Why Are Your Radiators Getting Hot When the Heating Is Off?

  Рет қаралды 166,372

Skill Builder

Skill Builder

3 жыл бұрын

So your radiators are getting hot when the heating is turned off and you don't know why?
Roger explains in his latest Know Your House whiteboard explainer.
#KnowYourHouse #DIY #SBFAQ
===================================================
Skill Builder Link Tree: linktr.ee/skillbuilder
Tell us what you like: skill-builder.uk/vote
Get in touch, send us your pictures and videos: skill-builder.uk/send
Twitter: / skillbuilderuk
Facebook: / skillbuilderchannel
Out of respect to our channel sponsors and the wide variety of people who watch our videos, we will remove comments that do not follow common standards of politeness and decency.

Пікірлер: 400
@descheers2217
@descheers2217 3 жыл бұрын
Another invaluable piece of info, thanks for that. I was just re-watching an old video of yours regarding leaking stop taps and again a priceless titbit of info that's helped me out a few times. These sorts of videos that you and Robin do are a great source of information and are superb because of how short and straightforward they are. Many thanks again 👍
@stevejones9529
@stevejones9529 Жыл бұрын
Thanks for your comment on stop taps, I've just stop mine leaving
@kennethbone5490
@kennethbone5490 3 жыл бұрын
I had this exact issue in house I bought where the plumbing was converted to a pressurised hot water tank for a loft extension with an extra en-suite bathroom. In summer some of the downstairs radiators got warm from the lockshield ends. Four British Gas engineers tried to fix it over 3 days. They changed the motorised valve twice! They couldn't work it out and left it unfixed. I then got in local independent heating engineer out who diagnosed the problem and fixed it with a non return valve on the hot water return as you described in a mornings work. Great video, spot on.
@mdsween
@mdsween 3 жыл бұрын
I have exactly the same circumstance as you Kenneth! Am about to do the heat check now before I call out the plumber
@tonybowe1266
@tonybowe1266 3 жыл бұрын
Love these SB videos. Amazing knowledge and very clear when explaining how things work. I have this issue so know what to look for now. Thank you.
@michaelblissett9863
@michaelblissett9863 Жыл бұрын
An excellent teacher, clear and precise and has a way of explaining in detail that is very helpful to many.
@n0vaph0enix
@n0vaph0enix 3 жыл бұрын
I think you may be a wizard! This has been bugging me for ages and this was such a simple and clearly detailed explanation that you’ve made it seem completely obvious.
@aspetm3846
@aspetm3846 2 жыл бұрын
As usual you have done great work and explained your own experience to be helpful for others. Many thanks Roger.
@mystikal518
@mystikal518 Жыл бұрын
its always a joy to listen to someone who really knows his onions! Brilliant explanation
@silastetley9643
@silastetley9643 3 жыл бұрын
Roger job spot on, well explained. The time taken is worth it 👌.
@SkillBuilder
@SkillBuilder 3 жыл бұрын
Thank you. I watched my previous efforts and thought it was just not clear enough. I am glad it worked in the end.
@GrahamF
@GrahamF 10 ай бұрын
Absolutely spot on & exactly what was happening to my system! I tried everything to find out why this was happening, and it wasn't until I got rid of my heat only boiler, and changed to a combi boiler. The connection from the HW return was connected to the radiator return pipe under the floor. This was done when the house was built! Lazy plumbing indeed. Thank you 👍
@adrianodoherty6283
@adrianodoherty6283 2 жыл бұрын
A decent explanation of a problem most plumbers/heating engineers have come across. Just moved house and it’s happening in mine too! 😀 Need to get round to draining it down and correcting before too much longer!
@daytonamann5618
@daytonamann5618 3 жыл бұрын
Hi Roger, Thanks for the clear explanation. I have that problem and never really found a clear explanation until I saw your video! Thanks
@danielgyc8800
@danielgyc8800 3 жыл бұрын
Well explained mate! Nice to refresh on these sort of things when you haven’t been jobbing for a while!
