Installing Power Receptacle in our Metal Building! IT’s EASY!

  Рет қаралды 146,838

The Big Dan Show

The Big Dan Show

3 жыл бұрын

Пікірлер: 155
@michaeljavert4635
@michaeljavert4635 Жыл бұрын
Box is likely grounded, but better practice is to bond it to the ground. The steel armor and box are conductive, so it's grounded that way. Also the ground screw on receptacles also have continuity to the metal parts that screw the receptacle to the box, so there is a ground present even in the absence of a ground wire, in that case. But always use the ground wire and always bond it. Also use the top and bottom screws and a nut. The center screw can come loose, and also the pressure of plugging things in can weaken the outlet and wear it out prematurely.
@boltkane6827
@boltkane6827 9 ай бұрын
That's right. It is a code violation to install a receptacle to a cover the way it is is done in this video. NEC 406.5(C)
@nathangriffin9893
@nathangriffin9893 Жыл бұрын
I work at southwire mc plant where this cable is manufactured, you do not need that tool. Break the armoring and cut it with tin snips.
@michaelking42
@michaelking42 Жыл бұрын
Mate, I'm an electrician from Australia, living in Florida now. I find it crazy how difficult you yanks make electrical work. Living here, I almost have to relearn the entire trade. Thanks for the info, and also to the commentary above and below for their input. Makes it a little easier to figure this stuff out.
@bigbawls81
@bigbawls81 3 жыл бұрын
Very informative. Thanks for sharing Big Dan.
@heted1
@heted1 2 жыл бұрын
Great video. Thanks for sharing.
@randellwolfe4555
@randellwolfe4555 Жыл бұрын
Great video!, helped me as it was first time I have installed outlet in metal box
@randybarnes6661
@randybarnes6661 2 жыл бұрын
Thanks for sharing your knowledge buddy
@barryely1
@barryely1 Жыл бұрын
There isn't much knowledge here. This video should he deleted. Box isn't bonded and anti short bushing wasn't used.
@DJsHotRodFab
@DJsHotRodFab Жыл бұрын
Thank you for passing on your knowledge.
@barryely1
@barryely1 Жыл бұрын
There isn't much knowledge here. This video should he deleted. Box isn't bonded and anti short bushing wasn't used.
@DJsHotRodFab
@DJsHotRodFab Жыл бұрын
@@barryely1 you are correct. I used anti short bushings on my wiring and bonded all metal boxes
@kenjares6719
@kenjares6719 3 жыл бұрын
Thanks. I was looking for this info
@barryely1
@barryely1 Жыл бұрын
There isn't much knowledge here. This video should he deleted. Box isn't bonded and anti short bushing wasn't used. I hope you search for other videos showing the correct way of doing this.
@JohnThomas-lq5qp
@JohnThomas-lq5qp 2 жыл бұрын
Best practice is to use the two provided 6 - 32 screws to attach receptacles to metal cover rather then only the center screw that usually comes loose. After cutting Type AC or MC cable cut the sharp edge at a 45 degree angle then install red anti short bushing.
@ericarona8599
@ericarona8599 Жыл бұрын
Those screws aren't "provided"? It comes with only one in the center
@JohnThomas-lq5qp
@JohnThomas-lq5qp Жыл бұрын
The 1900 duplex receptacle covers that I purchased at several electrical supply houses always had two 6/32 screws along with hex nuts that often had flimsy lock washers attached or small piece of metal for 6/32 screws to screw into. I always had a plastic hinged storage box that contained an assortment of 6/32 & 8/32 screws, flat washers, hex nuts & lock washers.
@ericarona8599
@ericarona8599 Жыл бұрын
@@JohnThomas-lq5qp The cover plates had those break off tabs that I just used and worked great
@timothymcvay7286
@timothymcvay7286 3 жыл бұрын
Awesome video
@santiagodominguez2522
@santiagodominguez2522 3 жыл бұрын
Good job!!!
