How to troubleshoot and diagnose a non-working VFD

  Рет қаралды 294,844

VFDs.com

VFDs.com

Күн бұрын

Пікірлер: 127
@pvssrinivas
@pvssrinivas 2 жыл бұрын
Wow! Absolutely amazing, fabulous!!!. This is how you explain the concepts -- clear cut, right to the point, no beating around the bush, etc. I wish others watch this video and learn how to make educational videos..
@wangarooi
@wangarooi 3 жыл бұрын
I used to repair mitsi drives for a living...many moons ago when vf control was the defacto. This guy is exactly right in his explanation. If I could add a couple of points: 1. Smell the drive.....if it has a "burnt" smell then its usually the power section and chopper section blown. You can sometimes see the power device sidewall blown out, exposing some white smoky looking gel...maybe this has changed on the newer devices. 2. A faulty drive has a certain squeaky sound....unfortunately that a difficult one to explain I could diagnose a faulty drive just by the way it sounded..it was usually the capacitors on the chopper boards. Mitsubishi used to pull the gate signal slightly negative to switch the power devices off. I doubt I could hear a faulty drive now and the newer power devices are much better at switching on and off. Anyway, that was many moons ago my exposure to industrial drives is now a button/parameter checking thing and this in its own right can be the difficult thing you have to find the right parameter but the fundamental principles stay the same But to the good gentleman explaining this video you are spot on.
@technologytijuana
@technologytijuana 2 жыл бұрын
Hello sir, what would be the problem for a vfd that is getting the dc bus voltage directly to the vfd output. Im getting 650vdc in u v w?
@wangarooi
@wangarooi 2 жыл бұрын
@@technologytijuana ...didi you chck for a short from the DC bus to UVW... Obviously let it discharge first
@kirkjackson3306
@kirkjackson3306 Жыл бұрын
Makes the job so much easier if, for example, the vfd reads a ground fault present. It allows you to make straight to that 3 phase motor and it's wiring,. Easy continuity testing. Such a help!
@bch2780
@bch2780 Жыл бұрын
The way to solve problem is so simple, the complicated is the detail of parameters of each brand, How many brands in the market may be 100 brands
@mundrubjet
@mundrubjet 7 жыл бұрын
Also, when you shut down a VFD, you should wait at least 10 minutes as most of them hold a charge that will dissipate through a resistor. If you go touching things right away because you have opened the disconnect, you could do the electron boogie for a few seconds. And that's worse than the chicken dance...
@MOHDFAISAL-qw8mz
@MOHDFAISAL-qw8mz 5 жыл бұрын
Right
@scottwillis5434
@scottwillis5434 5 жыл бұрын
Allow for failed bleeder resistors. Use a voltmeter (rated for at least 500V) to check the capacitor voltage, which may exceed 320VDC when powered, before sticking your fingers in there. Stay clear of anything over 40V or so! AC 'tingles'; DC contracts your muscles and overrides any (millivolt) signals from your brain: your muscles won't let go! Bit awkward, that. A relative opened up a camera flash unit that had been off for a day (they don't have bleeder resistors to discharge them). He must have touched the charged capacitor; he doesn't *usually* scream loudly like that...
@MOHDFAISAL-qw8mz
@MOHDFAISAL-qw8mz 5 жыл бұрын
@@scottwillis5434 yes sir.... Right
@RyanJardina
@RyanJardina 4 жыл бұрын
@@scottwillis5434 500v rated meter. The DC bus on a 480V AC input drive is about 680V DC 🤦‍♂️
@Jimmyjackfruit
@Jimmyjackfruit 2 жыл бұрын
Craig, I know the drive is not powered up, but watching you touch the U, V, W busses makes me jump. Haha! Great video.
@bobbyyoung2831
@bobbyyoung2831 2 ай бұрын
Very much appreciated. Covered a bunch of info in a short time. Thanks
@ramsahadeo9487
@ramsahadeo9487 3 жыл бұрын
Now you made me smarter ...thank you
@alejandromata825
@alejandromata825 Жыл бұрын
While the motor was disconnected and the drive was off you can also check the gates on the IGBTs with your meter on diode check, you can check the capacitors across the buses somewhat, you could also check the MOVs and the rectifier with a diode check as well.
@richardcollins5931
@richardcollins5931 4 жыл бұрын
VFD Repair - Industrial Solutions Authority, Hamilton Ohio, USA - Best turnaround time in the industry. Be sure to tell them Rich sent ya.
@PBS-nm1uu
@PBS-nm1uu 4 жыл бұрын
this is a great presentation thanks, for all the info, made me a smarter person.