@MatSmithLondon
@MatSmithLondon 3 жыл бұрын
This is my favourite type of video, simple but really good. I think explaining stuff like this is your forte! (Not to say the other types aren’t good, but really like this format)
@SkillBuilder
@SkillBuilder 3 жыл бұрын
Thanks Mat. How is the house coming on.
@donaloconnell5015
@donaloconnell5015 2 жыл бұрын
Hello Roger you are a great tutor for me because you speak my kind of uncomplicated language. I think a lot of tradesmen didn't have uncomplicated speakers like you when they were learning so they do their learning at the expense of their customers for many years.
@SkillBuilder
@SkillBuilder 2 жыл бұрын
Thanks for that. I try to stay clear of BS numbers and all that stuff because I think that is what a lot of lecturers become obssesed with
@jctai100
@jctai100 3 жыл бұрын
Excellent explanation! thank you
@philtucker1224
@philtucker1224 Жыл бұрын
Thanks Roger, that was a great explanation! (I actually have that minor issue with the rad nearest to the hot water tank) Although you explained the “wrong-way flow” and the one way valve solution very well, I think sometimes it’s the convection of the heat that creeps along the pipes, as opposed to an actual flow, so the one way valve may not necessarily function to prevent that…thank you for sharing 🙏
@jimwoods9551
@jimwoods9551 Жыл бұрын
I’ve got that too, one rad beside the cistern is heating. No motorised splitter valve. The cistern return is linked upstairs leaving a single return pipe to the lower floor. Going to try an NRV in just that rad.
@alimusheri8305
@alimusheri8305 3 жыл бұрын
Great lesson. Thank you
@grahamshillingford8229
@grahamshillingford8229 3 жыл бұрын
I had the exact same issue on the same set up but it was the valve that had failed in my case. Another well explained & informative explanation Roger.👍👍
@SkillBuilder
@SkillBuilder 3 жыл бұрын
I can be the valve but it is easy to feel if it is letting by. I am amazed when plumbers just replace it without doing that.
@SoledadSolary
@SoledadSolary 3 жыл бұрын
Excellent Roger. Thanks. Well explained.
@BusinessButlers
@BusinessButlers 3 жыл бұрын
Thanks for a great explanation, Roger.
@jonathanconway8094
@jonathanconway8094 Жыл бұрын
Another terrific video. Thanks. We have only a towel rail heated in the summer via the boiler and all rads are off but still get warm despite TRVs off. Rads upstairs and UFL down. As soon as it gets warm I shut the lock shield valve down and this sorts the problem. A new installation (including a low loss header (no idea what that adds)) but after watching this I'm getting them back in! Cheers
@SkillBuilder
@SkillBuilder Жыл бұрын
The summer operation towel rail is intentional but I suspect it is reverse circulating. They should be able to feel this on the pipes A non return valve should sort it out
@declanmoran1894
@declanmoran1894 3 жыл бұрын
Great stuff Roger , fully explained 👍👍👍
@sleekitwan
@sleekitwan Жыл бұрын
I had this, after I bought a run-down beautiful post-war end terrace in Scotland. It had a turret and spiral staircase, I loved it. Troubles made me sell it after a few years or updating, but the hidden issue was whenever the hot water cylinder was put to use, there was this trend to heat only the lower radiators in the house, not upstairs. I usually believe that once something’s done, I treat it as 100% until I find otherwise, this is one of the three times this has NOT held up! The system had two valves, but once I sketched it out I realised it needed a third. It had been relying on either the house being cold a lot, so some heating downstairs might not be a bad thing (!), or the owners had not noticed, etc. I fitted the third valve, which stopped the back-channel movement of hot water from the cylinder heating circuit, from going at all into the radiators backwards. It drove me nuts, but the present owner benefits as all of a sudden it’s not just a nuisance but an expensive one. As you will understand, the effect mainly was on radiators BELOW the level of the ‘head’ from the hot water entering and leaving the cylinder, which was perched in a corner cupboard of the kitchen, above the fridge. So, a three-motorised-valve system, instead of two, and it was perfect. Quite weird for me. Take care all. PS - have a laugh on me…the cost of the house when I bought it in 2003? £35,000 . 2 bedrooms plus a perfectly serviceable loft bedroom, and in fact this is what scuppered my letting plans - the government introduced a bedroom tax, and suddenly nobody moved because they;d have their benefits and home rooms scrutinised at that point, and this extra room was not ‘legit’. The council man said kindly ‘I am going to forget the request for retrospective approval, and put it in the drawer with the others’. I don;t understand hints, it’s terrible! He meant, I might be asked to return it to how it was, whatever that really means. It can mean, they examine the cables to see what date is stamped on them, but that’s a whole planning and building regs world of pain, let’s not go further.