@manuelfuentes8741
@manuelfuentes8741 5 ай бұрын
Good job my friend
@mikeryan6277
@mikeryan6277 2 жыл бұрын
Box needs to be bonded as well as grounding the devise, and MC Cable needs to be secured.
@cannoncolossus2449
@cannoncolossus2449 2 жыл бұрын
Good comment. The ground should be bonded to the box and MC cable secured. The way presented in this video is potentially dangerous in the long term and will not pass inspection. Otherwise good video.
@tot2600hrs
@tot2600hrs 2 жыл бұрын
Forgot the anti chaffing grommet inside MC cable.
@sercansakizoglu967
@sercansakizoglu967 10 ай бұрын
exactly he didn't ground the box right ?
@NYTROeast
@NYTROeast Жыл бұрын
Should you be doing a jumper from the ground to the box so the box is grounded also since it is a metal box fastened to a metal building?
@fatherappel1792
@fatherappel1792 9 ай бұрын
I understand that the socket should be grounded to a metal outlet box. However, I've also read that you can never ground to the structure. So what should be done when using a metal box on a metal frame??
@domofishing9316
@domofishing9316 3 жыл бұрын
Notice the switch has bottom screw with yellow cap which would ground, but will it need a pigtail to the metal box to ensure proper grounding?
@bsmith8564
@bsmith8564 2 жыл бұрын
Yes on a raised cover.
@Steven-eh9qs
@Steven-eh9qs 3 жыл бұрын
I want more videos like this, hes seems very knowledgeable.
@JBarnes917
@JBarnes917 3 жыл бұрын
To bad he missed the box being bonded with the ground. This is an NEC code issue.
@CHEECHMUN
@CHEECHMUN 2 жыл бұрын
@@JBarnes917 So is an extra wire from the green screw, needed to go directly to metal box?
@JBarnes917
@JBarnes917 2 жыл бұрын
@@CHEECHMUN exactly, there is a spot in the back of the box that a ground screw is made to go in. You can get pre made pigtails that have the screw and a short green wire on it.
@CHEECHMUN
@CHEECHMUN 2 жыл бұрын
@@JBarnes917 Thank you!!!
@barryely1
@barryely1 Жыл бұрын
There isn't much knowledge here. This video should he deleted. Box isn't bonded and anti short bushing wasn't used.
@jimcole6423
@jimcole6423 2 жыл бұрын
You can use any jacketed conductors in a metal building that will be enclosed.
@LiloUkulele
@LiloUkulele 2 жыл бұрын
After my shop burned down I'm rebuilding with metal. Time to learn how to use shielded cable.
@JuanGarcia-nj9dk
@JuanGarcia-nj9dk 3 жыл бұрын
Whats was your investment this building including your concrete slab?
@Geno-j5g
@Geno-j5g 8 күн бұрын
Why didn’t you make hooks on the screws? 1st yr apprentice here I was always told to hook it this is so much easier!
@donaldlee6760
@donaldlee6760 2 жыл бұрын
At 1:04 - that cutting disk reminds me of a dremel cutting disk. I wonder if one has a dremel tool and they don't need to cut MC cable as part of their daily job, then one could just use their dremel?
@michaelking42
@michaelking42 Жыл бұрын
It would be very easy, but easy to cut the wire insulation as well.
@jesseexum1084
@jesseexum1084 4 ай бұрын
What size fittings are these and where did you get them?
@sercansakizoglu967
@sercansakizoglu967 10 ай бұрын
did he ground the box as well ?
@jamesbrenneman6841
@jamesbrenneman6841 3 жыл бұрын
Thanks great video
@gguerrero5503
@gguerrero5503 Жыл бұрын
What's the name of the fasteners used at 3:09 and following?
@imbradleymi
@imbradleymi 2 жыл бұрын
What box is this? I would like to use them for my shop.
