Power Outage Generator Test At High School | Real Power Loss Simulation Emergency Generator Test!

  Рет қаралды 15,755

NIC’S - SYSTEMS & ELECTRIC

NIC’S - SYSTEMS & ELECTRIC

15 күн бұрын

Пікірлер: 75
@TheLastWolfBane
@TheLastWolfBane 13 күн бұрын
coming from a guy whos father is a electrician, you looking away from the breaker when you turn it on or off is fricken awesome
@randomfan8111
@randomfan8111 13 күн бұрын
my neighborhood has like 135 of these things inside the leasing office to prevent concerns of houses going on power outages when theyres a power outage or a storm.
@The_FireAlarmGuy
@The_FireAlarmGuy 13 күн бұрын
Nice video Nic, 😊 Nicely explained 😁 Good to see the generator and the system running and working as it should 🤩😉
@lutinogamesofficial4347
@lutinogamesofficial4347 13 күн бұрын
I love your videos of the high school. Great as always! Dont stop posting!
@L_und_M_3D
@L_und_M_3D 13 күн бұрын
Great vid as always! Keep it up nic!
@ViperLunaKitten
@ViperLunaKitten 13 күн бұрын
i love your videos on how fire alarm systems generator systems work and all the replacement on all the schools im really learning more about this stuff and things like that you have a good summer to come and thanks
@nics-systems-electric
@nics-systems-electric 13 күн бұрын
Glad you like them!
@LostDeadSoul
@LostDeadSoul 7 күн бұрын
I have come across "Sender unit". It is the unit which measures the fuel in the tank. It is more specifically called a Fuel Gauge Sender Unit. Fuel Leak / Sender failure might indicate that the fuel pressure does not come up and that there is either a leaking hose or the fuel level is not true and does not trigger Low Fuel Level Sender failure might indicate that the resistance of the sender is not plausible SC/OC.
@BigChief2003XL
@BigChief2003XL 12 күн бұрын
I’d like to see the light go out and come back on in the hallway as well. Every other light is powered by generator, so I’d kinda like to see that in action.
@wastemanagenl
@wastemanagenl 13 күн бұрын
Amazing video! I love the thumbnail too
@Aron_B10
@Aron_B10 13 күн бұрын
Explained good as always
@alfieInspired
@alfieInspired 13 күн бұрын
Keep making great videos mate ❤
@keyesrm
@keyesrm 9 күн бұрын
“Sender failure” possibly refers to sensors. I’ve heard engine oil pressure sensors referred to as oil pressure senders, I’m guessing it’s checking for resistance and/or voltage to be within a certain range to verify operation
@mgkleym
@mgkleym 8 күн бұрын
The fuel sender is the mechanical float that measures the tank level. So that light comes on if it detects a sudden drop in the fuel level meaning ether the tank is leaking or the fuel gauge has failed.
@gamerboy12970
@gamerboy12970 13 күн бұрын
I love your channel I support you
@johnwiiu7005
@johnwiiu7005 8 күн бұрын
My school had quality asbestos and if you were in the PC room, the rule was to never turn on more than 10 PC's otherwise the surge protector for the PC room next door would switch off.
@LethaWolfStudios
@LethaWolfStudios 13 күн бұрын
They tested the generator at my work yesterday before it opened (it’s a department store at mall here in Florida). I was wondering if you can think of any reason why the lights went off three times instead of just twice when the loads switched as shown here?
@hotbytesB
@hotbytesB 13 күн бұрын
I like when that generator started up. How often do you have to test it?
@nics-systems-electric
@nics-systems-electric 13 күн бұрын
Supposed to be ran once a month and a load bank test once a year
@Max_And_His_Tech
@Max_And_His_Tech 13 күн бұрын
I love your channel
@keithpierce8458
@keithpierce8458 13 күн бұрын
great video
@nics-systems-electric
@nics-systems-electric 13 күн бұрын
Thanks!
@litz13
@litz13 10 күн бұрын
We have the same type of thing at our datacenter, only it's a tad bit bigger at 500kva. Our two UPS's are 284kw and 140kw.
