Using a

  Рет қаралды 33,986

Sunsynk

Sunsynk

2 жыл бұрын

This video explains how to program and use a Sunsynk hybrid inverter with a generator set we look at the different programming options and ways to program the inverter. This is purely for demonstration only using a small battery generator emulator power supply and LED to indicate when the generator is running #Sunsynk, #Generator, # power inverter, www.Sunsynk.com

Пікірлер: 45
@GeoffBob77
@GeoffBob77 2 жыл бұрын
I battled for ages to get to my Sunsynk-5K-SG01LP1 inverter to start my generator. I followed the instructions in the manual (with the generator remote start circuit connected to the "G-S" terminals under the inverter front panel) and followed the advice in this video. Long story short, on my model inverter the normally open contacts of the generator start relay are connected to the adjacent terminals labelled "G-V", not "G-S" as stated in the manual. Keith, I have said this before. You have a great product, but the manual that comes with it is utterly riddled with errors and omissions. One of my biggest complaints is the size of the text in the diagrams that is too small and of too low resolution to read. I would further recommend that you split the manual in two, one half labelled installation, the other half labelled operation.
@wernergouws2744
@wernergouws2744 Жыл бұрын
Hiis it possible to connect a generator with a manual choke?
@MultiOutdoorman
@MultiOutdoorman 2 жыл бұрын
Hi Keith. Good info as always. Just bought my first 2 Sunsynk inverters from Tom this week. Questions if i may ? Under what circumstances would we connect a CT coil to the output of a generator / genset? Also, if we are off grid (but tied in with grid backup) should we be able to use current control elements of more than 1 CT coil at the same time, on these Hybrid inverters ? ( genset , grid and separate PV AC source) For example, i have an "Immersun" proportional load-diversion controller that i initially used to divert spare PV energy into my hot water heating element ... and that device has both a CT coil for generation(PV) monitoring, and a second CT coil for Grid monitoring. The excess produced by my solar gets diverted as a resistive load, or relay switching if needed. But no zero export feature otherwise ... I wouldn't like a generator or other AC source to be back fed if the grid or AC my coupled PV were to be energised at the same time ? Cheers Simon
@dannytech4709
@dannytech4709 2 жыл бұрын
Thanks Keith learning a lot with your Videos ! Have a question can you send this product to Puerto Rico ?
@davekennealy
@davekennealy 2 жыл бұрын
Hi Keith, I had a 5kw inverter and had the generator on the Gen port. I now have added a second inverter in parallel. how do now add the generator and where do I connect the control cable?
@lyleengelbrecht4119
@lyleengelbrecht4119 Жыл бұрын
how can anyone follow you if you are Racing through the settings
@AebiFincaArena
@AebiFincaArena Жыл бұрын
great video, thanks! I'm about to connect a generator to the 5k Deye (same as the Sun...) in a manual mode - it's just a 3k gen. and without auto start. Is this config alloud/possible? and 2nd question: why do I have a tension on the generator clamps when not connected (that's why I didn't try to connect so far...) Thanks for any advice, Urs
@williamhyman
@williamhyman Жыл бұрын
Thank you...nice..can I can't connect a single phase genny to a 12kW SUNSYNK 3phase inverter...do I need a 3 phase genny?
@JohnBrinkman
@JohnBrinkman 2 жыл бұрын
Thank you for your always informative video Keith. I have been trying to connect my 5.5kva petrol generator to my 8kw Sunsynk inverter but have been struggling and am hoping you can assist. When connected to the grid side of the inverter (I have a mnaul bypass for switching between the grid and the generator) I can hear the inverter trying to connect to the generator as it tries to apply load but then drops out. If I connect the generator to the Aux side it doesn't seem to try connect at all. I have checked the HZ and voltage on the generator and both seem within range at 230Volts and 50hz. I have also tried setting the max load very low but does not seem to make any difference connecting to the Aux port. Do the Hz & Voltage Min/Max settings in the grid menu apply to the generator when connected to the Aux input as well? Any suggestions, I have emailed to the support email address as well.
@c4g8f
@c4g8f 2 жыл бұрын
Can we connect a three phase generator to the 8kw single phase inverter? Does it take power from one phase of the generator?
@roberthallas349
@roberthallas349 11 ай бұрын
Hi, I want a system that uses an ex rental generator, I believe it’s called a ‘dirty generator’ do your all in one inverter/chargers cope with that? Thanks.
@synthwave7
@synthwave7 Жыл бұрын