@dskirkpa55
@dskirkpa55 3 жыл бұрын
Thanks, Roger. Indeed very useful information. Continue to keep up the good work
@lw5944
@lw5944 Жыл бұрын
Thanks for your video, which is helpful. I have a combit bolier, I can't turn off one of radiators. Could I ask what could be the cause of the problem? Many thanks.
@tobinparsons
@tobinparsons 3 жыл бұрын
Thanks, exactly the problem iv got! Top man.
@RoderickSpoke
@RoderickSpoke 3 жыл бұрын
Brilliant as usual, we have just had this happen tonight 1st time in 6 years. Turned off the rads on the control unit and let's see what happens tomorrow.
@diykhan
@diykhan 3 жыл бұрын
Very informative guide thanks 👍👌
@manofweed1
@manofweed1 2 жыл бұрын
Absolutely brilliant explanation, totally correct. As you've probably guessed we have a similar problem, though only a few rads get a bit warm on top. But even if the primary return went closest to the boiler a strong pump action could still make the rads reverse circulate couldn't it ? Thanks.
@williammcgrattan9583
@williammcgrattan9583 3 жыл бұрын
Excellent Roger👍
@stephencrozier396
@stephencrozier396 3 жыл бұрын
Thanks Roger, more content like this please!
@ratchriat1716
@ratchriat1716 3 жыл бұрын
Found this video very informative and useful.
@imw4956
@imw4956 10 ай бұрын
Roger, that might just explain my current problem! I had my combi boiler changed to unvented system and had it relocated in a different part of my house - have some but not all rads getting hot when calling for hot water . Plumber does not now what to do he has changed the 3 way motorised valve so hopefully when I show him your Video it will solve said problem! Thanks I appreciate the time and effort you put into producing these great videos. Ian
@SkillBuilder
@SkillBuilder 10 ай бұрын
Let's hope you can get to the bottom of it.
@sunegroennebaek5283
@sunegroennebaek5283 3 жыл бұрын
Perfectly understandable. Thank you very much 😊😎🇩🇰
@steved5627
@steved5627 3 жыл бұрын
Very useful information. Do you have a video covering a constant low level hum from a SSE 330 boiler - even when the CH and HW are off (at night)? Thanks
@patrickmulholland1840
@patrickmulholland1840 2 жыл бұрын
EXCELLENT EXPLAINATION THANKYOU
@robertelliott6280
@robertelliott6280 Жыл бұрын
Very helpful, thanks.
@davidknight4096
@davidknight4096 3 жыл бұрын
Great content, keep it coming
@paulthomas4701
@paulthomas4701 2 жыл бұрын
Its only been like that for 8 years! We thought we were going crazy or the controls kept losing connection. Our underfloor heating warms the tank and our immersion cooks the underfloor heating. The pipe work looks a little more complex, but I can see the returns are fighting in an equal T. Thanks
@buggalugs
@buggalugs 3 жыл бұрын
solid information yet again :)
@harveysmith100
@harveysmith100 3 жыл бұрын
Very clear explanation Roger. I had this problem but with a different outcome so I will share it to help others. Rads getting hot when the heating was off but hot water on. Checked the motorised valve, all working correctly, even changed it, still no solution. Used my laser thermometer to see that the three port valve wasn't sealing. The rubber ball in the valve had just deteriorated and was allow some bypass. Changed the three port and the problem was solved.