@Liamblox1223
@Liamblox1223 13 күн бұрын
Hello I love fire alarm systems thats the reason why I love your channel I wish I could get a fire alarm system in my own home or something but I cant but I might in the future we just have to wait and see but I'm going to ask promotion to see if I can set of the fire alarm at my school for a good video but if there say yes I think it should be after school time or there might want a fire drill so there might let me do it and record it for content. I love your videos and I hope to see you again soon have a great day or night from Liam [your biggest fan]
@All_ConsumingBandu
@All_ConsumingBandu 13 күн бұрын
In my last comment on your channel I talked about mixed signals and you use that word alot. So I did some research on what it means. It means that horns would do continuous, then code 3 then 4 randomly after a few seconds. I don't know what YOU mean about mixed signals but either of us could be wrong.
@nics-systems-electric
@nics-systems-electric 13 күн бұрын
I am not wrong I am not sure how you got that as a answer however mixed signals is referring to a mixture of device types producing a significant difference in sound other the tone produced or the pattern of the signal
@wastemanagenl
@wastemanagenl 13 күн бұрын
@@nics-systems-electric so, mixing horens and low frequency sounders isn't legal... Right? (I don't know much about the code(s) in US and Canada because I'm from the Netherlands)
@nics-systems-electric
@nics-systems-electric 13 күн бұрын
@@wastemanagenl it's difficult as I don't know of any information on which specific devices which are and are not allowed I would guess those would not be legal due to the quite different tone however if they are in separate areas where they are not audible from each other it would likely be OK
@wastemanagenl
@wastemanagenl 13 күн бұрын
@@nics-systems-electric I'm learning
@cutepaws3859
@cutepaws3859 13 күн бұрын
Just curious, do you guys run those exhaust fans on generator once in a while I'm guessing during the annual test, but what's a sure
@nics-systems-electric
@nics-systems-electric 13 күн бұрын
They get tested annually with the fire alarm system
@jordanwoodcock7498
@jordanwoodcock7498 7 күн бұрын
I work at a green house each year we go a generator test sadly ours are Cummins powered so it’s a chore to start the ole girls
@ebelray6890
@ebelray6890 10 күн бұрын
Get a box of earplugs as they are not expensive, easy to throw into your pocket and really effective.
@nics-systems-electric
@nics-systems-electric 10 күн бұрын
If they had some here I would
@Defianthuman
@Defianthuman 13 күн бұрын
I think that the sending failure is referring to a fuel sending unit in the tank since if it fails then generator runs out of gas. (At the end of the video)
@nics-systems-electric
@nics-systems-electric 13 күн бұрын
Yeah probably that would make sense
@mommyelizabeth9316
@mommyelizabeth9316 7 күн бұрын
bro owns a truck 💀
@captainpunch2671
@captainpunch2671 13 күн бұрын
I wanna hear more of that engine
@nics-systems-electric
@nics-systems-electric 13 күн бұрын
I've got lots of videos showing it running during other tests and power outages
@captainpunch2671
@captainpunch2671 13 күн бұрын
@@nics-systems-electric sounds good 👌. I’d swap it into a truck 🛻
@noah_will
@noah_will 12 күн бұрын
Do you guys put a CO detecter in the generator room, or is that not much of a concern with the exhaust system you have?
@nics-systems-electric
@nics-systems-electric 12 күн бұрын
There is not a CO detector. diesels produce much less carbon monoxide than gas engines so I guess it's not as much of a concern especially since it's exhausted outside and there is constant air movement in the room when it's running
@Peti817172M
@Peti817172M 9 күн бұрын
At the switchback why was the 3 sec blackout, if the main power and the generator ran simultaniously?
@nics-systems-electric
@nics-systems-electric 9 күн бұрын
That's what I explained about the neutral delay. Because frequencies aren't matched there needs to be a delay when transferring.
@inothome
@inothome 8 күн бұрын
Do you ever alternately turn off one ATS at a time to verify that particular ATS can start the gen? I know in a true power outage it may not matter, but at least in the US when it comes to hospitals you have to verify each ATS can start the gen. Which used to be rotated each test and I have seen 15 or more ATSs in some hospitals. But that way, if that one circuit trips for whatever reason the ATS is confirmed it can start the gen. But not sure how strict regs are for schools there. It's a school, not a hospital.