@pentagonlandscaping
@pentagonlandscaping 2 жыл бұрын
1900 box with bracket
@jasnapon
@jasnapon 10 ай бұрын
That outlet should be grounded to the metal box as well
@brandonm922
@brandonm922 3 жыл бұрын
Box wasn’t grounded, receptacle wasn’t wrapped in electrical tape on the conductors and ground should go up but everything else was right to me. Great way of explaining!
@trustme7731
@trustme7731 2 жыл бұрын
Tape isn't necessary or required. There is no requirement for the position of the ground.
@ABflanagan523
@ABflanagan523 2 жыл бұрын
I agree that the box wasn’t making direct contact to the ground wire but the MC and metallic box is an equipment grounding conductor.
@JBarnes917
@JBarnes917 2 жыл бұрын
@@ABflanagan523 needs a ground pig tail period… THIS WILL FAIL A REAL INSPECTION.
@jcjammer1
@jcjammer1 2 жыл бұрын
No red bushing before connector?
@jimchang9394
@jimchang9394 2 жыл бұрын
It's bounded,The 20 A receptacle with the gold clip is a self-bonding mechanism.
@Trumptrain2024Vance
@Trumptrain2024Vance 3 жыл бұрын
What company did you use for the building!!!
@keithharrington8715
@keithharrington8715 2 жыл бұрын
As an electrical guy, I know that videos are there to inspire. Please do not take them as a step by step instruction as the code allows each building department (Jurisdiction) to adjust (interpret) the code as written. Many commentors pointed out several code misses: 210.8. Gfci for homes puts "out buildings" under garage requirements. 547. Is for "AGRICULTURAL BUILDINGS" with wiring method restrictions based on the animals kept there. Anyone can put a wire under a screw, but which screw is where the money is made. You can learn and do yourself, but calling the building inspectors or a local guy that just did that same job last week might get you a solution to a problem you never knew you had.
@OU8Aspark
@OU8Aspark 2 жыл бұрын
Can you tie multiple outlets together?
@jimcole6423
@jimcole6423 2 жыл бұрын
Yes!
@garbo8962
@garbo8962 10 ай бұрын
And where are the two screws that come with the cover? Would not pass inspection in my area with just the flimsy single 6/32 screw .Hospital that I did a lot of electrical work in would only allow connectors that used locknuts. Smart using type MC cable that has a insulated copper real deal ground conductor verses the flimsy #16 or 18 guage aluminum wire that's inside type AC ( BX ) cable. You should have use a ground screw to ground the metal box. Extremely dangerous if the two 8/32 screws come loose or fall out then box is not grounded.
@timothymcvay7286
@timothymcvay7286 3 жыл бұрын
So how do you wire the panel
@JBarnes917
@JBarnes917 2 жыл бұрын
If you have to ask here then you shouldn’t be doing it
@stevevojack9092
@stevevojack9092 2 жыл бұрын
Using the 14 gauge stripper on the 12AWG nicks and compromises the conductor (especially when you rotate it), no anti-short bushing installed. What I expect from a 6 month apprentice.
@mattozx6rr
@mattozx6rr 2 жыл бұрын
The anti short bushing is only required on AC cable. You do not need it on MC cable if you use a roto cutter then clean the square end up for a flush mount in the connector. That said I would still use an anti short bushing just for extra insurance and peace of mind.
@Kevin-wj4ed
@Kevin-wj4ed 2 ай бұрын
What are the violations?
@blacksteel2434
@blacksteel2434 2 жыл бұрын
You didnot wrap your wire around the outlet screws what in the word
@nsbconstruction9698
@nsbconstruction9698 3 жыл бұрын
No ground to the box?
@JBarnes917
@JBarnes917 3 жыл бұрын
Glad I’m not the only one yelling at the screen. These residential rats shouldn’t be teaching.
@Faruk651
@Faruk651 2 жыл бұрын
these are hacks
@jcjammer1
@jcjammer1 2 жыл бұрын
I Always use metal conduit. No chance of getting snagged and unraveled. just my personal choice.😄
@joselovos6708
@joselovos6708 Жыл бұрын
@@JBarnes917 old stile
@JBarnes917
@JBarnes917 Жыл бұрын
@@joselovos6708 old? It’s illegal and it’s dangerous
@michaelblanton9782
@michaelblanton9782 4 ай бұрын
Where is the ground connection to the metal box?