@SkillBuilder
@SkillBuilder 3 жыл бұрын
That is a good idea to use the infrared thermometer. I did mention the motorised valve but dimissed it a bit, I should have given it more emphasis. Thanks for providing a bit of balance.
@harveysmith100
@harveysmith100 3 жыл бұрын
@@SkillBuilder To be honest, I have never come across it before and never thought it could be the valve. It took three visits, a lot of head scratching, half a dozen cups of tea and a fair few hobnobs.
@martynlaverick3405
@martynlaverick3405 Жыл бұрын
Brilliant! Thank you.
@MAMDAVEM
@MAMDAVEM 3 жыл бұрын
Excellent timing for me Roger, I'd planned to replace my 3-valve this week to solve this exact problem and now I'm wondering if the problem is as you described. thanks!
@SkillBuilder
@SkillBuilder 3 жыл бұрын
If it has stopped then it is the valve. I think I unwitingly gave the reverse circulation too much weight. Thge important thing is that there is a simple way to find out which problem it is.
@george9710
@george9710 Жыл бұрын
This is really good thank you!
@em8969
@em8969 Жыл бұрын
Excellent video mate
@Georger392
@Georger392 2 жыл бұрын
Thank you 🙏
@mickcarter670
@mickcarter670 3 жыл бұрын
Brilliant Roger 👍🏼
@TYLERCONSTRUCTION
@TYLERCONSTRUCTION 3 жыл бұрын
I learn a lot from these videos. In fact, I learn a lot from all your videos. Cheers Roger 👍
@peterdavies2847
@peterdavies2847 2 жыл бұрын
Now I understand. Thanks for posting.
@royster3345
@royster3345 3 жыл бұрын
Great explanation, have this problem, rads get a little warm when just HW on, installed by a professional as well....!
@SkillBuilder
@SkillBuilder 3 жыл бұрын
Some professionals don't know about reverse circulation. It is taught at college but not everyone goes to college.
@zali1049
@zali1049 Жыл бұрын
Thank you for the really useful videos. I had reverse circulation on my downstairs radiators. This was resolved my fitting a non- return valve. However the issue now is that when i have both the Heating and Hot water on at the same time, the downstairs radiators are not warming up? Any ideas what it could be? Could it be there is too much resistance because of the non return valve?
@factsoverfeelings9228
@factsoverfeelings9228 2 жыл бұрын
Perfect explanation. Theres a reason for everything ... when someone like you can articulate that it makes the world a better place. Now time to find that out of place T, on the return from the cylinder. My heat is on in my home, and the thermostat is off. Im thinking to myself, WTF?! Def. subscribing
@leerolfe5332
@leerolfe5332 3 жыл бұрын
Roger. Been around construction all my life coming from a building/construction family. Decided on plumbing as my profession. If i'd of had you as a mentor I'd of taken half the time to learn the knowledge. Took me a few years to grasp this particular fault find after my apprenticeship! Amazing explanation.
@TheD7035
@TheD7035 Жыл бұрын
Thanks Great video! our gravity fed Y system (with cyl) is a you have described, but has a small lock shield valve quarter to half turned on on the cyl pipe return to the boiler. The return pipe is in the correct place as you describe but I understand the addition of a lock shield valve also helps slow down the heating water in the cylinder coil so that the water in the coil is not going too fast as to "whizz" through the cyl and therefor heats the water as effectively as it can. I believe that the lock shield addition on the pipe return from the cyl also means the boiler should not receive back cyl coil water that is perhaps still too hot. NB. I'm Just in the process of tidying up the wiring centre (this is has been been a mess) with the larger Salus wiring centre ready for Hive to work on Home Kit. ( Grundfos UPS3 pump is set to Prop Pressure & working fine) Thanks again great video explanation.