@allan_bomb
@allan_bomb 7 жыл бұрын
Maybe you can describe how to check the rectifier bridge, if the SCRs are shorted and the capacitor in the next video. Also, before powering on the drive, you should always ohm the input terminals if they are shorted. Those are main causes of drive failure.
@SombraLocs
@SombraLocs 6 жыл бұрын
Allan Valdez That's the video I'm looking for
@ackmino
@ackmino 6 жыл бұрын
Allan - worked on many of these as a locomotive tech. Yes, the SCR/diodes fail more than anything. Basically you can find your problem using your meters diode check. They almost always fail shorted rather than open. The freq drives usually show the diode configuration on the panel cover.
@scottwillis5434
@scottwillis5434 5 жыл бұрын
Just learn basic high-voltage precautions before starting work!
@abdullahghurbal37
@abdullahghurbal37 4 жыл бұрын
Great effort and professional explanation Thank you sir
@jonathanscott8226
@jonathanscott8226 2 жыл бұрын
Nice little video with great tips, thank you!
@pneumatic-generator2022
@pneumatic-generator2022 7 жыл бұрын
Thank you for your explain. i have a question . pls . a VFD can work with the dc source. if so can you give us clarificatons thank you .
@VFDscom
@VFDscom 7 жыл бұрын
Most VFDs out there are AC but some manufacturers make DC VFD. For example, Emerson has 2 lines of DC VFD.
@pneumatic-generator2022
@pneumatic-generator2022 7 жыл бұрын
thank you
@rocklymr15
@rocklymr15 7 жыл бұрын
Hey great video! Knew a lot of this before hand, but it was a great wrap up of a lot of basic issues. Any chance you have a video on VFD motor protection programming?
@jani140
@jani140 7 жыл бұрын
How can a normal vfd be able to put power back into the grid? It can't because normally on the utillity side of the DC bus is no inverter to do so. But if the motor feeds into the drive You could have a break resisor or DC break. Otherwise the drive will trip and let the motor free run
@mithileshramteke3882
@mithileshramteke3882 3 жыл бұрын
Good explanation thank you
@jprivacy5051
@jprivacy5051 5 жыл бұрын
Great educational video man.
@anonymousperson2578
@anonymousperson2578 7 жыл бұрын
Excellent video!
@D.Hozzie
@D.Hozzie 11 ай бұрын
Good stuff. Thanks for sharing.
@ogbagiorgisabrha6355
@ogbagiorgisabrha6355 3 жыл бұрын
It very good explanation I enjoy it very much.
@kevinmithnick9993
@kevinmithnick9993 2 ай бұрын
nice info sr
@en2oh
@en2oh 11 күн бұрын
Do these drives have fuses? I have a drive that doesn’t even power on
@franciscrasto
@franciscrasto 4 жыл бұрын
Sir your explanation is simply great. .God bless you.
@user-hu4if6xw8p
@user-hu4if6xw8p Жыл бұрын
Thanks sir for this information.
@jaythompson5102
@jaythompson5102 Жыл бұрын
Can you explain why the power supply may be overvolting at night? I missed this concept somehow
@josegeorgekadakampallil8055
@josegeorgekadakampallil8055 7 ай бұрын
Thank you Sir
@maximochimfwembe5886
@maximochimfwembe5886 Жыл бұрын
AN FR-A700 INVERTER HAS DEVELOPED A PROBLEM OF ONLY RUNNING IN ONE DIRECTION(FORWARD) BUT PREVIOUSLY IT WAS RUNNING IN BOTH DIRECTIONS AND I HAVE CHECKED THAT THERE IS NO SIGNAL FROM THE INVERTER(AT RUN TERMINAL) GOING TO THE PLC .WHAT CAN BE THE PROBLEM.QUICK RESPONSE WILL BE HIGHLY APPRECIATED
@jimbass924
@jimbass924 3 жыл бұрын
Great Profesional explanation!!
@1989Chrisc
@1989Chrisc 7 жыл бұрын
I was kinda scared when you started touching the power cables. I could hear a buzzing so was thinking it was powered up
@richardcollins5931
@richardcollins5931 4 жыл бұрын
The stir fan alone on that drive would have been 120db, if it were on it would have been obvious.
