HVAC Service Call: Smoke in Store.

  Рет қаралды 5,563

HughesMan HVAC

HughesMan HVAC

5 ай бұрын

HVAC Service Call: Smoke in Store. This situation could have ended badly!
Hit me up at hughesmanhvac@gmail.com
Check out the Misfits of HVAC Podcast
/ @misfitsofhvac
misfitsofhvac@gmail.com

Пікірлер: 118
@jamienoel
@jamienoel 5 ай бұрын
I don't usually rag on other companies, but this is an exception and there's no excuse for it. I'd make it known in the write-up that the previous company bypassed the safety.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
I mentioned it for sure
@MikeB9771
@MikeB9771 5 ай бұрын
That unit has been hacked in every bad way, lucky the building didnt burn down. Total hackery.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Agree 100%
@jrh86
@jrh86 5 ай бұрын
I've never seen an upside down limit switch before 😂 barking mad ! Immediately dangerous.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Definitely 👍
@jasonjohnsonHVAC
@jasonjohnsonHVAC 5 ай бұрын
Good lord....safeties is 100% non negotiable for bypassing....i dont care how cold it is...never gonna happen....that is a disaster waiting to happen.....nice job Ryan
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Thanks Jason, thanks for watching man!
@BartlettTFD
@BartlettTFD 5 ай бұрын
I think it might be necessary to have the owner pull the service history on this unit. The company that performed this “work” needs to be held accountable for it. Some city inspector’s office should be notified if appropriate. That company should be fined and told that further violations will cause them to lose their business license. This is really a dangerous situation.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Extremely dangerous, totally agree 👍
@subcoolHVAC
@subcoolHVAC 5 ай бұрын
Good job Ryan, need to issue a BOLO for the Hack installer and the vandal who worked on those units.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@nonamesplease8228
@nonamesplease8228 5 ай бұрын
Who in the heck would bypass a safety. Then walk away and say "it will be alright", No excuse
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@topher8634
@topher8634 5 ай бұрын
Good thing you got video. Something tells me that there will be more to this. Like who worked on it previously.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
I think so too, thanks for watching
@user-qd3pi5ji7q
@user-qd3pi5ji7q 5 ай бұрын
This customer probably didn't call a different company today...
@HVACGUY
@HVACGUY 5 ай бұрын
Dang. That was dangerous
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Yes
@topher8634
@topher8634 5 ай бұрын
Might want to see if a wiring harness is available. If not, I'd say they need to replace it. I mean blower motor, possible heat exchanger failure, wiring damage and limits, that's half the unit.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Yeah, I submitted my report and will see what happens.
@jochemsluis8834
@jochemsluis8834 5 ай бұрын
Great job Ryan. You should never bypass any safety device unless for testing purposes. Leaving it bypassed leaves you with a whole hell of hurt. Safety is paramount and if it works is secondary.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@jenna_1221
@jenna_1221 5 ай бұрын
Wow. Can’t believe people sometimes 🤦🏼‍♀️
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@zack9912000
@zack9912000 5 ай бұрын
We always drill holes on the outside of the economizer, with no reason to run the wires like that. Much less bypassing limits
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Yep
@timmohney9737
@timmohney9737 5 ай бұрын
Scary that there are people out there that do stuff like this.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Yep 👍
@timmorrison4107
@timmorrison4107 5 ай бұрын
You could have cooked Thanksgiving dinner in that oven, wow everything needs reworked ,I’m surprised that drain pan didn’t melt away, I say new unit is an excellent option.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
🍗
@REWYRED
@REWYRED 5 ай бұрын
Hmmm... cooked motor, possible comprmised exchanger, comprimised wiring, comprimised condensate pan...... The entire thing baked itself.. If that was my unit it would be getting replaced and i would be going after whoever jumped the limit for replacement value plus.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@jani140
@jani140 5 ай бұрын
Please change all those wires. If they got that hot and not yet short, the plastics get very brital and isolation on "still good" wires will flake off soon.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
We quoted a new wiring harness
@MrJujubean
@MrJujubean 4 ай бұрын
Wow! I do not know how anyone could think it was a good idea to bypass a limit or any other safety.