@nics-systems-electric
@nics-systems-electric 7 күн бұрын
It's not something you have to do. the generator just has to be started monthly you can just hit the run button to satisfy that requirement. I think I have started it from the standby transfer switch before just by doing a test with load from the actual transfer switch not switching the breaker off. Definitely not a bad idea to test all transfer switches.
@inothome
@inothome 7 күн бұрын
@@nics-systems-electric Makes sense here to not really worry about it. But when it comes to back up gens and hospitals it's a whole other layer of regulations they have to meet and validate regularly.
@aliciaamerson7658
@aliciaamerson7658 13 күн бұрын
Why do you turn off 2 subpanels instead of the main breaker for these tests.
@nics-systems-electric
@nics-systems-electric 13 күн бұрын
There's multiple reasons. we don't want to shut down the entire building for no reason. You also don't want to be operating a large breaker under high load as it can fail. When you do a full building shut down you wouldn't be just opening the main breaker you would be turning off every smaller one first anyway.
@noahbakke5935
@noahbakke5935 13 күн бұрын
Can you do a video with the exhaust fans and fire alarm running on generator? It would be interesting to see how much load they actually put on the generator….
@nics-systems-electric
@nics-systems-electric 13 күн бұрын
The fire alarm system itself won't make any difference the exhaust fans would definitely put more load on it however I won't get the opportunity to do that as I only have a month left working in this school district
@mommyelizabeth9316
@mommyelizabeth9316 7 күн бұрын
Double barrel exhaust to make more power
@mommyelizabeth9316
@mommyelizabeth9316 7 күн бұрын
give it an backfire ECU RATATATATATATA
@Rosie257.
@Rosie257. 13 күн бұрын
8:59
@bigfoot13s80
@bigfoot13s80 9 күн бұрын
Does any of the hvac get powered with the generator?
@nics-systems-electric
@nics-systems-electric 9 күн бұрын
No
@JoebDragon
@JoebDragon 8 күн бұрын
why does an school have an atm in it? and does it have no fees?
@nics-systems-electric
@nics-systems-electric 8 күн бұрын
Most high schools do so students can get cash as there's still lots of things that are cash only especially at school I do believe there is a fee
@kalVR
@kalVR 11 күн бұрын
does the CCTV system work on the genorater?
@nics-systems-electric
@nics-systems-electric 11 күн бұрын
That would be on the Non-Emergency power which also is powered by the UPS
@osta2288
@osta2288 3 күн бұрын
Did u film this on a samsung? just curius :þ
@nics-systems-electric
@nics-systems-electric 3 күн бұрын
iPhone
@Siren_StrObE
@Siren_StrObE 10 күн бұрын
Is the PA system powered by the generator?
@nics-systems-electric
@nics-systems-electric 10 күн бұрын
No the PA does not have any back up power which does not make much sense at all
@jaye7679
@jaye7679 7 күн бұрын
why not use solar panels and battery arrays instead of fossil fuels.. excess power can be used instead of grid power, saving $$$ over the long run
@nics-systems-electric
@nics-systems-electric 7 күн бұрын
Solar has its place but emergency power is not it. Not only the batteries that would be required would be extremely large and expensive that whole system would need to be CSA/ULC listed for life safety emergency use. we have schools with solar but not with batteries that would be just too big for a school. The solar system shuts down during a power outage and only the generator produces power at those schools anyways.
@SirFrag32
@SirFrag32 7 күн бұрын
The amount of batteries needed to run for the required duration would be massive. Plus with diesel, assuming roads are clear, you can get fuel deliveries at regular intervals.
@GaryBeltz
@GaryBeltz 10 күн бұрын
What is wet sacking?
@nics-systems-electric
@nics-systems-electric 10 күн бұрын
I'd google it as I am not a diesel mechanic.
@TimSeatonPainting
@TimSeatonPainting 8 күн бұрын
Wet stacking, I believe is referring to either moisture or unburnt fuel in the exhaust, causing it to produce black smoke. I used to do maintenence for a nursing facility, we had a 250kw Cummins that I did monthly load tests on.