One question still arises - you say the Generator supplies the load when it kicks in. Why is the battery not supplying the load and the generator then just charges the battery ? Also - why don't you grey out the AUX GEN setting totally, so it cannot be adjusted if the timer is in use or ticked for GEN ?
@mthabisincube7889
@mthabisincube7889 10 ай бұрын
The battery can not charge and discharge at the same time, that's why the generator has to supply the load when the battery is at it's charge state.
@denveronly
@denveronly Жыл бұрын
Hello, if i have a 3 phase 12K invertor will i be able to run a 1 phase generator to charge it ( two methods - 1) if connected to Gen port and bridged phases (all 3 phases have 220Volts 2) Inverter is tied to the grid, when the grid goes away and the generator will fire up giving same bridged 1 phase spilt to 3 phases 220v on each
@andrewclark5094
@andrewclark5094 Жыл бұрын
I'm in the UK and would like to use the system as an UPS running off its Sunsynk battery. I have a number of questions about that so firstly can someone point me to any document that explicitly covers all the required settings and connections? I'd specifically like to know:- A. Do I need to use e.g. my 2kVA gene to energize the inverter for off-grid use? I have a (4PDT) changeover switch that I can mount in the Consumer unit that can isolate the grid (manually) in the event of an extended grid outage and connect the gene in 1 throw. B Is it better to connect the gene direct to the inverter up in the loft or just isolate the grid and feed the gene power into the Consumer Unit downstairs? C. I have a big (3000VA) APC Smart UPS. If I just need to energize the inverter can I use this Line Interactive unit which outputs a Modified Sine Wave or could that cause any damage? Thanks in advance. Andrew.
@majidjan3990
@majidjan3990 2 жыл бұрын
Very nice
@malachygallagher4936
@malachygallagher4936 10 ай бұрын
Hi I am an elect -security contractor in ireland & have just registered for pv solar! Just starting my first install & don’t know what inverter to use! I like your SUNSYNK ! I am doing my own system first & I have 2 arrays! 1 has 14 panels @ 430 w & other has 9 panels @ 430w? Can I use your 5 or 6 kw hybrid inverter for my job? What ratio do your inverters work on? I have seen myenergy Libbi inverters but still think that your are better! I am in ireland & whatever inverter I start with I will keep using! Only problems are sizes of arrays! Thank for your videos! Hope to hear from you soon! Regards malachy.
@joehebbo7047
@joehebbo7047 Жыл бұрын
11:13 is 52.5 Hz frequency generator is bad what is the average 50-50.5-49 ??? Please any answer
@dipakdhana
@dipakdhana Жыл бұрын
Can another inverter charge the battery
@theosmith4695
@theosmith4695 2 жыл бұрын
Hi Keith I intend to use the generator purely to charge the batteries during prolonged power outages and should we have a week long rainy spell. So it will be on an adhoc basis when required. The generator is a 6.6kW unit without a automatic start feature. Should I then set the timer to charge from the generator for that specific time period?
@dannyweideman9468
@dannyweideman9468 Жыл бұрын
HI Theo wat het jy toe gedoen om jou batterye te laai. Ek het nou n 8kw inverter en wil ook die gen gebruik slegs om te laai.
@kapppie
@kapppie Жыл бұрын
Hi there, thanks for your videos. I have a problem, please help. My generator and Main grid(municipality) runs through the main supply breaker. (because the automatic start as well as other connections). When i run municipality the 12kw 3ph Hybrid see the grid and charge the baterries. But when i run the Gen its sees the gen power coming in but the battery does not charge and my load runs from the battery. please help me with some solutions
@juanduplooy3462
@juanduplooy3462 2 жыл бұрын
Hi guys, so I'm trying to hookup my auto start, my gen requires a bat negative (not a problem) switching through a relay. I need to know what supply comes ot of ports 7 and 8 (gen start) so I can fit the relay advice much appreciated.
@rv10flyer84
@rv10flyer84 2 жыл бұрын
7&8 are just open contacts. On a call for Gen, the contacts close.
@jwalsystems36
@jwalsystems36 6 ай бұрын
I have a situation where I have 2x 8kW 1Ph Sun Synk Inverrters - no grid available and have just installed a 20kVA 1Ph generator with a Smart Gen Controller. We have connected as mentioned in the video but the issue is the inverters to send the auto-on command/signal to the generator to start. My problem is that when the batteries reach the charge voltage set, the inverters do not send the uato-off signal to the generator. What are the possible issues? As mentioned grid is not available.
@ReaanBrand
@ReaanBrand Ай бұрын