@1989Chrisc
@1989Chrisc 4 жыл бұрын
@@richardcollins5931 I should have said live instead of powered up
@1989Chrisc
@1989Chrisc 4 жыл бұрын
@@richardcollins5931 or hot as you yanks say
@sohailjanjua123
@sohailjanjua123 2 жыл бұрын
Hi, I like your lecture. Thanks
@kevywevvy8833
@kevywevvy8833 7 жыл бұрын
On a mitsubishi inverter, 9999 in a parameter means it's set to dataplate ratings by default. Setting a 'real' value in there is usually a precursor to sensorless flux vector mode. Setting these away from 9999 must be followed by a flux vector autotune
@arifmalik6607
@arifmalik6607 Жыл бұрын
Sounds great
@alxk3713
@alxk3713 7 жыл бұрын
Very Educational
@talalalrahbi9430
@talalalrahbi9430 5 жыл бұрын
THANK YOU SIR,,i have a problem with VFD is not working and the MCCB is burned ,,so what could be the causes of this issue?
@maximochimfwembe5886
@maximochimfwembe5886 Жыл бұрын
I HAVE REPLACED AN FR-A700 WITH AN FR-A800 AND ENTERED THE SAME PARAMETERS THAT WAS IN A FAULT A700 INVERTER BUT THE DRIVE IS NOT WORKING.WHY?
@josemiramontes4280
@josemiramontes4280 4 жыл бұрын
The mergency stop signal🤔???
@claudiuswilliams7829
@claudiuswilliams7829 Жыл бұрын
What if the VFD shows its running but there is no power coming out from the output phases. even though the VFD shows running . But when checked with a multimeter the VFD output to the motor itself has no power coming out of each phase..
@henzelmen
@henzelmen 3 жыл бұрын
Thank you sir, good and to the point information
@TheUkjedi
@TheUkjedi 3 жыл бұрын
Great video
@edgarbanuelos2660
@edgarbanuelos2660 5 жыл бұрын
Hi good morning I'm starting with vfd what book you recommend me
@1krazmf851
@1krazmf851 7 жыл бұрын
I put a dimmer switch on my ceiling fan. Po mans vfd
@scottwillis5434
@scottwillis5434 5 жыл бұрын
That will result in extra heating, and the fan is running slowly so reduced cooling. At least keep an eye on it...
5 жыл бұрын
Good explanation
@jakeblanton6688
@jakeblanton6688 Жыл бұрын
R= L1 S= L2 T= L3 N= Negative for DC Bus P= Positive for DC Bus P= ? U= T1 V= T2 W= T3 Would someone please explain to me what the second P stands for because Craig didn’t go over it. I would greatly appreciate it.
@Magneticitist
@Magneticitist 7 ай бұрын
Well this is 5 months late and you know the answer by now.. but for the record this is typically the 'P+' connection where a DC Link Choke would go. So the choke itself is what would bridge the P and P+ terminals in order to close the loop to the DC bus. If the choke is not present, a jumper needs to be there in order for the DC bus to charge.
@zahirulislam7961
@zahirulislam7961 3 жыл бұрын
Running motor suddenly stop Vfd Display show, Err F 1301, what's the problem? Please tell me.
@eloymarquez4783
@eloymarquez4783 4 жыл бұрын
Great info! Thank you
@zahirulislam7961
@zahirulislam7961 3 жыл бұрын
3 phase motor don’t run, VFD display show ‌`fault` and E l l, what's the problem?
@LearningEngineering
@LearningEngineering 7 жыл бұрын
great thanks sir.
@MOHDFAISAL-qw8mz
@MOHDFAISAL-qw8mz 5 жыл бұрын
Thanks guys
@spartaeus
@spartaeus 4 жыл бұрын
My Mitsubishi vfd goes back to default setting if I turn the power off to the vfd. Is that normal???
@bigt95nt011037
@bigt95nt011037 2 жыл бұрын
What is the best oscilloscope for troubleshooting a vfd?
@brianstredder9525
@brianstredder9525 5 жыл бұрын
Have an old Toshiba g2+. OC3 fault. No motor attached, still can't clear the fault?
@antonioborges2576
@antonioborges2576 4 жыл бұрын
Great info
@jb-ik8sj
@jb-ik8sj 2 жыл бұрын
Do these work well with a 480 3phase generator?
@belkizaguinaga5032
@belkizaguinaga5032 Жыл бұрын
My VCU john zink turn off and gives me a code vfd 101 communication failure
@madsteyn739
@madsteyn739 3 жыл бұрын
how can i reset a allen bradley 1336 plus to factory settings?
@mutunzanachisha2243
@mutunzanachisha2243 Жыл бұрын
How to trouble shoot cfw-11 vsd
@austinspivey7427
@austinspivey7427 2 жыл бұрын
Who knew Donald trump was this good at troubleshooting VFDs
@primary1271
@primary1271 5 жыл бұрын
hey man you are the best
@oregonsignalfan
@oregonsignalfan 2 жыл бұрын
where can I find water-cooled VFDs?