@CrowdControl2K8
@CrowdControl2K8 Жыл бұрын
I had this in a house in London. Radiators were hot when the boiler was switched off. Eventually I found the pipes going to the tenants house. The landlord had connected his radiators to his tenants house next door.
@SkillBuilder
@SkillBuilder Жыл бұрын
That is a new one on me but I did see a flat in a conversion block that was using the neighbour's gas supply.
@zjzozn
@zjzozn 3 жыл бұрын
Nice one Dave 👍
@casinodelonge
@casinodelonge Жыл бұрын
Really interesting, thank you.
@jimcameron4672
@jimcameron4672 3 жыл бұрын
Excellent
@ajskilton
@ajskilton 3 жыл бұрын
Roger, may I ask a question please? I've built an extension that I would like to run the GCH from the house to. I may need a bigger boiler but that's another issue. My question is could I take the extension return directly into the boiler return, close to the boiler, and the hot feed for the extension from the house radiator circuit feed? Thank you and thanks for this video. Anthony
@ajskilton
@ajskilton 3 жыл бұрын
This video may actually answer my question??
@5ThingsI
@5ThingsI 2 жыл бұрын
Have this same issue but only with my living room radiator. I’ll give this a go!
@livingladolcevita7318
@livingladolcevita7318 3 жыл бұрын
any chance you could do a film about under floor heating converting normal radiator heating system if indeed this is possible
@573mughal
@573mughal 2 жыл бұрын
I have just got the same problem, atleast I have got an idea 💡 what would be the problem. Now I know what is the solutions. Thank you for making knowledgeable video. Blessings
@timmonaroman7618
@timmonaroman7618 Жыл бұрын
appreciate it I have the opposite my CH is coming on when I put on the HW only It is not reaching the temp I would expect of 60 to 65deg c but only 54 deg c and no more Preumably because the rads are taking its potential to I keep trying to fix this to no avail Mr Bisby may i ask one thing😊 my HW cylinder return is 22mm buthas been reduced to 15mm and I do not think its connected to the return There is a H piece 22mm twin pipe connected to CH side but one of the pipes has an offset 15mm to the 15 mm pipe that is where it connects Could you help me identify the 15mm pipe if its the boiler return or a CH return and how do I find the primary return
@steviebye1
@steviebye1 3 жыл бұрын
Thanks for another great video, I have this problem but I have a combi boiler. Any ideas?
@SkillBuilder
@SkillBuilder 3 жыл бұрын
It will be the divertor valve in the boiler that is letting by.
@grotekleum
@grotekleum 3 жыл бұрын
Even with the rads all tee'd before the primary return is there still not the chance of the water working back some, or would there be some sort of back pressure preventing it. Would it be reasonable to put a one-way valve in too, above the tee, but before the tank return?
@fred5095
@fred5095 3 жыл бұрын
Hi this has just started with mine. I have a combi boiler with a mega flow system and I have switched off the heating but have kept the hot water on a schedule. Now when the hot water comes on the heating comes on as well. The heating comes on at full blast. Does this mean my motorised valve need replacing?
@bredahancock2692
@bredahancock2692 3 жыл бұрын
Hi Roger, we have a baxi 428 combi and the central heating flow pipe gets very hot when the hot water is on even though the heating is off. Should this happening? If not, what would be the cause please? I did have a baxi engineer out as I felt the hot water wasn’t as hot as it used to be but he just said the weather is colder and dismissed my concern over the CH pipe getting hot. Any advice would be appreciated. Thanks
@adriatikqypi9356
@adriatikqypi9356 3 жыл бұрын
Brilliant video
@SkillBuilder
@SkillBuilder 3 жыл бұрын
Thank you
@DjSkipAlexander
@DjSkipAlexander 6 ай бұрын
Thanks
@steve45678
@steve45678 3 жыл бұрын
I'm going to start a campaign, to get you back on LBC radio " helps at hand phone in". Your brilliant and always liked listening to LBC when your radio show was on . Do you also remember the name of a motoring expert that was on LBC at roughly same time as your show? I think his first name was Gerrard?.
