The 3 Pillars of Daikin Service Checker Analysis

  Рет қаралды 8,996

Roman Baugh

Roman Baugh

Күн бұрын

Пікірлер: 77
@relaxalate
@relaxalate Жыл бұрын
Really good video . DSH is a new item I’ve been running into on VRV and Daikin applied equipment. This really helped me bridge my knowledge gap , thank you!
@jeffendrulat3530
@jeffendrulat3530 Жыл бұрын
Thanks Roman..... Best 20 minutes that I spent today!
@sameerpremlall8124
@sameerpremlall8124 Жыл бұрын
Hi Roman, this is brilliant. Thank you for the content. I started service checker analysis about a year ago when I started working at Daikin and it took me a while to get the hang of it. I've gotten alot better at it but this video hear made so much sense. Thank you once again. Keep the videos coming 💪
@sameerpremlall8124
@sameerpremlall8124 Жыл бұрын
One other question, the parameters that you speak about is all in degrees Fahrenheit correct ?
@platinumhvacrtechnologies457
@platinumhvacrtechnologies457 Жыл бұрын
Yes in ⁰F
@po65231r
@po65231r Жыл бұрын
Is he not talking about k so should still be the same amount if deg c or F ??
@johngrayer7773
@johngrayer7773 Жыл бұрын
@@po65231r Hey mate, K doesn't relate to F at all, K is absolute C, so if a water chiller (for example) has 12C entering and 6C leaving water temperature, this could be expressed as 6K of duty (12-6). 0K = -273C (absolute zero), 273K = 0C, 373K = 100C and so on. Cheers.
@epicone2449
@epicone2449 Жыл бұрын
More videos please. Good job 👍🏼 I thought VRV 3 and VRV 4 have different ranges in permissible values
@RomanBaugh
@RomanBaugh 7 ай бұрын
No same ranges as they share similar compressors.
@christopherhughes2482
@christopherhughes2482 Жыл бұрын
Excellent video!
@platinumhvacrtechnologies457
@platinumhvacrtechnologies457 Жыл бұрын
Roman this is great keep the videos coming especially on vrv
@hvacgirlo
@hvacgirlo Жыл бұрын
Brilliant information Roman. Thanks so much
@nguyennam880
@nguyennam880 Жыл бұрын
Looking forward to you sharing your knowledge related to data analysis checker. Thanks you.
@RomanBaugh
@RomanBaugh 7 ай бұрын
The wait is over
@jasonjohnsonHVAC
@jasonjohnsonHVAC Жыл бұрын
Outstanding video and explanation
@guuuuustaf
@guuuuustaf 7 ай бұрын
Great explanation!
@RomanBaugh
@RomanBaugh 6 ай бұрын
Glad it was helpful!
@ping_me1vp
@ping_me1vp Жыл бұрын
That's soo excellent thanks a million
@omegma87
@omegma87 Жыл бұрын
Thank you.
@americanpatriot9942
@americanpatriot9942 Жыл бұрын
Can we use this same method with all vrfs systems? Thanks in advance also great info god bless!
@johnchiarello1375
@johnchiarello1375 Жыл бұрын
Great video
@HVACR_VINYLS
@HVACR_VINYLS Жыл бұрын
Hey Roman. When I’m using my service checker on a VRV 4. I have noticed the eev pulses have 2 sets of data. Eg it has upper heat exchanger eev pulses, and then upper heat exchanger eev US pulse. What does the US dictate? I don’t use it in my diagnosis, I’m just curious to what it refers too.
@RomanBaugh
@RomanBaugh Жыл бұрын
Yes there are two different sets, however do not us the (US) valve pulses as they are not for our market and will be misleading.
@HVACR_VINYLS
@HVACR_VINYLS Жыл бұрын
@Roman Baugh thanks legend. Appreciate it
@prowesstv
@prowesstv Жыл бұрын
Bro got me locked in for the deep dive then only has two videos 😅😅
@RomanBaugh
@RomanBaugh 7 ай бұрын
The wait is over
@BleedingEdgeHVACR
@BleedingEdgeHVACR 2 ай бұрын
Sorry I’m confused is discharge superheat calculated by taking Discharge line temp-Discharge sat temp or Discharge line temp-Liquid sat temp?
@joshuavaldez4094
@joshuavaldez4094 Жыл бұрын
Great info 👍 👌
@Didik-cq8wy
@Didik-cq8wy Жыл бұрын
Trimaksih bos
@user-wz6fw5sm7f
@user-wz6fw5sm7f 11 ай бұрын
Hi Roman, great video could you advise of these figures you refer to in deg C i.e. DSH range (27 to72), SSH range (3.6 to 32) & LSC range (11)
@RomanBaugh
@RomanBaugh 7 ай бұрын
Fahrenheit my friend
@alanwang2900
@alanwang2900 Жыл бұрын
Great video! Thanks for sharing. Are these numbers different when unit in heating mode? I always see outdoor coil iced up after the main eev, and from service checker, it shows the valve 3000 pls
@RomanBaugh
@RomanBaugh Жыл бұрын
The measurements discussed in this video are universal between all modes, however where we are measuring these temperatures changes. Measuring subcooling in cooling mode is using different temperature measurement locations than in heat mode.
@alanwang2900
@alanwang2900 Жыл бұрын