@TheBigDanShow
@TheBigDanShow 4 ай бұрын
Good question
@santiagodominguez2522
@santiagodominguez2522 3 жыл бұрын
We build those metal shops where you buy yours
@CHEECHMUN
@CHEECHMUN 2 жыл бұрын
I bought mine from Eagle Carports. I think you and 2 other guys installed mine in SC!!!
@santiagodominguez2522
@santiagodominguez2522 2 жыл бұрын
@@CHEECHMUN awesome 👌
@santiagodominguez2522
@santiagodominguez2522 2 жыл бұрын
What city and state
@CHEECHMUN
@CHEECHMUN 2 жыл бұрын
@@santiagodominguez2522 Nichols, SC
@sammymiller5967
@sammymiller5967 Жыл бұрын
You need to add a red ear on your MC cable first
@tomnorman5461
@tomnorman5461 Жыл бұрын
It's called an 'anti-short bushing' in my neck of the woods. The snap-in connector he's using has this built-in.
@TerryRGraham
@TerryRGraham 9 ай бұрын
@@tomnorman5461 No, that built-in doesn't replace the anitishort bushing. It will fail inspection.
@JohnThomas-lq5qp
@JohnThomas-lq5qp 2 жыл бұрын
No such thing any more in the NEC called a neutral. AHOLES changed one of the most common electrical term that was used for over a hundred years to " Grounded Conductor " . Best to spend a little extra & purchase at least Spec grade receptacles. Will last a lot longer. Now must use a torque driver or torque wrench to tighten All ELectrical terminals. Not a plug , A plug goes on the end if a cord to plug into a receptacle.
@christopherdegarmo9826
@christopherdegarmo9826 2 жыл бұрын
bond the box.......
@soullessdevice
@soullessdevice Жыл бұрын
Well yeah, everything is easy
@stevestewart3816
@stevestewart3816 12 күн бұрын
At 2:47 he realized he fucked up lol
@F16_viper_pilot
@F16_viper_pilot 7 ай бұрын
Um, no ground to the box?? That ground wire should be attached to the box, not the outlet, and a grounding pigtail attached from the box to the outlet grounding screw.
@blainekeener6100
@blainekeener6100 2 жыл бұрын
Counted 4 code violations
@randalladkins
@randalladkins Ай бұрын
cool story
@garagekeys
@garagekeys 2 жыл бұрын
I don't think you should be using that MC cable if it's not going to be covered up, I thought that it was not supposed to be exposed locations where there can be damage
@caliguy1500
@caliguy1500 2 жыл бұрын
Section 330.15 states: Exposed runs of cable, except as provided in 300.11(A), shall closely follow the surface of the building finish or running boards. Exposed runs shall also be permitted to be installed on the underside of joists where supported at each joist and located so as not to be subject to physical damage. Type MC Cable without an outside nonmetallic jacket can be installed in an “other space used for environmental air” in accordance with Section 300.22(C). These cables can be installed either indoors or outdoors and in exposed and concealed locations. ... They can be installed in a cable tray or in any raceway.
@sammymiller5967
@sammymiller5967 Жыл бұрын
You first need to ground your box then your plug in
@surferdude642
@surferdude642 2 жыл бұрын
I assume that the box is grounded by the mc, but you should use the ground wire to ground the box and there is no need to attach a wire or pigtail to the receptacle. When the receptacle is mounted to the cover and the cover is mounted to the box everything is grounded. The receptacle has a self grounding strap on the lower yoke. The cover comes with screws and nuts to mount the receptacle securely and you didn't use those. The screw connection between the receptacles becomes optional. The 20 amp receptacle is ok, but unnecessary, a 15 amp commercial spec grade would be my choice, 15 or 20 amp circuit, it doesn't matter.
