Loss Of Charge TRANE CHILLER CGAM070F … Leaks or Something Else

  Рет қаралды 3,331

Subcool HVAC

Subcool HVAC

Күн бұрын

Got a work order for a 70 ton CGAM in alarm after power interruption with flow loss. #trane #airconditioning #chiller #hvac

Пікірлер: 21
@joshstevens9826
@joshstevens9826 6 ай бұрын
Trane has an algorithm that takes superheat and exv position over a certain amount of time. If sh doesn't come down and the exv doesn't get in a certain range it says loss of charge. Usually the suction temp sensor reads really high, like 50-60 ° high. Thats always the first thing I look at when I get a loss of charge alarm.
@subcoolHVAC
@subcoolHVAC 6 ай бұрын
Yep, it was definitely low on charge due to the leaks. That time frame is 5 min run and under 59 leaving , both compressors running SH was 12 after charging. EXV 60% . We’re replacing leaking service valves and replacing sensors anyways as insurance.
@zekenzy6486
@zekenzy6486 6 ай бұрын
Great Video. Thank you for sharing
@subcoolHVAC
@subcoolHVAC 6 ай бұрын
Thanks for watching!
@thesilentonevictor
@thesilentonevictor 6 ай бұрын
She needs some love
@subcoolHVAC
@subcoolHVAC 6 ай бұрын
Time flies it’s 11yrs old , coils replaced a few years ago
@LadariusCapersOfficial
@LadariusCapersOfficial 6 ай бұрын
@@subcoolHVACdoes it run a air handler unit 😊
@subcoolHVAC
@subcoolHVAC 6 ай бұрын
Yes, there are 2 total
@georgebrabec1749
@georgebrabec1749 6 ай бұрын
. to take your time, as you can see, working around those EEV's can cause more issues. I had an older 115 ton CGAM that kept going into EEV communication loss, even with the new cables. Used silicon on the connections around the valves, end of issue. Great square one troubleshooting of diagnostics.
@subcoolHVAC
@subcoolHVAC 6 ай бұрын
Thanks for sharing, 👍
@lee-johnson
@lee-johnson 2 ай бұрын
What was the subcooling before you added refrigerant? Nice work
@ccthepope
@ccthepope 6 ай бұрын
A great vid!
@subcoolHVAC
@subcoolHVAC 6 ай бұрын
Thanks as always!!
@Ericbakereb1
@Ericbakereb1 6 ай бұрын
Gotta love neglected equipment
@subcoolHVAC
@subcoolHVAC 6 ай бұрын
Seen worse, we’ll get it fixed up 👍
@adamdnewman
@adamdnewman 6 ай бұрын
There is almost always a leak somewhere 😂
@subcoolHVAC
@subcoolHVAC 6 ай бұрын
No doubt 👍
@joshstevens9826
@joshstevens9826 6 ай бұрын
9.9 times out of 10 cgam loss of charge alarm is a bad suction temp sensor.
@subcoolHVAC
@subcoolHVAC 6 ай бұрын
Indeed 👍
@jasonjohnsonHVAC
@jasonjohnsonHVAC 6 ай бұрын
Not always though....had one that was leaking from the shell of the receiver
@subcoolHVAC
@subcoolHVAC 6 ай бұрын
Yep, our old friend Rusty has visited this time
Trane Climate Changer AHU Making A Lot of Noise…Old Still Works
12:48
ISSEI & yellow girl 💛
00:33
ISSEI / いっせい
Рет қаралды 25 МЛН
Joker can't swim!#joker #shorts
00:46
Untitled Joker
Рет қаралды 40 МЛН
WILL IT BURST?
00:31
Natan por Aí
Рет қаралды 28 МЛН
А ВЫ УМЕЕТЕ ПЛАВАТЬ?? #shorts
00:21
Паша Осадчий
Рет қаралды 1,8 МЛН
York YMC2 Service Needed || That Doesn’t Sound Good
7:03
Subcool HVAC
Рет қаралды 2,8 М.
Trane RTAC Leak Repair + Oil Filter Part 1
19:57
DFW HVAC
Рет қаралды 12 М.
TRANE CHILLER  SOFTWARE TECH VIEW BINDING PROCESS
20:38
HVAC Tips&Tricks
Рет қаралды 7 М.
HURRY OUR BRAND NEW MANITOWOC ICE MACHINE IS NOT WORKING
22:35
HVACR VIDEOS
Рет қаралды 30 М.
Startup Issues with Trane Chiller
7:23
HVACTIME
Рет қаралды 7 М.
TWO GROUNDED COMPRESSORS ?
17:29
HVACR VIDEOS
Рет қаралды 37 М.
CGAM 110 Chiller EXV Comm Loss And Not Cooling | Multiple Issues
12:14
ISSEI & yellow girl 💛
00:33
ISSEI / いっせい
Рет қаралды 25 МЛН