@@RomanBaugh thanks, hope you could do a video the troubleshooting when unit is in heating mode. 🙏
@garypoplin4599
@garypoplin4599 4 ай бұрын
1:34 - Where do you put your probes to get the numbers for calculating discharge superheat? My understanding of the discharge superheat calculation is discharge line temperature less liquid line pressure (converted to temperature). Is that right?
@RomanBaugh
@RomanBaugh 2 ай бұрын
Discharge superheat is measured using discharge line temperature 6” down stream of compressor then subtracting it from liquid line temp converted to saturation temp. 180-110 = 70 DSH.
@shirvonseemungal7719
@shirvonseemungal7719 Ай бұрын
How do we measure subcool on a vrv
@jorgevalladares179
@jorgevalladares179 3 ай бұрын
Are the examples shown, reflect a system running on heat?
@RomanBaugh
@RomanBaugh 2 ай бұрын
Heat, Cooling, heat recovery it’s all relevant as long as you know the correct locations of where to measure these temperatures.
@mallkomoha6823
@mallkomoha6823 2 ай бұрын
Can rebroadcast the video in metric please?? I mean in degree Celsius.
@DaneSetser-nn9xc
@DaneSetser-nn9xc 7 ай бұрын
I’ve got a total of 9 systems of 4X heat recovery units. We have had multiple issues and lost compressors. Your video made me dive deep into these systems. One system in particular is running a high DSH 90-100. SSH is within range no higher that 32 sometimes drops less in five. Subcool is within range. I did an oil differential across the suction line and was getting 7F then jumped up to almost 40F. Do you have any more info. Also where did you get the 30 modes local Daikin rep doesn’t have it.
@RomanBaugh
@RomanBaugh 7 ай бұрын
Sounds like oil traps within the building. High DSH levels with normal range SSH and Subcooling means your compressors are low on oil. Sounds like piping errors or discrepancies. Meaning there are piping rules broken causing oil to become trapped in the system. Your local Daikin Rep will not have that list, as I translated it from Japanese. Daikin Japan is the only one with the list prior to now.
@DaneSetser-nn9xc
@DaneSetser-nn9xc 7 ай бұрын
Thank you I’ll start looking at the piping.
@cchurch816
@cchurch816 Жыл бұрын
Also sensors and transducers. How to verify they work right
@jorgevalladares179
@jorgevalladares179 3 ай бұрын
Without getting into the math, Daikin has two apps that can help you convert that. Daikin tech and Daikin services, it’ll convert dc voltage to pressure (vise versa) and temps to ohm (vise versa). Then get gauges or temp probes and see if they correlate.
@ashleydavies7863
@ashleydavies7863 8 ай бұрын
Are the temperature figures in Fahrenheit or Celsius? As I'm in the UK
@RomanBaugh
@RomanBaugh 7 ай бұрын
Fahrenheit good sir
@hugopalomo4222
@hugopalomo4222 Жыл бұрын
Hello Roman, could you put subtitles in Spanish? Thanks
@dcfabrication2097
@dcfabrication2097 Жыл бұрын
VRV DSH Discharge SuperHeat Discharge pipe temp - Tc ( condensing saturation temperature) Range 27-72 Below range ( overcharge) Above range ( low oil or low refrigerant) SSH Suction SuperHeat Suction pipe temp - Te ( evaporation saturation temperature) Range 3.6-32 (5-32) Below range (wet- liquid refrigerant at compressor)(overcharge or bypassing refrigerant In system) Above range ( low charge or restriction in system) SUB System SubCooling Tc - liquid pipe temp after heat exchanger(s) Range 11 +/- 3 Below ( undercharge or restriction ) Above ( overcharge or bypassing )
@RomanBaugh
@RomanBaugh Жыл бұрын
Unfortunately thats not the whole story, I will be making a video in depth of each item and all the intricacies that go with it.
@sydneyabbas7999
@sydneyabbas7999 Жыл бұрын
​@@RomanBaugh Thanks Roman fantastic video, will help a lot. Really looking forward of your next video. 👍🏼
@nguyennam880
@nguyennam880 Жыл бұрын
@@RomanBaugh Watting
@NotOurRemedy
@NotOurRemedy Жыл бұрын
@@RomanBaughare these numbers for VRV3 and 4?
@LC-qi5ff
@LC-qi5ff 11 ай бұрын
How does overcharge cause low oil in compressor?
@tom24057
@tom24057 9 ай бұрын
Flushes out oil
@RomanBaugh
@RomanBaugh 7 ай бұрын
System never runs the compressor over half speed causing velocity to be low not allowing refrigerant to bring oil back from the indoor units. Couple that with liquid flood back then compounds the issue removing any remaining oil from the compressor.
@cchurch816
@cchurch816 Жыл бұрын
But keeping them videos comming.
@marcoferreira226
@marcoferreira226 8 ай бұрын