@JBarnes917
@JBarnes917 2 жыл бұрын
1. You need to learn difference between “grounded” and “bonded”. 2. That receptacle needs a ground wire going to the box. Please read NEC 250.146, cover mounted wiring devices are NOT considered grounded.
@surferdude642
@surferdude642 2 жыл бұрын
@@JBarnes917 Thank you for the comment, but I believe that it's justified in this case. See NEC 250.146 exception (A). If he was using a receptacle with a self grounding strap, such as a Leviton spec grade, exceptions (A) and (B) would apply. Am I missing something here?
@JBarnes917
@JBarnes917 2 жыл бұрын
@@surferdude642 NEC 2005 Handbook commentary: The main rule of 250.146 requires an equipment bonding jumper to be installed between the device box and the receptacle grounding terminal. However, 250.146(A) permits the equipment bonding jumper to be omitted where the metal yoke of the device is in direct metal-to-metal contact with the metal device box and at least one of the fiber retention washers for the receptacle mounting screws is removed, as illustrated in Exhibit 250.52. Cover-mounted wiring devices, such as on 4-in. square covers, are not considered grounded. Section 250.146(A) does not apply to cover-mounted receptacles, such as the one illustrated in Exhibit 250.53. Box-cover and device combinations listed as providing grounding continuity are permitted.
@brents927
@brents927 2 жыл бұрын
I don't want the camera man's comments
@ourv9603
@ourv9603 3 жыл бұрын
I bought a brand new house. The contractor was thoughtful enough to give me 5 outlets on each wall. The outlets are fed with 20Amp breakers. Each outlet is wired with yellow 20Amp romex. HOWEVER, each outlet is 15Amp. How that passed inspection is beyond me. I'm having to replace all the outlets with 20Amp. !
@frank480
@frank480 3 жыл бұрын
NEC allows the use of 15 Amp rated outlets on 20 Amp branch circuits.
@wheelzup7597
@wheelzup7597 2 жыл бұрын
That will definitely pass code, it’s within spec.
@garagekeys
@garagekeys 2 жыл бұрын
I believe you are allowed to use 15 amps outlet on 20 amp circuit, just not a 20 amps plug on a 15 amp circuit can't do that
@donaldlee6760
@donaldlee6760 2 жыл бұрын
FYI - the reason it passed inspection is because it is safe to use 15 amp outlets on a 20 amp circuit. Obviously it is dangerous to do the opposite (plug your 20 amp device on a 15 amp circuit and possibly causing a fire).
@KevinCoop1
@KevinCoop1 2 жыл бұрын
@@TheBigDanShow You stayed metal buildings are required to have 20 amp receptacles on 20 amp circuits. Where does this rule come from?
@sammymiller5967
@sammymiller5967 Жыл бұрын
The man seems like a nice guy but he is doing it all wrong do not do it his way
@justincloncs1116
@justincloncs1116 Жыл бұрын
Box needs grounded
@effthegop
@effthegop Жыл бұрын
No "special tool" required. I retired after 45 years and never used a roto tool. Just bend carefully until the sheath comes apart and snip it with your sharp diagonal cutters. Quicker, easier and no extra cumbersome tools to carry.
@tomnorman5461
@tomnorman5461 Жыл бұрын
Although 'dikes' will work in a pinch, a 'ROTO-SPLIT' is faster and does a much 'cleaner' job of stripping the MC.
@effthegop
@effthegop Жыл бұрын
@@tomnorman5461 Sounds like a wager :). I'll take it !
@hightowerelectricllc6132
@hightowerelectricllc6132 3 жыл бұрын
FAILED! 1) No anti-short bushing for your MC 2) Receptacle is not GFCI protected, all garages need to be 3) MC cable not properly supported 4) Did not properly support the receptacle devise to the RS cover. That middle screw is not a means of support only the top and bottom yoke
@recon1314
@recon1314 3 жыл бұрын
The type of connector he used has a built in "anti short" sleeve in the throat. 100% on board with a fail for everything else
@jimyeats
@jimyeats 2 жыл бұрын
@@recon1314 That redhead at the end of the connector is just to protect the wires from the end/edges of the connector, you still need a redhead at the end of the mc cable where the wire would rub on that. Really truly.
