System short cycling, not keeping up, very high electric bill, and extremely high head pressure.

  Рет қаралды 31,627

HVAC GUY

HVAC GUY

Күн бұрын

System was going out on high head pressure. I washed coils, and thought I was done, but head pressure kept climbing, and temp drop never got above 11 degrees. I eventually settled on replacing TXV
#hvac
#hvaclife
#txv

Пікірлер: 65
@andydavis3739
@andydavis3739 3 жыл бұрын
I found that the micros are charge sensitive. Same issues. Ended up removing 10 ounces and brought the pressure's to livable. Micros need to stay in autos not HVAC
@countryfriedhvac
@countryfriedhvac 3 жыл бұрын
I haven’t seen a TXV cause insanely high head pressure like that. Usually liquid line restrictions don’t allow for return gas to the compressor so there is actually nothing for the compressor to compress to cause head to continue to climb. I would deep clean that coil and ensure proper airflow from the condenser fan.
@sknight0391
@sknight0391 3 жыл бұрын
One of our technicians had the exact same unit with the exact same problem 2 years ago. He replaced the TXV and it still didn't work. I went out there and found the problem was actually the indoor coil (micro channel) was completely slammed. To look at it it didn't look that bad. But once I started back spraying it from the blower side down, you would not believe this stuff that come out of it. The plugged coil was dropping the low side pressure so much that the other technician just kept dumping gas into it trying to get the pressure up and it ended up being 3 lb overcharged. The key here is.... Both coils are micro channel. That system probably only holds 4 lb and a few ounces. When you're dealing with a system that has micro channel coils inside and out you have to think of the charge in ounces instead of pounds. A few ounces of refrigerant can make the same difference that a pound of refrigerant would make in a system with regular plate fin coils. I think you should try heavily cleaning both coils (especially the evaporator), remove the entire charge, vacuum the system and weigh the refrigerant back in according to the data plate. 😎👍
@HVACGUY
@HVACGUY 3 жыл бұрын
Appreciate the advice.
@jman0870
@jman0870 3 жыл бұрын
He didn’t know what subcooling was? NEVER. EVER. EVER. Charge by suction pressure. Rookie mistake. Your guy needs a lesson on checking charge 🤣
@holtrussell
@holtrussell 3 жыл бұрын
Sounds like a winner approach!
@jeffreywhitlatch1409
@jeffreywhitlatch1409 3 жыл бұрын
It sounds good to me what you say, because txv works off of suction pressure.
@jman0870
@jman0870 3 жыл бұрын
@@jeffreywhitlatch1409 No...they don't. Spring pressure and suction pressure close the valve. Bulb pressure opens the valve. Airflow issues causes your saturation temp to plummet so the TXV closes down due to the bulb pressure dropping, sometimes far enough that you will see a very low suction and high superheat at the outdoor unit. The superheat at the evaporator outlet, however, will be proper. Airflow issues show up in your subcooling. When your TXV closes down you stack liquid in the condenser and your subcooling will go up. When you dump charge in because your suction is low your subcooling will skyrocket. First rule of troubleshooting is make sure everything is clean.
@HVACSteve951
@HVACSteve951 3 жыл бұрын
Remember when you have a micro channel condensing coil, you must blow the water out of the channels after cleaning because it will hold water inside the channels and cause super high head pressure.
@bobgallo2178
@bobgallo2178 3 жыл бұрын
Before you go replacing anything, try cleaning the condenser coil from the inside out.Could be a cheap fix.
@jman0870
@jman0870 3 жыл бұрын