@SkillBuilder
@SkillBuilder 3 жыл бұрын
Thanks but LBC will never revive that show. They are now purely political and it works for them. The motoring expert is Gerrard Sauer. I was in touch with him recently, a brilliant, brilliant man.
@steve45678
@steve45678 3 жыл бұрын
@@SkillBuilder Many thanks for your reply.
@shaunglendinning
@shaunglendinning 3 жыл бұрын
Great piece of advice Roger! Appreciated. Cheers.
@berryj.greene7090
@berryj.greene7090 2 жыл бұрын
Bravo! Another nice video. Honest & true. Thanks. Yes now that you have reminded me I have heard about this reverse flow phenomenon. There's another similar possibility isn't there? To do with the header tank feed thermo-siphoning. So you feed it in BELOW the return from a sort of U bend so that the heated water cannot rise. Anyway my heating has worked fine for 17 years but this Summer the rads are getting slightly warm when there is a HW demand, I thought it must be the valve. But is it the ball or the motor? Should I bite the bullet and replace both bits of it? Can the ball be fixed in any way? Why would it get stuck or not seat?
@LockMonster
@LockMonster Жыл бұрын
I have two 2 way motorised valves, both brand new, when i want just hot water, they radiators heat up, any ideas, both valves are working ok.
@gazz4898
@gazz4898 2 жыл бұрын
Hi, great video; would this problem occur If an extra radiator has been installed and that one is the only rad getting partially warm when the hot water is regenerating? Kind regards
@1908FD
@1908FD 3 жыл бұрын
I have this problem really great to understand why! My DIY solution - the radiator closest to the cylinder I switch off in summer seems to stop the reverse flow.
@SkillBuilder
@SkillBuilder 3 жыл бұрын
That will work in most cases and with TRVs they will close in the summer anyway.
@ladypenelope99
@ladypenelope99 3 жыл бұрын
Rog knows his stuff! 👍🏻🙂
@ButterFly-jm2fb
@ButterFly-jm2fb Жыл бұрын
October now. New boiler fitted in 3 floor house by Brit Gas last month. When heating goes off, top floor rads v hot. Same floor as emersion tank. Initially top floor rad long to heat. Now the opposite. Rads had power wash. Something stuck? What's the problem, do you think? Advice appreciated!
@safeer4567
@safeer4567 Жыл бұрын
Hi roger Great channel and video If i just have one radiator getting hot on the first floor when boiler on the ground floor how do i solve the issue ? Will i still need to lift boards to access pipework ?
@greenj1m
@greenj1m 3 жыл бұрын
Hi Roger, great channel. Only thing I do different is run the heating to define flow and returns after I've witnessed the problem with just the hot water on. If the same pipe gets hotter it's the valve leaking, if the other one does it's reverse circulation.
@SkillBuilder
@SkillBuilder 3 жыл бұрын
Jim Good way of explaining it but the same idea just the other way of coming at it.
@brianobrain8985
@brianobrain8985 2 жыл бұрын
Thanks for that. I've been going crazy for the past week trying to understand what is going on with this three-way valve and Honeywell actuator on my heating system.
@misshayirhayir2390
@misshayirhayir2390 2 жыл бұрын
The same thing has happened to me
@johnymingle
@johnymingle 2 жыл бұрын
Great video, Im an amatuer but I thought the pump in the airing cupboard pumped it one way? so i don't understand!!...Also, does the 3 port valve let the hot through to the radiators when the flow is reversed, hence the heating on when I don't want it. I'm not sure which way my flow was at the radiators so i can't test by feel. i've replaced the 3 port valve motor following your tutorial and the problem came back after a while so i replaced the pcb and still got the problem.....could it be the internals of the valve body itself sticking open? would appreciate any help.