@garagekeys
@garagekeys 2 жыл бұрын
Anti-short bushing I thought is not required with MC that is optional
@jimyeats
@jimyeats 2 жыл бұрын
@@garagekeys Maybe in certain codes and jurisdictions? Do you want your thinly coated wire rubbing on a sharp MC edge? Super easy and cheap insurance.
@garagekeys
@garagekeys 2 жыл бұрын
@@jimyeats yeah, I looked in the NEC 320.40 states AC cable needs the bushings not MC it's optional it looks like if you follow NEC
@markdesilvey454
@markdesilvey454 2 жыл бұрын
Many violations. Nowhere close to a professional install.
@Kevin-wj4ed
@Kevin-wj4ed 2 ай бұрын
What are the violations? I want to learn.
@garyhobbs249
@garyhobbs249 3 жыл бұрын
He didn’t ground the box lmao
@morehp1
@morehp1 3 жыл бұрын
It’s a structure metal building the the panel is grounded to the structure, that box is screwed to the building, metal to metal, it’s grounded.
@garyhobbs249
@garyhobbs249 3 жыл бұрын
If you had your master electrical license then you’d understand
@ABflanagan523
@ABflanagan523 2 жыл бұрын
@@garyhobbs249 Seems you don’t. I agree good practice would be to run a pigtail from the box to the outlet for a solid ground but with a metallic box and MC it’s an EGC.
@JBarnes917
@JBarnes917 2 жыл бұрын
@@morehp1 no ground screw or ground tail in box so it’s not bonded. Learn the difference between grounded and bonded…. When you get an electrical license let us all know
@garagekeys
@garagekeys 2 жыл бұрын
@@morehp1 is that allowed by code?
@DAVADMDAVAD
@DAVADMDAVAD Ай бұрын
I need tu git ma Prescribe fer ma medsin.
@oldnbroke1544
@oldnbroke1544 Жыл бұрын
You should pull this video...box isn't bonded, the receptacle is upside down...you sir are unsafe...
@JBarnes917
@JBarnes917 3 жыл бұрын
Guy didn’t bond the box with the ground.. this is basic NEC code knowledge. You WILL fail an electrical inspection and it’s just not safe. He should stick to changing light bulbs.
@ABflanagan523
@ABflanagan523 2 жыл бұрын
Outlet is grounded due to the yoke making contact with the metallic box. I agree there’s no pigtail from the 12-2 to box and box to outlet but it is grounded, just not the way you’d expect.
@JBarnes917
@JBarnes917 2 жыл бұрын
@@ABflanagan523 wrong… open your code book. 250.148(c) if you have a metal box it needs a ground screw and pig tail. Again this install will fail an inspection.
@Faruk651
@Faruk651 2 жыл бұрын
@@ABflanagan523 We use metal boxes for residential and commercial in Ontario, Canada. No plastic crap. And we have to ground the metal boxes and devices by code.
@ABflanagan523
@ABflanagan523 2 жыл бұрын
@@JBarnes917 250.146 (A) Surface Mounted Box. Where the box is mounted on the surface, direct metal to metal contact between the device yoke and the box or a contact yoke or a self grounding receptacle shall be permitted to ground the receptacle to the box.
@JBarnes917
@JBarnes917 2 жыл бұрын
Wrong NEC 2005 Handbook commentary: The main rule of 250.146 requires an equipment bonding jumper to be installed between the device box and the receptacle grounding terminal. However, 250.146(A) permits the equipment bonding jumper to be omitted where the metal yoke of the device is in direct metal-to-metal contact with the metal device box and at least one of the fiber retention washers for the receptacle mounting screws is removed, as illustrated in Exhibit 250.52. Cover-mounted wiring devices, such as on 4-in. square covers, are not considered grounded. Section 250.146(A) does not apply to cover-mounted receptacles, such as the one illustrated in Exhibit 250.53. Box-cover and device combinations listed as providing grounding continuity are permitted.