High subcooling is always an overcharge. I’ve never seen a high pressure switch fail closed before. That’s kind of crazy. If I find a unit running crazy high subcooling I immediately go into “Some dipshit misdiagnosed a bad TXV and charged by suction pressure” mode. I just did one a couple weeks ago. Unit was running a slightly low suction, 30 degrees of superheat, and 30 degrees of subcooling on a circuit that should run 10. We are slammed and I didn’t troubleshoot any further. Replaced the TXV, found the unit grossly overcharged, and upon disassembly, the push rod was 100% stuck in the TXV due to oil breakdown.
@edwardgarza5104
@edwardgarza5104 2 жыл бұрын
Replacing TXV and adjusting the charge repaired your issue?
@jman0870
@jman0870 2 жыл бұрын
@@edwardgarza5104 yes. Someone charged it by suction pressure because the rod in the TXV was bound from sludge. It will happen again though. I don’t go out of my way to clean the system up for customers who intentionally run their equipment until the condensers are completely impacted. New TXV, drier, and a fresh charge. Whatever shit is floating around in the system from oil breakdown is still in there. 🤷‍♂️
@johnwalker890
@johnwalker890 3 жыл бұрын
Good job Curtis.
@donnierobertson3088
@donnierobertson3088 3 жыл бұрын
Nice job and video like always
@vitoplower1119
@vitoplower1119 2 жыл бұрын
Have you figured that out yet? 6 years old - could be one of those Copeland compressors oil with coagulant from 2014-2015 clogging up txv
@Chris2745100
@Chris2745100 3 жыл бұрын
TXV only lasted 6 years? Its an expensive part to replace...
@lancelawrence3259
@lancelawrence3259 3 жыл бұрын
Nice work
@arcticarrowhvacr
@arcticarrowhvacr 3 жыл бұрын
I wish the micro channel commercial/residential packaged systems didn't have a condenser guard that way you could slap the coil and knock the water loose. Anyways, Rheem and their damn typical TXVs!
@KB-wq5bb
@KB-wq5bb 3 жыл бұрын
I had one like that couple weeks ago but install crew had just installed a new coil
@wata_laf
@wata_laf 3 жыл бұрын
Maybe I’m not following the piping close enough but did you put your liquid line temp clamp on the outlet side of the metering device?
@chrissipple1018
@chrissipple1018 2 жыл бұрын
Please explain what your doing and what delta t. condenser or evaporater.
@Dontleavemedimi
@Dontleavemedimi 6 ай бұрын
Good content. Could it be overcharged if your head pressure is too high. Clogged filter drier.???
@BYENZER
@BYENZER 3 жыл бұрын
I was screaming at my monitor, "ICE!! ICE!!! Moisture in the system! Frozen ICE is inside the TXV"! SUCK it down and get that moisture out. Oh well, since you replaced the TXV, you had to suck it down it anyway. Now they have a brand new TXV. Not a bad thing. Too bad that HI-Pressure switch is shot. She won't short cycle now!!
@HVACGUY
@HVACGUY 3 жыл бұрын
I haven’t replaced TXV yet
@holtrussell
@holtrussell 3 жыл бұрын
Noncondensables thought did cross my mind.
@richardbartlett6932
@richardbartlett6932 3 жыл бұрын
Ice at those pressures..?
@BYENZER
@BYENZER 3 жыл бұрын
@@richardbartlett6932 YES! An ice dam can hold back over 25,000 psi. Each time the ice, inside the TXV, melts and reopens a pin hole for refrigerant flow, the temperature re-drops below freezing and a new ice dam re-plugs the hole.
@BYENZER
@BYENZER 3 жыл бұрын
@@richardbartlett6932 But, who knows, it could simply be F.O.D., (Foreign Object Dam), blocking the TXV's orifice hole. Or the TXV sensing bulb has leaked and is kaput. Or the TXV pintle is stuck closed from C.O.D. (Copeland Oil Crud). Who knows.
@Eddy63
@Eddy63 3 жыл бұрын
Good vid ...
@Falcon-eh8tq
@Falcon-eh8tq 3 жыл бұрын
Nice video thanks for posting! did you try shocking the TXV sensing bulb? I like to put it in ice water for 5 minutes and then in the palm of my hand for 3 minutes and see what that does to the pressures. On new TXV's i try to never completely front or back seat the adjuster, as that's just asking for it to stick in 10 years, IMHO.
@HVACGUY
@HVACGUY 3 жыл бұрын
No, I didn’t try that.
@jman0870
@jman0870 3 жыл бұрын
You should never need to front or back seat a TXV spring adjustment. If you do, the TXV is junk. Your rod is sticking due to oil breakdown or debris.
@LadariusCapersOfficial