@timothymcmahon1507
@timothymcmahon1507 5 ай бұрын
That’s just the new wireless limit switch
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
😆
@nastyhvacr
@nastyhvacr 5 ай бұрын
Good find! Last guy out has got some splaining to do.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Thanks for watching pat
@qomco
@qomco 5 ай бұрын
Thats why you dont bypass safeties...
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Exactly 👍
@10minutenewhampshirebreak77
@10minutenewhampshirebreak77 5 ай бұрын
Some tech, somewhere has some explaining to do!
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@gregbowman3598
@gregbowman3598 5 ай бұрын
Good one Ryan
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Thanks Greg
@ChingusTheOneAndOnly
@ChingusTheOneAndOnly 5 ай бұрын
What a find !
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@Farley445
@Farley445 5 ай бұрын
Bring back the melted filters to your shop and show your guys
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@oscalerup1129
@oscalerup1129 5 ай бұрын
That’s crazy, I had one job once we came behind the people that installed it, the one 3T RTU had a main limit bypass with a lil popper 😅. One other 10T had a hole in the condenser from a screw when they put on the hail guards. And they left the manual on top of the burners so when it fired it burned all of the wiring in that compartment
@Studentofhvac
@Studentofhvac 5 ай бұрын
Excellent. Interesting.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Many thanks!
@Paul-IE-Repairs
@Paul-IE-Repairs 5 ай бұрын
i would replace the wire, that insulation is compromised, the way it was creaking and cracking it exceeded its rating, 90C is 194F and a new insulation pad.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
I agree, I’ve filled out my report and also have the video. Appreciate the input, thanks!🙏
@danpresson
@danpresson 5 ай бұрын
Great job Ryan you are so thorough
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
I appreciate that!
@fshn76
@fshn76 5 ай бұрын
Good stuff Ryan. Just dealt with a unit that caught fire because someone had bypassed safeties all I had to do was go take pictures, total loss.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@Randylazz
@Randylazz 5 ай бұрын
What are the chances that the person who did all that managery is watching this video……..
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
🙏
@stevencossaboon3237
@stevencossaboon3237 5 ай бұрын
Nice work Ryan.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Thanks!
@brianliles4859
@brianliles4859 5 ай бұрын
Need to replace the unit
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@Zackrutledge1998
@Zackrutledge1998 5 ай бұрын
Nice work man. Good video👍🏻 You ever see anything like that before? I never have.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
I have not, thanks for watching
@joecorbin5158
@joecorbin5158 5 ай бұрын
Wowser….😳😳😳🔥
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@Brutis-1983
@Brutis-1983 5 ай бұрын
Looks like what we call Chuck in a Truck was there. Is was a service tech that trained when I started would call them. Plus filter change in December and did not cut the heat off. SMH . Good luck with that unit.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@vincentmcclelland9179
@vincentmcclelland9179 5 ай бұрын
I wonder if the whole unit needs to be condemned and replaced
@BryanGullickson
@BryanGullickson 5 ай бұрын
i know i would as it would be cheaper to replace than sit there and rewire and replace 90%of the unit
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@adamdnewman
@adamdnewman 5 ай бұрын
Surprised if any of the wires in the blower area are good insulation wise
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Probably not, they were hard and brittle.
@ryanisaacson118
@ryanisaacson118 5 ай бұрын
That ac you looked at with the plug pulled looked like a single circut system
@Farley445
@Farley445 5 ай бұрын
Start for fire burning smell on the wires check in see if there all connected you can’t not let the customer turn on the unit for safety reasons
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@steveblake8766
@steveblake8766 5 ай бұрын
121 thumbs uP
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@zekenzy6486
@zekenzy6486 5 ай бұрын
Great Video. Thank you for sharing. May I ask, what is the same and different between roll out switch and high limit switch ?
@mitchell8204
@mitchell8204 5 ай бұрын