@easywatching
@easywatching 2 жыл бұрын
Very good content
@Brown969
@Brown969 3 жыл бұрын
What about bypassed towel radiators? Have come across this when towel radiator heats both on Hot Water and Central Heating. Is that still an acceptable installation technique?
@SkillBuilder
@SkillBuilder 3 жыл бұрын
Yes that summer operation of a towel rail is still common on stored water systems. It is hard to achieve with a combi so an electric element is placed in the towel rail.
@sutteren
@sutteren Жыл бұрын
nice video, thx :)
@mfr58
@mfr58 Жыл бұрын
Great advice, as an amateur I would have thought just of the 3 way valve. However what I would say is that if this problem suddenly occurs some time after installation, I would think it unlikely the install problem that you describe as it would have been like it from the start....No?
@TheD7035
@TheD7035 Жыл бұрын
Just a thought to bear in mind perhaps there could have been a build up of magnetite some where inside the system near or at the three port valve / pump etc causing some obstruction / sticking if it's years after installation. May be Check with a magnet if you can on the copper pipe. Apparently Sentinel X100 or similar is supposed to help reduce magnetite build up esp with a Magnetic type "filter" regularly flushed or cleaned... as I say just a thought! 😀
@semerson2765
@semerson2765 3 жыл бұрын
Good one Roger 👍🏼 My shower mixer doesn’t go completely cold on the coldest setting. Is that likely to be design or installation error?
@SkillBuilder
@SkillBuilder 3 жыл бұрын
I also like a cold shower. You need to callibrate it. Usually it is a case of taking the knob off and moving the stops.
@vanderpant2116
@vanderpant2116 3 жыл бұрын
Your're a master 👍
@karlosh2422
@karlosh2422 2 жыл бұрын
Brilliant. Makes sense to me :)
@RandomRoshProduction
@RandomRoshProduction Жыл бұрын
well done
@clemprice1501
@clemprice1501 3 жыл бұрын
Hi Rodger Great informative video as always. I also have this issue but with my combi boiler which was only installed a year ago is there any different issues with this or is it a case where as you mentioned they have joined the return in a similar place ? Thanks
@SkillBuilder
@SkillBuilder 3 жыл бұрын
Clem It won't be this issue with your combi. Does it happen when you are running the hot tap or after the hot tap is turned off?
@clemprice1501
@clemprice1501 3 жыл бұрын
Skill Builder when I’m running the hot water
@Richard-ij8ge
@Richard-ij8ge 3 жыл бұрын
@@SkillBuilder it is most likely a problem with your combi boiler. The boiler has a diverted valve also which can get jammed between heating and hot water. Also your plate heat exchanger could be full of debris/sludge forcing water down your heating circuit.
@stewartcross9939
@stewartcross9939 2 жыл бұрын
FANTASTIC nice and simple I also had a run in with British Gas 6 engineers came round still could fix my problem they couldn’t run a bath shame the is not enough good plumber like yourself. Great videos 👍👍👍👍
@doncodman913
@doncodman913 3 жыл бұрын
Many thanks . will look for that now, Bloody hate it when rads get hot when not needed. rgds Don
@ryanogden5895
@ryanogden5895 3 жыл бұрын
Nice vid. Be even better if you did a loft opening enlargeing video lol. Keep em coming
@simonstones1918
@simonstones1918 3 жыл бұрын
Thanks roger, you’re such a generous man....👍
@SkillBuilder
@SkillBuilder 3 жыл бұрын
That isn't what my wife says.