@LadariusCapersOfficial 3 жыл бұрын
@@HVACGUY is it a rheem package air conditioner
@Falcon-eh8tq
@Falcon-eh8tq 3 жыл бұрын
​@@jman0870 Right, that's true my intent was to say a TXV should never be left in front or back seat position, It will stick, and imho some TXVs ARE just straight up junk, more moving parts, I work on residential AC often so if practicable i switch to piston w manufacturer information
@jman0870
@jman0870 3 жыл бұрын
@@Falcon-eh8tq TXVs are incredibly reliable...I don't know where you got your information. The number one killer of TXVs is oil breakdown outside of installation errors. I don't know why you would ever set a TXV fully front or back seated. If you have to adjust one that far it needs replaced because it's stuck and you are effectively operating it as a piston or it is the completely wrong tonnage range/body type/powerhead type. Maybe you are still stuck in the time period where Copeland put a corrosion inhibitor in their compressors without telling anyone and it was gumming up TXVs?
@billhill839
@billhill839 11 ай бұрын
When you come across a system with those symptoms, the FIRST thing you do is check and/or clean the coils.
@jaimegonzalez6926
@jaimegonzalez6926 Жыл бұрын
TX filter clogged
@khx73
@khx73 3 жыл бұрын
How did it get that high over 500 and not go out on high head pressure?? Yikes
@HVACGUY
@HVACGUY 3 жыл бұрын
Tell me about it. That was worrisome.
@khx73
@khx73 3 жыл бұрын
@@HVACGUY Well, if nothing else, a great pressure test for a micro channel coil. 700 psi though.. damn
@jman0870
@jman0870 3 жыл бұрын
410a high pressure switches are commonly set at 575-600, that’s how 😂 410a sucks.
@profuse007
@profuse007 2 жыл бұрын
You swinged the temp probes 19 times total.... lol
@realestateservicessaleshea99
@realestateservicessaleshea99 3 жыл бұрын
6 years old ,it should still be under warranty? Did you give the txv the old tap-a-roo Can't wait for the video of the replacement. 🍺🍺🍺🥃🥃🍿🏌🏻‍♀️ Stay safe. Retired (werk'n) keyboard super tech. Wear your safety glasses.
@HVACGUY
@HVACGUY 3 жыл бұрын
It was registered, so yes it is under warranty.
@TheDeadheadable
@TheDeadheadable 2 жыл бұрын
Why are you washing the coils backwards? Pushing that shit into the coil and helping at all.
@stephenmsellers5287
@stephenmsellers5287 Жыл бұрын
Do you charge for cleaning coils
@marknovak6228
@marknovak6228 3 жыл бұрын
Coil clean?
@db4239
@db4239 3 жыл бұрын
Hope you found your knife!
@HVACGUY
@HVACGUY 3 жыл бұрын
No, it’s lost somewhere. But, I found an electrician hook knife made by Milwaukee at HomeDepot for $15. Good price, I’ll be trying it out.
@steveblake8766
@steveblake8766 3 жыл бұрын
#31 thumbs up
@stephwaylonwells3218
@stephwaylonwells3218 3 жыл бұрын
First 👍😎👍
Air Conditioner Not Keeping Up!
12:31
HVAC GUY
Рет қаралды 33 М.
System short cycling on Saturday evening
7:33
HVAC GUY
Рет қаралды 39 М.
managed to catch #tiktok
00:16
Анастасия Тарасова
Рет қаралды 46 МЛН
هذه الحلوى قد تقتلني 😱🍬
00:22
Cool Tool SHORTS Arabic
Рет қаралды 44 МЛН
Yum 😋 cotton candy 🍭
00:18
Nadir Show
Рет қаралды 7 МЛН
Do Line Restrictions Cause High Head?
7:31
HVAC School
Рет қаралды 81 М.
LENNOX PACKAGE UNIT HIGH HEAD PRESSURE
19:12
HVACR VIDEOS
Рет қаралды 50 М.
No Cooling, Low Pressure Control Open, Finding out Why
7:31
HVAC GUY
Рет қаралды 26 М.
High Pressure, Cause and Effect. EP28
7:54
Nighthawk HVAC
Рет қаралды 11 М.
Top 5 Things AC Companies Don't Want You To Know How To Do!
12:40
How To Home
Рет қаралды 2,3 МЛН
Heat Pump System Short Cycling
5:16
HVAC in SC
Рет қаралды 32 М.
Refrigerant Overcharge Troubleshooting and Prevention
21:47
HVAC School
Рет қаралды 178 М.
Diagnosing Poor Compression
13:53
HVAC School
Рет қаралды 76 М.
Multi-zone split type Air Conditioner installation
16:49
craftsman tv
Рет қаралды 383 М.
3 Things HVAC Contractors Don't Want You To Know About.
13:17
The DIY HVAC Guy
Рет қаралды 2,2 МЛН
managed to catch #tiktok
00:16
Анастасия Тарасова
Рет қаралды 46 МЛН