Roll out switches are typically manual reset so they have a little button you need to push if it trips otherwise it will not close again by itself. High limits on the other hand tend to be automatic reset because they can be tripped by dirty filters, low airflow, etc but they will automatically reset and the unit will light back up. They should not trip during normal operation with clean filters, so if a unit is cycling on limit (running until it hits high limit then shuts off then lights up when limit recloses) there is usually a problem to fix somewhere.
@ryanmarlatt5726
@ryanmarlatt5726 5 ай бұрын
Those machines have fixed orifices. Pick yourself up a mini Guage so your not bringing up a whole hose.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
These units have txv’s
@bryann2633
@bryann2633 Ай бұрын
I think it got hot
@HughesManHVAC
@HughesManHVAC Ай бұрын
Me too, this unit has since been replaced
@MariosACandRefrigeration
@MariosACandRefrigeration 5 ай бұрын
I would be surprised ,if you do not have that limit in your van.
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Me too
@Farley445
@Farley445 5 ай бұрын
Owes inspect the job
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@acrservicesmathewr7565
@acrservicesmathewr7565 5 ай бұрын
What’s your opinion on the plastic pulleys on VFDs? Have been bypassing vfds due to unavailability and after bypassing we change the pulleys to steel since bypassing gives to much torque on startup and blows them apart. All this nonsense just to meet efficiency standards. Carrier going downhill
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Not a fan of the plastic pulleys either
@Kevin-wj4ed
@Kevin-wj4ed Ай бұрын
Replace the unit!!!!!!!!!
@HughesManHVAC
@HughesManHVAC Ай бұрын
We did
@roqueherrera8471
@roqueherrera8471 4 ай бұрын
Where u located?
@hvacblogger
@hvacblogger 5 ай бұрын
What did it smell like? 😆
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
😂
@MariosACandRefrigeration
@MariosACandRefrigeration 5 ай бұрын
2:00 no wires at the limit ?
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Yes someone bypassed it
@Farley445
@Farley445 5 ай бұрын
Them Raheem is much better
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@mmorrison6775
@mmorrison6775 5 ай бұрын
one question Why didnt the duct smoke shut down the ac?
@BryanGullickson
@BryanGullickson 5 ай бұрын
well if the disabled safety is any indication i'd have to assume either bypassed or not equipped also that fire department needs to go back to training as it took them 3 times of coming out to shut the unit down
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
It may have, the alarm company and fire department were both there before me and it was shut off by the time I showed up.
@jonathanhensel8929
@jonathanhensel8929 5 ай бұрын
That return smoke detector sampling tube is backwards.
@Farley445
@Farley445 5 ай бұрын
Are group will do the job and take off and not do the job the right way
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
👍
@user-hi4sh9um7x
@user-hi4sh9um7x 4 ай бұрын
Hi sir I am AC technician I need job u r have job i have experience 15 Saudi Arabia package unit your career train
@aa999xyz
@aa999xyz 5 ай бұрын
that is crazy!
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Thanks for watching
@Eddy63
@Eddy63 5 ай бұрын
Nice vid ... Thx
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
Thanks Eddy!
@ValDominator
@ValDominator 5 ай бұрын
i feel patronized
@HughesManHVAC
@HughesManHVAC 5 ай бұрын
?
HVAC Service Call: Tripped Smoke Detector
25:35
HughesMan HVAC
Рет қаралды 2,5 М.
"The Unit is making a loud noise" Part 2
13:33
HughesMan HVAC
Рет қаралды 1,8 М.
Хотите поиграть в такую?😄
00:16
МЯТНАЯ ФАНТА
Рет қаралды 2,3 МЛН
I Can't Believe We Did This...
00:38
Stokes Twins
Рет қаралды 108 МЛН
Who has won ?? 😀 #shortvideo #lizzyisaeva
00:24
Lizzy Isaeva
Рет қаралды 62 МЛН
Became invisible for one day!  #funny #wednesday #memes
00:25
Watch Me
Рет қаралды 58 МЛН
Unit is not Cooling, No AC Service Call
12:37
HughesMan HVAC
Рет қаралды 8 М.
Heat Geek Gives His Verdict on John’s Nightmare Heat Pump
35:46
Skill Builder
Рет қаралды 596 М.
No AC Service Call: Seagulls Attack!!
24:47
HughesMan HVAC
Рет қаралды 1,4 М.
Condenser replacement  Full Video
46:53
Nor-Cal Refrigeration & H.V.A.C
Рет қаралды 9 М.
I CAN'T BELIEVE THEY APPROVED THIS REPAIR
33:08
HVACR VIDEOS
Рет қаралды 229 М.
How Semiconductors Ruined East Germany
21:59
Asianometry
Рет қаралды 859 М.
Diagnosing a Locked Compressor 3D
10:02
HVAC School
Рет қаралды 47 М.
THE SYMPTOMS KEPT COMING
22:56
HVACR VIDEOS
Рет қаралды 58 М.
HVAC Calls on 6/14/23.  Changing Parts All Day!
15:58
Jeff’s HVAC Adventures
Рет қаралды 3,4 М.
Мужчина выростил лук в бутылке
0:56
Бимс
Рет қаралды 5 МЛН
Шашлык вкусный
0:57
Тони
Рет қаралды 2,2 МЛН
Крючок застрял в пальце - что делать? 😬
0:19
СПОРУ НЕТ!
Рет қаралды 3,2 МЛН
Qual você NÃO comeria?
0:14
F L U S C O M A N I A
Рет қаралды 29 МЛН