@brandonrippeonphoto
@brandonrippeonphoto 10 ай бұрын
No red eye; no box bonding. amateurs should not be making how to videos for electrical work…
@TheBigDanShow
@TheBigDanShow 10 ай бұрын
Lol
@wisdomcalls2475
@wisdomcalls2475 10 ай бұрын
Q. Shouldn’t you be bonding the metal frame building to ground due to lightning strikes 🤔
@terrydougherty7078
@terrydougherty7078 2 жыл бұрын
Please don’t follow any of these “tips”. Call a professional.
@garagekeys
@garagekeys 2 жыл бұрын
Do yourself a favor.... Call a pro
@theshop5331
@theshop5331 5 ай бұрын
good grief
@TheBigDanShow
@TheBigDanShow 5 ай бұрын
Lol
@trustme7731
@trustme7731 2 жыл бұрын
Multiple code violations. Leave the electrical work to the professionals.
@trustme7731
@trustme7731 Жыл бұрын
@@TheBigDanShow It doesn't meet the NEC requirements which are minimum requirements. Fire is not the only hazard with electricity.
@jaxchristian6408
@jaxchristian6408 8 ай бұрын
Ya . Keep it a secret. Act like you guys are the only ones that can install an outlet
@jessicakeefer5077
@jessicakeefer5077 Ай бұрын
Come down on your prices and we will 😌
@trustme7731
@trustme7731 Ай бұрын
@@jessicakeefer5077 Would you shop for the cheapest heart surgeon?
@trustme7731
@trustme7731 Ай бұрын
@@jessicakeefer5077 So, you are willing to live with, or die from, illegal electrical work?
How To Install MC | Metallic Cable | MC Connectors
21:35
Why Not DIY
Рет қаралды 178 М.
Metal building insulation and electrical episode #2
7:44
THE HEIGHTS
Рет қаралды 137 М.
Alex hid in the closet #shorts
00:14
Mihdens
Рет қаралды 13 МЛН
Who has won ?? 😀 #shortvideo #lizzyisaeva
00:24
Lizzy Isaeva
Рет қаралды 65 МЛН
Happy 4th of July 😂
00:12
Alyssa's Ways
Рет қаралды 70 МЛН
Double Stacked Pizza @Lionfield @ChefRush
00:33
albert_cancook
Рет қаралды 85 МЛН
Wiring Up A Metal Building
13:40
Real Life Tested
Рет қаралды 83 М.
Wiring My New Shop | Adding Outlets and Lighting
10:52
April Wilkerson
Рет қаралды 174 М.
How To Make Up A Duplex Receptacle Box During Rough In (Commercial)
7:31
How To Seal Gaps In A Metal Building
8:01
PatriotDIY
Рет қаралды 156 М.
Foam Board vs Spray Foam… Insulating our steel building/garage | Tips and Tricks
8:37
Great American Northern Garage
Рет қаралды 1,7 МЛН
Installing 220v Outlets in the Shop - Easier Than You Thought
7:51
Jonathan Katz-Moses
Рет қаралды 2,1 МЛН
I meet Mr.Beast
0:15
ARGEN
Рет қаралды 26 МЛН
Secret Experiment Toothpaste Pt.4 😱 #shorts
0:35
Mr DegrEE
Рет қаралды 12 МЛН
Пранк над Махачевым🥶
0:19
FERMACHI
Рет қаралды 10 МЛН
НИЧЕГО СЛОЖНОГО
0:21
KINO KAIF
Рет қаралды 3 МЛН
Mother Cat Drinks Lots of Coffee to Get By #funny #catlover #cuteanimals #cartoon
0:21
Super Emotional Stories
Рет қаралды 13 МЛН
НРАВИТСЯ ЭТОТ ФОРМАТ??
0:37
МЯТНАЯ ФАНТА
Рет қаралды 6 МЛН