@simonstones1918
@simonstones1918 3 жыл бұрын
Skill Builder that’s cause you spend more time with us knowledge-hungry “builders”, roger! Get the white board out and show her in doors how you’re gonna spend more time with her, starting with a little trip to brighton 😎
@colincowell8148
@colincowell8148 3 жыл бұрын
Many thanks for explaning this problem,as I have a recurring problem with my central heating that I can not sort, Hopfully I will come across it in one of you blogs,
@SkillBuilder
@SkillBuilder 3 жыл бұрын
Colin You can tell us the problem by going to the contact Skill Builder and I will do my best to help. If it is a good subject for a whiteboard I will do one.
@colincowell8148
@colincowell8148 3 жыл бұрын
Hi threre, The problem I have is I dont think that the Pump is powerful enough to pump water through the ground floor radiators ,As I have to switch the pump up to top speed to get them to warm up,I also suspect that the room stat is not talking to the Boiler and am about to replace it,the zone valve is working,but to get the heating to work I am using the Hot water Cylinder Belt thermostat to run the heating which heats the hot water in the taps and make it too hot. Any advise would be of great help.
@wallypreston-kk9rs
@wallypreston-kk9rs Жыл бұрын
I have had problems with my entrance heating. I have had 3 new 3 valve changed. I think it is now, after looking at our youtube I think it is revers circulation problem? My question is could you just change around the valves on the radiators? I had a new boiler and tank fitted 2 years ago. Can you give me some advise?
@wanderer6688
@wanderer6688 3 жыл бұрын
Hi Roger, thanks so much. Our radiators do this but they get absolutely boiling hot in the summer not just warm, would it be the same issue ? It’s a new renovation so all pipework is new. I’ve had the plumber look at it but he couldn’t find anything wrong. Split system our underfloor heating downstairs is fine but all radiators on the 2nd thermostat system do it.
@SkillBuilder
@SkillBuilder 3 жыл бұрын
Most likely this will be the case but you need to check by feeling the pipework and seeing which way the water runs.
@dominiclogue5924
@dominiclogue5924 25 күн бұрын
very good
@lazylad9064
@lazylad9064 3 жыл бұрын
Excellent diagram and explanation of what can or might be problems. Thanks Rodger a little bit of knowledge is better than none👍👍👍
@jamestranter2151
@jamestranter2151 Жыл бұрын
Great video I have this exact issue but only 1 radiator getting hot in the hallway instead of all of them…..could it still be this issue that you have explained?
@oharepd
@oharepd 3 жыл бұрын
Excellent video. One question I have is that we have a loft conversion and the radiator in the bedroom in the loft conversion gets hot when the hot water turns on, but no other radiators do in the house (they get hot when heating is on). Is it possible that this problem can effect just one radiator?
@SkillBuilder
@SkillBuilder 3 жыл бұрын
Hi Paul It can sometimes short circuit around one rad. It is likely that the plumber saved having to run a pipe right back to the source or that it was intended.
Get More Heat From Your Radiators ~ System Balance
16:36
Skill Builder
Рет қаралды 943 М.
He sees meat everywhere 😄🥩
00:11
AngLova
Рет қаралды 11 МЛН
Became invisible for one day!  #funny #wednesday #memes
00:25
Watch Me
Рет қаралды 53 МЛН
THE POLICE TAKES ME! feat @PANDAGIRLOFFICIAL #shorts
00:31
PANDA BOI
Рет қаралды 24 МЛН
How to Change a Thermostatic Radiator Valve Without Draining The System
14:53
This is Why Heat Pumps May NOT Be The Future
13:12
Skill Builder
Рет қаралды 2,3 МЛН
The Surprising Fact About Many London Buildings
21:55
Skill Builder
Рет қаралды 212 М.
How to Repair a Motorised Central Heating Valve
12:01
Skill Builder
Рет қаралды 459 М.
How to Fix a Cold Radiator 4 Easy Ways | DIY Plumbing
11:52
The DIY Guy
Рет қаралды 1,2 МЛН