ITM Main Drain Test

  Рет қаралды 40,756

Northern Illinois Fire Sprinkler Advisory Board

Northern Illinois Fire Sprinkler Advisory Board

Күн бұрын

ITM Information on a Main Drain Test for a fire sprinkler system.

Пікірлер: 32
@raymondleach9307
@raymondleach9307 4 жыл бұрын
I would also add that as an inspector I always review the data plate to see what the original residual flow was at time of installation, if the results are lower than the system may not operate as intended.
@raymondleach9307
@raymondleach9307 3 жыл бұрын
@KZfaq Lover you always do the water supply test regardless if there is a data plate.
@Bobby-wy3fm
@Bobby-wy3fm 3 жыл бұрын
@KZfaq Lover Sometimes there isn't a hydraulic nameplate because it isn't required for certain systems.
@comtecfire7399
@comtecfire7399 4 жыл бұрын
It might be a good idea to tell why the main drain test is done, and what percentage drop is acceptable on this type of test.
@djjammindave
@djjammindave 2 жыл бұрын
actuall he does explained it in another small video.
@achanceman
@achanceman 4 жыл бұрын
You need two spares heads for every head installed in the building. You can also disable the horns on the fire panel prior to running water.
@jaysonmengel2031
@jaysonmengel2031 3 жыл бұрын
Main drain below flow switch so no alarm
@Bobby-wy3fm
@Bobby-wy3fm 2 жыл бұрын
@@jaysonmengel2031 if the main drain pipe is located above the water flow switch, it WILL trigger the fire alarm.
@jarkoff9335
@jarkoff9335 5 жыл бұрын
No 5 year internal/fdc inspection record?
@philipkavilae5338
@philipkavilae5338 Жыл бұрын
8" Riser Pipe , with threaded ?
@rickygonzalez.o2126
@rickygonzalez.o2126 4 жыл бұрын
Wow that domestic line is tied to the city feed I get there's a back flow before it's run into the building but old cast and steel aren't doing anyone any favors lol
@xentaatnex8261
@xentaatnex8261 2 жыл бұрын
I dont know when this video was created but it looks like those panel batteries are due for replacement.
@cmarname
@cmarname 2 жыл бұрын
Is it required to repeat the test at each floor level (the control valve assembly has also a connection to the drain)?
@paccbutler1826
@paccbutler1826 2 жыл бұрын
The main drain test, is a system's test. You cannot perform this test per floor
@mauriciocastro5080
@mauriciocastro5080 4 жыл бұрын
They didn't have the heads listed anywhere
@lightningplasma
@lightningplasma 4 жыл бұрын
do you have to turn off the fire pump and drain fire hydrants outside, if any, before you do this?
@TheGardista
@TheGardista 2 жыл бұрын
Never put the fire pump out of service
@djjammindave
@djjammindave 2 жыл бұрын
simple answer: NO
@georei
@georei 3 жыл бұрын
Next time you do a drain test, open the drain valve all the way.
@Hollowayshouse1026
@Hollowayshouse1026 2 жыл бұрын
Does anyone know where I could get certification training . I have a Fire Protection business. I have owned this for over a year but previous owner never got into. Sprinkler systems . I’m in Mississippi
@TheGardista
@TheGardista 2 жыл бұрын
In Pennsylvania state
@djjammindave
@djjammindave 2 жыл бұрын
look online NICET training and certification. There is another certification program out there similar to NICET and it becoming widely accepted as the standard just like NICET. Can't remember the name of it, at this very moment.
@jeffhail5778
@jeffhail5778 5 жыл бұрын
Batteries 11/02/09 Better change them out next time. Good training segment. Thanks.
@smokeGR20
@smokeGR20 5 жыл бұрын
He did a sprinkler main drain test..nothing to do with batteries..that is done on a fire inspection..so he did a proper test..
@jeffhail5778
@jeffhail5778 5 жыл бұрын
@@smokeGR20 I understand your point. I write up or document any discrepancies I recognize during supression or detection testing. I'm responsible for both and a 1 man office so I'm more observate on all systems.
@creasybear1698
@creasybear1698 4 жыл бұрын
Why didn’t you time the static return point after shutting off residual flow
@FireTech7
@FireTech7 2 жыл бұрын
I noticed the same thing
@seanstafford4012
@seanstafford4012 3 жыл бұрын
That call to the alarm company was fake .. he never hit the tampers and the main drain was below the flow switch he never tripped any horns you could flow that drain all day and the fire department would never respond... wish I had ten accounts just like that lol
@cmarname
@cmarname 2 жыл бұрын
Interesting remark. is the water flow alarm supposed to be positioned before the drain? I thought that the inpector test connection was after the flow alarm, not the main drain.
@paccbutler1826
@paccbutler1826 2 жыл бұрын
@@cmarname The flow switches are located (in different areas) after the main drain. The main drain test is upstream of any flow switches. Typically, this should not trigger them. The inspectors test is located (usually near the end-of-the-line) at the end of the system. When the inspector's test is performed, a flow switch will detect flow, send a notification, and will trigger the alarm.
@AnaStudent
@AnaStudent Жыл бұрын
​@@paccbutler1826 I was flustered. It makes sense that the water comes upward and never hits the water flow switch so no alarm.
ITM Basic Inspector Test
2:27
Northern Illinois Fire Sprinkler Advisory Board
Рет қаралды 10 М.
ITM Double Interlock Preaction System
5:49
Northern Illinois Fire Sprinkler Advisory Board
Рет қаралды 59 М.
Nutella bro sis family Challenge 😋
00:31
Mr. Clabik
Рет қаралды 13 МЛН
That's how money comes into our family
00:14
Mamasoboliha
Рет қаралды 10 МЛН
Became invisible for one day!  #funny #wednesday #memes
00:25
Watch Me
Рет қаралды 56 МЛН
Know More Risk: Wet System -“ Alarm Check Valve
4:37
FM Global
Рет қаралды 143 М.
Sprinkler System Water Flow Device Testing
10:36
ORR Protection
Рет қаралды 3,7 М.
Main Drain Test Fail
17:33
Fire Sprinkler Tech
Рет қаралды 857
5 year fire sprinkler inspection
20:02
Joy Cool
Рет қаралды 11 М.
ITM Wet System Riser, Backflow and Connections
4:08
Northern Illinois Fire Sprinkler Advisory Board
Рет қаралды 32 М.
Resetting a GEM Dry Valve
10:32
Fire Sprinkler Tech
Рет қаралды 2,3 М.
Dry Sprinkler Inspection
2:59
Silco Fire & Security
Рет қаралды 21 М.
Dry Pipe Valve Visual Inspection
4:27
Inspect Point
Рет қаралды 21 М.
FIRE PUMP How to perform annual Fire pump test.
7:00
Fire Technician101
Рет қаралды 55 М.
Nutella bro sis family Challenge 😋
00:31
Mr. Clabik
Рет қаралды 13 МЛН