Trane RTAC Leak Repair + Oil Filter Part 1

  Рет қаралды 12,496

DFW HVAC

DFW HVAC

Күн бұрын

What could have been a pretty quick fix turned into a lengthier ordeal when isolation valves on a Trane RTAC chiller didn't hold. Leak Repair + oil filter change on screw compressor. Like, comment, and subscribe for future uploads. Will post follow up video when job is complete.

Пікірлер: 35
@twaymangaming683
@twaymangaming683 2 жыл бұрын
This guy has been running hvac for over a decade definitely a guy to watch
@dfwhvac
@dfwhvac 2 жыл бұрын
Thanks bud , back at you. Sick gaming channel
@ChingusTheOneAndOnly
@ChingusTheOneAndOnly Жыл бұрын
I’m watching, Great stuff on here , Thank you , This channel should take off soon
@AGON17
@AGON17 7 ай бұрын
I don't know how all these large commercial KZfaq accounts went under my radar til I started searching for CGAM and RTAA videos
@markcotter2355
@markcotter2355 2 жыл бұрын
good job from fellow DFW tech
@dfwhvac
@dfwhvac 2 жыл бұрын
Thanks watching ! DFW techs are bad ass 👍🏼
@niggadonthatethis18
@niggadonthatethis18 2 жыл бұрын
Great walkthrough! Great information!
@dfwhvac
@dfwhvac 2 жыл бұрын
Thanks my guy ✅
@kennethlobo4420
@kennethlobo4420 8 ай бұрын
Thanks for thus great tip to keep the chilled water pump running when on recovery mode,I know that this has to be done when breaking a vaccum.
@dfwhvac
@dfwhvac 6 ай бұрын
Yessir , recovery and charging should only been done with verified water flow on chilled water systems to prevent potential freezing issues in the tubes or heat exchanger
@user-pn8em4mo7c
@user-pn8em4mo7c Жыл бұрын
Great video man! Thanks now I feel alone more confident cleaning the oil filter.
@dfwhvac
@dfwhvac Жыл бұрын
Great to hear man and glad I can help ! They’re intimidating at first but if you have someone show you how to do it it’s not as hard as you’d think ! That’s why I make these videos
@HeavyDuty1337z
@HeavyDuty1337z 8 ай бұрын
If that was a semi I’d say oil looks like 10+ years old/or dirty system/or running hot. Pre normal for a screw chiller tho considering compression ratios, you’ll get that darker tint on the POE pre quick from the elevated DLT
@TheMaintenanceNetwork-DallasTX
@TheMaintenanceNetwork-DallasTX Ай бұрын
Keep doing your thing!
@ChingusTheOneAndOnly
@ChingusTheOneAndOnly Жыл бұрын
Great content , Thanks for posting
@dfwhvac
@dfwhvac Жыл бұрын
Thanks for watching . Been busy on a contract that doesn’t allow filming on site , but will try to get some more content out soon.
@joshstevens9826
@joshstevens9826 Жыл бұрын
Coat the entire gasket in oil , nylog, or what i use vacuum grease. Will be easier to get the gasket off next time.
@kennethlobo4420
@kennethlobo4420 8 ай бұрын
Thanks A lot enjoyed watching this video.found ur cannel accidently
@dfwhvac
@dfwhvac 6 ай бұрын
Thanks for watching
@JM-wk2tz
@JM-wk2tz Жыл бұрын
Great video I’ve never worked on chillers, always been curious as to their operation. I’ve worked mostly on supermarket refrigeration and for the most part I was able to follow along. We have oil filters and the same kind of drier cores. What would you recommend to learn more about chillers?
@dfwhvac
@dfwhvac Жыл бұрын
Read Manufacturer IOM manuals. They are usually much more detailed and in depth as far as each operation of the system when compared to regular DX cooling units. There’s also a great channel called HVAC TIME . He works on chillers a lot and is very knowledgeable
@JM-wk2tz
@JM-wk2tz Жыл бұрын
@@dfwhvac great advice thanks !
@jevonhoward
@jevonhoward Жыл бұрын
Trane has a training class specific to the RTAC chiller in LaCrosse,Wi.They spend 3 1/2 days covering everything front to back if your Company is willing to pay for it.
@bobparrott8130
@bobparrott8130 9 ай бұрын
Nice work 👍
@fkdeazevedo
@fkdeazevedo 11 ай бұрын
Is that where you add too?
@diegoandrade5953
@diegoandrade5953 Жыл бұрын
Hello, about the compressor low oil flow failure. my chiller has 2 compressors on the circuit and one of them has a low oil flow alarm. the oil level is ok. what could it be in this case?
@dfwhvac
@dfwhvac Жыл бұрын
Depends on the make and model Of the chiller and it’s components. But it could be a dirty / clogged oil filter or strainer or oil pump not operating properly if you can visibly see oil in a sight-glass
@joshstevens9826
@joshstevens9826 Жыл бұрын
Dirty co dessert coils can give you an oil alarm. Cant remember the numbers, butnif the oil temp is close enough to SAT discharge temp it will alarm on oil flow. Usually tranr uses the top couple rows of the condenser for oil cooling. So dirty coils will give you elevated oil temps
@jevonhoward
@jevonhoward Жыл бұрын
If its a RTAC, more than likely the oil filter or check valve that sits in front of the filter.The IOM has the formula to calculate the oil flow ratio.If ratio is too high you will get that alarm.Also make sure transducers are reading properly as the computer is using transducer pressures to calculate the ratio.If high ratio is confirmed, I would replace both the check valve and the oil filter since both involve pumping down and opening the system.2" deep socket needed to replace that check valve.
@jasonjohnsonHVAC
@jasonjohnsonHVAC 9 ай бұрын
Did you send the oil in for analysis by any chance
@lammaking333
@lammaking333 9 ай бұрын
No sir we did not . But we came back a month or two after this call for all the chillers on this school district and submitted oil analysis as part of the annual pm
@jasonjohnsonHVAC
@jasonjohnsonHVAC 9 ай бұрын
@lammaking333 nicely done...oil analysis is a big key to spot a potential major issue
@ajajomedia1220
@ajajomedia1220 Жыл бұрын
Is that chiller also
@dfwhvac
@dfwhvac Жыл бұрын
Yes sir , it is an air cooled chiller with screw compressors . R134A refrigerant
Trane RTAC Pt. 2 - Filter Drier, Vacuum, Recharge
23:33
DFW HVAC
Рет қаралды 10 М.
Low Oil Troubleshoot RTAA Chiller
11:24
HVACTIME
Рет қаралды 15 М.
Cute kitty gadgets 💛
00:24
TheSoul Music Family
Рет қаралды 16 МЛН
SPONGEBOB POWER-UPS IN BRAWL STARS!!!
08:35
Brawl Stars
Рет қаралды 21 МЛН
How to Leak Test an AC With Nitrogen Pressure
8:00
HVAC School
Рет қаралды 226 М.
Comparing & Testing Several Valve Core Removal Tools
29:01
Reliable HVACR
Рет қаралды 17 М.
Chiller Shaft Seal Repair on York YK Centrifugal
15:50
HVACTIME
Рет қаралды 33 М.
How to Change Terminal Plate on Trane CHHP Screw Compressor
8:32
National Compressor Exchange, Inc
Рет қаралды 2,2 М.
Loss Of Charge TRANE CHILLER CGAM070F … Leaks or Something Else
12:39
Typical HVAC unit LEAKING refrigerant & How I Fixed it.
17:37
Quality HVACR
Рет қаралды 39 М.