@BritishEngineer
@BritishEngineer 10 күн бұрын
0:07 “60 kay double you” why don’t you refer to it as it’s real name? Respect derived SI units. I don’t even think it’s going to be kW. It would be KvA?
@nics-systems-electric
@nics-systems-electric 10 күн бұрын
It's not "Kay double you" It's actually 60kw which is a measurement of power. kW is a common abbreviation for thousand watt. and is not the same as kVA. Generators are usually rated in kW however often both are specified on the nameplate as with this one. 60 kW or 75 kVA. Hope that helps.
@inothome
@inothome 8 күн бұрын
kVA vs kW... VA is Volts times Amps and with DC gives you the Wattage, k for kilo, M for mega etc.... When it comes to AC since the current and voltage will not be in phase (except a purely resitive load) a simple VA calculation will not give you your actual power output. You have to account for the power factor, which is the ratio of VA vs real power expressed as power factor. As a general rule of thumb they use a 0.8 power factor to derive the kW rating from the kVA rating. But in real world conditions the power factor will change based on the types of loads. Purely resistive loads are a PF of 1, a crappy motor may be as low as 0.5 unloaded. So transformers and generators are based off the VA they can produce not the actual Wattage, since the power factor is unknown. And yes, your toy 5,000W gen at home is rated by Watts for simplicity, but real generators are rated in kVA or MVA. As far as nitpicking kW vs kilo-Watt.... that's just being a pain in the ass for no reason. Anyone in the industry calls it kW, MW etc.... By the way, Watt is the SI unit for power. So kW is correct in SI nomenclature too. And for someone telling someone to respect SI units, kvA is wrong. kVA is correct. V and A are capitalized as they are respective SI units. The k is just the sign for thousand and is lower case.
@nics-systems-electric
@nics-systems-electric 7 күн бұрын
@@inothome I appreciate the explanation and detail. I'm not sure what makes my generator a toy as it does the same function as larger set ups during a power outage. Either way thanks for the comment.
@inothome
@inothome 7 күн бұрын
@@nics-systems-electric You misunderstood, that wasn't directed at this generator. I was referring to little portable gens that are rated in Watts, not kVA like this gen is. Like a Honda 5kW gen, they normally don't advertise them in VA since most people buying them wouldn't understand. I was more talking to the original snarky comment about "respecting derived SI units".
Installing A Red Fire Alarm Strobe Light On My Generator Building.
15:20
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 10 М.
Setting Off Fire Alarm System HVAC Duct Detector With Smoke Machine Into Air Duct!
12:13
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 11 М.
Bro be careful where you drop the ball  #learnfromkhaby  #comedy
00:19
Khaby. Lame
Рет қаралды 36 МЛН
¡Puaj! No comas piruleta sucia, usa un gadget 😱 #herramienta
00:30
JOON Spanish
Рет қаралды 22 МЛН
La final estuvo difícil
00:34
Juan De Dios Pantoja
Рет қаралды 26 МЛН
How To Turn Car Alternator Into Powerful Motor
4:04
Rex Tech
Рет қаралды 21 М.
Budget Friendly Emergency Backup Power - Transfer Switch
10:33
Hometown Acres
Рет қаралды 2,3 МЛН
How to Install an Elevator in your Backyard
18:43
JerryRigEverything
Рет қаралды 964 М.
Building a Generator
12:36
Tim Station
Рет қаралды 1,1 МЛН
Triphasic Infinite Energy Generator 10Kw 230V - Liberty Engine 1.1
17:33
The Liberty Engine Project
Рет қаралды 996 М.
600/347V Diesel backup generator test with load transfer at high school
16:40
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 24 М.
Setting off fire alarms by lighting fire alarm heat detector on fire!
11:14
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 13 М.
Miracle Doctor Saves Blind Girl ❤️
0:59
Alan Chikin Chow
Рет қаралды 25 МЛН
То чего мы все боялись в детстве
1:00
КЕРЯ
Рет қаралды 3,2 МЛН
СҰЛТАН СҮЛЕЙМАНДАР | bayGUYS
24:46
bayGUYS
Рет қаралды 650 М.
Cat story: from hate to love! 😻 #cat #cute #kitten
0:40
Stocat
Рет қаралды 10 МЛН