat to 74 f and am using electric furnace 10 kwh for 108 hours a month. my electric rate is 0.097 kwh. the highest bill to have was 250 but that is from whole home usage. the goodman heat pump says it uses 2.9 kwh at 10 f with a COP of 2.08 and a 2.7 kwh with COP of 1.34 at -5 f. the price for the 5 ton a-coil and 3.5 heat pump is $4,876. i can get 30% off that price on rebate then it whould be $3,413.235 also, why whould tech go with mortex 5 ton a-coil and 3.5 heat pump. thanks for help.
@mustangmike6421
@mustangmike6421 6 ай бұрын
Can u do a video on superheat and subcooling, i know everyone tells people to only check subcooling, which if the system is installed properly the txv will hold the superheat to what it is suppose to be, but alot of the time it's not and superheat is usually way low.
@TaddyDigest
@TaddyDigest 6 ай бұрын
Type in the search bar super heat and sub cooling taddy digest. I did a video
@charlesbarkley1340
@charlesbarkley1340 Ай бұрын
If Steven crowder went into HVAC
@TynaGaines
@TynaGaines Ай бұрын
I'm having this same exact problem with my ac. Guy came out couple years ago and replaced the fan thing on the inside unit and said that would fix our problem. The system will not hold refrigerant. The line constantly freezes up. Definitely don't have $$ for a brand new system. Just need an honest trustworthy HVAC person to look at it and find the leak and tell me if it can be fixed. I'm in Virginia about 50 miles south of DC and 50 miles north of Richmond if you know of anyone in the area you can recommend.
@TaddyDigest
@TaddyDigest Ай бұрын
You could try some leak Sealant, and u v dye define the leak. Check out my video on leak sealant
@scottchristian71
@scottchristian71 Ай бұрын
What about the charred wires ?
@johnharrisonschulz
@johnharrisonschulz Ай бұрын
How much do you charge for a new evap coil? Here in California it's about $4,500 to replace an evap coil. If it's under warranty, it's about $2,000. Some hvac companies don't even check to see if it's under warranty. I've done two evap coils under warranty this year as a second opinion. The first two companies diagnosed bad evap coils and never checked to see if they were under warranty and quoted the customer about $4,500.
@TaddyDigest
@TaddyDigest Ай бұрын
wow that is bad That is way over priced
@salehm1723
@salehm1723 Ай бұрын
4500$!! That's crazy
@jerrysinclair423
@jerrysinclair423 4 ай бұрын
I’ve been using the same leak detector. Had to replace the battery and sensor. Other than that, it’s been a great detector! I’ve also use a H10. A little expensive but what isnt these days?!
@Byepolarchaos
@Byepolarchaos Күн бұрын
Can you pressurized it and put the smoke that they use to troubleshoot EVAP systems in cars?
@microgreensgrower3946
@microgreensgrower3946 9 ай бұрын
I'm at 2:20 in the video. Does this hold true for vehicle A/C's? (slow leaks = low pressure side and fast leaks =high pressure side? Thanks for the video!
@TaddyDigest
@TaddyDigest 9 ай бұрын
It really depends on the size of the area that's leaking
@VooDooWarrior01
@VooDooWarrior01 Жыл бұрын
Guys here tried to charge me over $1500 just to put $75 leak sealant in, so I got my 608 very and work on my system myself.
@tmblackwell4462
@tmblackwell4462 22 күн бұрын
The cost of these has become ridiculous. Older people on a budgeted income can not afford it. I know people that just suffer instead. It's deplorable. There should be a better and easier plug and play replacement by now.
@MonsurBakare
@MonsurBakare 2 ай бұрын
I joined
@zairuscanales
@zairuscanales Жыл бұрын
Hi! Thank you for this very informative video. I’m your new subscriber. Can I ask you a question regarding our AC unit? We just bought a house and unfortunately the AC is not cooling the room. The AC Unit is manufactured in 2006 (very old). And it’s definitely leaking refrigerant. The technician that checked the unit suggested to add refrigerant and check for leaks 1 or 2 weeks after. Is that okay? Or should I insist to find the leak first? I would really appreciate your advise. Thank you on everything that you do!
@TaddyDigest
@TaddyDigest Жыл бұрын
I would go ahead and let him add refrigerant because you need to know exactly how low it is Sometimes, it's hard to find the leak unless the refrigerant is significantly low, so it's good to know how low the refrigerant is before you schedule a leak check
@victork3397
@victork3397 Жыл бұрын
My company likes to use fluorescent trace dye for leak searches. And those require a return visit for Leah search after the dye has been circulating for a few weeks. Maybe that’s what the tech was referring to?
@lonestaryall2501
@lonestaryall2501 Жыл бұрын
Mice?? Yuck!! Great job on this system by you!!