Hi jwalsystems36 I have the same issue on my system. Have you been able to get a solution without connecting the generator through the grid port?
@joehebbo7047
@joehebbo7047 Жыл бұрын
I made all settings perfect and keep repeating to check any mistakes but their none but my generator on my inverter keep on and off like every few seconds gives to the battery and load and few seconds stop do you think it s because of the 50 hz frequency i didn t try to check it i was confused why my generator not charging
@EcoNumbersNMore
@EcoNumbersNMore 2 жыл бұрын
Great video! Is it possible to use a 1-phase generator or 1-phase microinverter to feed the generator port in the 12kW 3-phase hybrid inverter (SUN-12K-SG04LP3)?
@bogdankushlyk
@bogdankushlyk 8 ай бұрын
1 phase microinv - works as a charm. not so sure about the 1-phase gen though
@EcoNumbersNMore
@EcoNumbersNMore 8 ай бұрын
@@bogdankushlykThanks for your reply! Just to be sure, you connect 1x 1-phase microinverter to the GEN port of the 3-phase Deye and it works well? No alarms, fault messages etc for not having power on the other 2 phases?
@bogdankushlyk
@bogdankushlyk 8 ай бұрын
@@EcoNumbersNMore yes, put it on L1, in my specific case. the only must-have in this case is that it has to be a grid-tie inverter.
@HannesVenbeck
@HannesVenbeck 11 ай бұрын
Hi Keith, thank you for the videos. We have a 100kw setup, 2 X 50kw Sunsynk Inverters and 2 X 60kw Freedwon batteries, and another 50KW setup with one 60kw battery. At both installations the generator is about 50m away from the inverters and it is therefore not feasible to install a separate cable to make use of the gen port. Our generator is connected to the main grid supply. The generator will start after receiving the instruction from the inverter, but the inverter will then immediately tell the generator to stop because the supply from the generator is being confused for a grid supply. Is there a built in solution for this ? We are using a seperate relay timer at the moment to keep the gen signal closed for a specific period, this is not ideal.
@ridoois6698
@ridoois6698 11 ай бұрын
Hi, Did you ever come right with this?
@StefanBronkhorst13
@StefanBronkhorst13 10 ай бұрын
I have a very similar scenario and would also like your input about this Keith.
@juanduplooy495
@juanduplooy495 Жыл бұрын
Can you connect a Grid-tie inverter to sunsynk gen in port. Therfore using the grid-tie inverter as a generator.
@bootangy
@bootangy Жыл бұрын
did you find out?
@juanduplooy495
@juanduplooy495 Жыл бұрын
@@bootangy You can add a Grid-tie inverter.
@bootangy
@bootangy Жыл бұрын
@@juanduplooy495 can i use my enphase microinverters? would it do ups too? ty
@MrTrojantrdll
@MrTrojantrdll 2 жыл бұрын
I like
@chrisnagel8640
@chrisnagel8640 8 ай бұрын
Hi support please help. Installed a 8kva sunsync 10 months ago. Generator connected to the inverter dry contacts. Dry contact battery level set 46V start gen, 52V switch gen set off. Worked well until Aug. Now when grid is off the inv dry contact activates the dry contact and start gen switch gen off when grid is restored. Checked battery levels and is stable. Thanks in advance
@michaelvw11
@michaelvw11 3 ай бұрын
I don't know for sure but if the contact which is used for the generator start is the same contact which is used for the off grid neutral/earth bonding signal, than this is probably the problem. I don't exactly know how a sunsynk is setup, but with a deye inverter there is a box in the settings "signal island mode" which probably should be ticked off when using this port to start a generator. Hope this helps
@wozzco8111
@wozzco8111 Жыл бұрын
I’d like to see you redo this video with a real generator (maybe a 7.5 kva petrol) to show how that works because very few people are able to make that work. Your generator used here is not a true reflection of a real world example.
@roelfcoetzee7307
@roelfcoetzee7307 4 ай бұрын
I would like to see that.
@karelgjbezuidenhout9769
@karelgjbezuidenhout9769 Жыл бұрын
Video outdated
Did you find it?! 🤔✨✍️ #funnyart
00:11
Artistomg
Рет қаралды 119 МЛН
Uma Ki Super Power To Dekho 😂
00:15
Uma Bai
Рет қаралды 60 МЛН
格斗裁判暴力执法!#fighting #shorts
00:15
武林之巅
Рет қаралды 72 МЛН
How to Charge Solar Batteries Using a Generator
9:56
Solar Surge
Рет қаралды 87 М.
Using a Gen Set with Sunsynk Inverters
5:32
Sunsynk
Рет қаралды 12 М.
All tests of a cheap OFF GRID inverter with a power generator and more.
41:25
Panele Fotowoltaiczne
Рет қаралды 20 М.
Transformer based inverter vs Hybrid Transformerless inverter.
16:45
Smilinsun Solar Energies
Рет қаралды 7 М.
Earth Neutral Bond
14:13
Sunsynk
Рет қаралды 29 М.
12kw Sunsynk Inverter Setup - Worth the Investment ?
28:00
Electronics and All
Рет қаралды 7 М.
Sunsynk System Mode run through
5:23
BackBoneEnergy
Рет қаралды 44 М.
Did you find it?! 🤔✨✍️ #funnyart
00:11
Artistomg
Рет қаралды 119 МЛН