I have a question are your Temps F or C?
@RomanBaugh
@RomanBaugh 7 ай бұрын
Fahrenheit
@Scottyboyhvacdude
@Scottyboyhvacdude Жыл бұрын
How long before you have to take this down?
@tom24057
@tom24057 Жыл бұрын
Why?
@RomanBaugh
@RomanBaugh 4 ай бұрын
Still up Scott 😂
@Scottyboyhvacdude
@Scottyboyhvacdude 4 ай бұрын
@@RomanBaugh I only say that because there's been some other helpful daikin content that was taken down. I don't understand the secrecy. We as technicians need any tools we can get, thank you!!
@guuuuustaf
@guuuuustaf 5 ай бұрын
Do you know the process of Daikin minisplit, how do they calculate evaporating temp and condensing temp. Since they do not have pressure transmitters. Only discharge probe, ev probe and condensing probes, and air thermistor probes. Do they calculate evaporating and condensing temperatures via the compressor load ampere, and also take into account the heatexchanger probes? Its bugging me for real. Hope you have somewhat of an answer.=)
@ryanbrown7134
@ryanbrown7134 5 ай бұрын
Short answer is they don’t. Thermistor data is all that is used to control the motor speeds and valve pulses. At least that’s what is taught in the mini split class.
@guuuuustaf
@guuuuustaf 5 ай бұрын
@@ryanbrown7134 Then how can they get correct sh and sc? Its been bugging me how are they actually know how to adjust the eev. Some of the data needed for correct sh, sc is unknown. They must use ampere drawn by the compressor too trying to get somewhat of correct ev pressure and condensing pressure... 😁
@ryanbrown7134
@ryanbrown7134 5 ай бұрын
@@guuuuustaf It bothered me too when I first started working on them. They don’t monitor superheat or subcooling. They may have an algorithm that determines wet operation with compressor current and discharge temp but I doubt it. Even if they did, they wouldn’t tell us anyways. Other than the logic, mini splits are very simple units.
@guuuuustaf
@guuuuustaf 5 ай бұрын
Haha okeey thank you for the answer=). may be therefore they often have two accumulator tanks beside compressor. Cause the sh cant always be 100%.They are indeed very simple. The logic as you say is the more tricky part. @@ryanbrown7134
@Jonathan-li1xh
@Jonathan-li1xh 5 ай бұрын
If the units don’t have the pressure sensor , it should have thermistor at the evap and at the condenser coil . These temperature will be used for evap temperature and condensation temperature instead pressure reading converted into sat temperature.
@cchurch816
@cchurch816 Жыл бұрын
U sound like u think all techs have basic schooling in refrigeration theory.
@epicone2449
@epicone2449 Жыл бұрын
You need to know the basics before diving into VRV. Like experienced in service on package units or split systems
@cchurch816
@cchurch816 Жыл бұрын
​@@epicone2449 looked for the dsh, sc and sh on a daikin fit heat pump couple days using the daikin btsc app. The symbols arnt matchin on the app. Reverted to just using to probes. Went after the dsh and sh in heating mode. Looked normal. Last tech suspected low charge after the tstat error history shows low pressure trip. Found the data wire was grounded at the equipment chasis and corrected it.
@andrewkozik4666
@andrewkozik4666 Жыл бұрын
Excellent video!
@buggedmechanics
@buggedmechanics 5 ай бұрын
Great video
@RomanBaugh
@RomanBaugh 5 ай бұрын
Glad you enjoyed it
Solving Refrigerant Flow Mysteries with the Daikin VRV Service Checker
18:24
How To Diagnose Daikin VRV EEV Powerhead
12:36
Mechanical Pros
Рет қаралды 4,3 М.
Parenting hacks and gadgets against mosquitoes 🦟👶
00:21
Let's GLOW!
Рет қаралды 11 МЛН
No empty
00:35
Mamasoboliha
Рет қаралды 12 МЛН
Octopus Heat Pump Survey HAS Hidden COST!
25:39
Nicolas Raimo
Рет қаралды 23 М.
The Basics of Service Checker
17:15
Roman Baugh
Рет қаралды 908
Why does an AC freeze
23:39
Love2HVAC with Ty Branaman
Рет қаралды 149 М.
Ham Clock Displays - What They Tell You
14:16
Gadget Talk
Рет қаралды 8 М.
How To Check Superheat & Subcooling On An HVAC System
16:03
The DIY HVAC Guy
Рет қаралды 106 М.
HOW TO TEST DAIKIN EEV COIL (5 Cables).
12:23
Mitch Attwood
Рет қаралды 14 М.
A2L Refrigerants R-454B and R-32 Explained! Bottles, Changes, Rules, Tools!
22:15
What goes on inside a Mitsubishi branch controller?
13:03
VrfMadness
Рет қаралды 21 М.
DAIKIN VRV FAULT ! *IT WONT WORK IN HEATING MODE !?
10:34
HVAC UK
Рет қаралды 14 М.
Parenting hacks and gadgets against mosquitoes 🦟👶
00:21
Let's GLOW!
Рет қаралды 11 МЛН