@AzizAziz-tp6wd
@AzizAziz-tp6wd 2 ай бұрын
Good price
@markbrown6669
@markbrown6669 Ай бұрын
Great video, my question is if the condenser is grounding out at start up and burning out the fuse do I need to replace the condenser
@TaddyDigest
@TaddyDigest Ай бұрын
Not sure I would probably need more info
@markbrown6669
@markbrown6669 Ай бұрын
@@TaddyDigest I replace fuses in the electric box to the condenser turn on the system and it start sparking, I shut it off and I had the wiring check and check the fuses again and one of them was shorted out again. I'm not sure if the shortage is because the condenser needs to be replace or if there's something else I can do before replacing the condenser.
@chada472
@chada472 Жыл бұрын
If its a heat pump you have high pressure on the indoor coil when its heating right?
@TaddyDigest
@TaddyDigest Жыл бұрын
yes
@JC-sc9rx
@JC-sc9rx 2 ай бұрын
Tad is solid
@Byepolarchaos
@Byepolarchaos Күн бұрын
Why did you pressurized it and put the smoke that they use to troubleshoot EVAP systems in cars?
@dylanbeasley3093
@dylanbeasley3093 12 күн бұрын
I live in an apartment and they come fill it with Freon or whatever. Works great and lasts about 3 weeks then goes back to hot. After watching how hard it is to find I guarantee the maintenance crew is not going to do all that extra work. What should I do
@scottygenao2051
@scottygenao2051 Жыл бұрын
You only put the max on what the system tells you #tag . Especially if you putting nitro on the low side if low side says max250psi you put 250psi
@gabooda2380
@gabooda2380 11 ай бұрын
there is no way to only put nitrogen in the low side unless you would disconnect the coil. But yeah, the coil clearly states design pressure and R22 is very low pressure. I thought last one I saw was 150 on the R22 coil and 450 on 410a coil.
@JJLTACTICALSOUTIONS
@JJLTACTICALSOUTIONS 17 күн бұрын
I bought a brand new construction home and closed Jan 2022. Yesterday the A/C company who installed the central air came last night at 7pm and BAM, The tech says there is a small Freon leak but couldn’t find it. So he charged me $144 for the service call and $188.50 for 2.5lbs of Freon. He told me his office will call me back. Today they call me and she tells me it will cost me $257 for the leak check and probably more for Freon. So I’m like WTF! STRADA installed all of this and now I am on the hook for this leak and the house is only 2 years old and they installed all of this! WOW.
@TaddyDigest
@TaddyDigest 17 күн бұрын
that's a bummer 😕
@johnjmacejak
@johnjmacejak Жыл бұрын
Send the mice patrol to sniff out leaks …
@tomasavilla1175
@tomasavilla1175 Жыл бұрын
My unit froze up the lines are copper so I turned the unit off so it can thaw from the big ice block so would that problem be from having a leak in the system? Thanks in advance
@TaddyDigest
@TaddyDigest Жыл бұрын
Could be from leaking refrigerant. Could be from a dirty filter. Could be from low air flow. Just use a process of elimination to figure out.
@jonbeck6035
@jonbeck6035 Ай бұрын
Dont forget to pull the disconnect, ive sone that a couple times, best way to learn is to get zaped i guess or just pay attention haaha.
How to replace the AC units leaking condenser coil?
34:42
Taddy Digest
Рет қаралды 9 М.
Happy 4th of July 😂
00:12
Alyssa's Ways
Рет қаралды 68 МЛН
MISS CIRCLE STUDENTS BULLY ME!
00:12
Andreas Eskander
Рет қаралды 13 МЛН
Spot The Fake Animal For $10,000
00:40
MrBeast
Рет қаралды 153 МЛН
WHAT’S THAT?
00:27
Natan por Aí
Рет қаралды 13 МЛН
HOW TO LEAK TEST AN AC SYSTEM WITH NITROGEN PRESSURE
6:38
Alex The Handyman
Рет қаралды 4,3 М.
The Top 7 Things AC Companies Don't Want You To Know How To Do!
17:29
Leak Search Tips From Bert
17:50
HVAC School
Рет қаралды 68 М.
No AC.  Capacitor replacement and coil cleaning
14:44
HVAC Legend
Рет қаралды 2,8 М.
Fix AC leaks with this ultimate sealant! Easy and effective!
14:09
Taddy Digest
Рет қаралды 30 М.
Top 5 Things AC Companies Don't Want You To Know How To Do!
12:40
How To Home
Рет қаралды 2,2 МЛН
Low Refrigerant? Freon Leak? Check This First!
7:02
Sam
Рет қаралды 428 М.
Testing The Burn Ability Of Insulation In Wall
19:45
post 10
Рет қаралды 2,6 МЛН
STOP Replacing Your AC Unit TOO Soon!!!
6:27
Atlas AC
Рет қаралды 271 М.
Happy 4th of July 😂
00:12
Alyssa's Ways
Рет қаралды 68 МЛН