@ltgaming8510
@ltgaming8510 2 жыл бұрын
HOW TO TROUBLESHOOT COUNT OLAF
@TangenyShikolalye
@TangenyShikolalye 5 жыл бұрын
pleae help meguys > i have mishubish A700 vfd but when i start it it only runs for 10 minutes then it trips, the it dispalys the OP3 ALARM , what could be the problem and what could be the cause
@industrialautomationexpert799
@industrialautomationexpert799 5 жыл бұрын
before vfd run Earth nutral viltage 1V, after vfd run Earth to nutral voltage 14/15 Volt-i need to solution please explain.we give Earth connection properly VFD to Motor. we use SUBMERSIBLE MOTOR.
@user-hj9io8nr9w
@user-hj9io8nr9w 3 жыл бұрын
Great Thanks!
@varune90
@varune90 5 жыл бұрын
Dear sir vfd frequency going to low in auto mode what case this?
@coolworkshvac6043
@coolworkshvac6043 2 жыл бұрын
awesome sir thank yoi
@deepak9640
@deepak9640 7 жыл бұрын
helo sir , i had a question 90 kw motor is controlled by danfoss vtl 6000 drive . when ever i check load of motor it is not constant some times it show 10amps and some time 50 amps. it showing variable load what should i do please help..
@VFDscom
@VFDscom 7 жыл бұрын
What is your application?
@deepak9640
@deepak9640 7 жыл бұрын
It is used as exhaust fan
@corbeNification
@corbeNification 7 жыл бұрын
Test on another smaller motor. If it still shows the motor current incorrectly replace the current transducers. If problem persists replace the control card, Danfoss no longer support the VLT 5000 and 6000 I believe so you will have to source a second hand card..
@corbeNification
@corbeNification 7 жыл бұрын
I would also check the ribbon cables between the PCB's for continuity and the headers on the PCB's for corrosion.
@ishukaushikvideo6120
@ishukaushikvideo6120 6 жыл бұрын
Dear sir May be some reasons for this type of problems. (1) check the motor winding resistance should be equal and in Ohms. (2) motor terminal connection should be not loose connection (u, v, W) . (3) may be possible Vfd CT have problems, need too replace or repair. (4) earthing should be proper between drive &exaust fan. (5) exaust fan should be not jam. Mob :8447550303
@abar7178
@abar7178 5 жыл бұрын
thank you
@AriVovp
@AriVovp 5 жыл бұрын
Why is this controller solarge for a 350hp motor, in the mean time , the controller for the Tesla Model s motor is tiny and light weight compare to this?
@jeremyhall9346
@jeremyhall9346 4 жыл бұрын
Dc..... tesla Ac...... this motor. Big difference.
@dosolmire9476
@dosolmire9476 4 жыл бұрын
Please give me a Solution, Do you know how to fix ac drive problem, UVW unbalance output Voltage? U-V Voltage 7% less, compared to U-W & V-W Voltage
@creativeweirdo6193
@creativeweirdo6193 3 жыл бұрын
Bruh I came here from a series of unfortunate events 😂
@selvarasumanikandan7646
@selvarasumanikandan7646 3 жыл бұрын
Thanks sir
@dukewp5481
@dukewp5481 3 жыл бұрын
Hello Red River Electricians
@nazgullinux6601
@nazgullinux6601 2 жыл бұрын
I know Donald Trump's uncle was a physicist and all that but I didn't expect to see the Don giving a VFD troubleshooting overview for a random vid like this lol.
@JackDavidson-ov2tf
@JackDavidson-ov2tf 5 жыл бұрын
Great video sir. Can you do a video on Siemens VFD drives? I have been running into issues on theses. Thank you
@battsengelnansal4756
@battsengelnansal4756 6 жыл бұрын
How to loading cell?
@alingeorge8160
@alingeorge8160 7 жыл бұрын
Sir , for a 60Hz rated motor ,how much we can increase the frequncy ...? Plz help
@hast66
@hast66 5 жыл бұрын
Depends on whole setup. When frequency increases, torque decreases until to point that the motor stalls. You're "lucky" if it still runs at 90Hz. But then, motorload should be probably zero.
@kjacoby
@kjacoby 4 жыл бұрын
Stefan Haesen yeah I didn’t think it would run that high?
@electroproject3655
@electroproject3655 4 жыл бұрын
thanx ..sir ...............
@maryphiri4561
@maryphiri4561 5 жыл бұрын
Hie can i run a say 1.5 kw 3phase motor with a petrol gen single phase using vfd? Anybody plz
@rl7623
@rl7623 2 жыл бұрын
F70800???
@battsengelnansal4756
@battsengelnansal4756 6 жыл бұрын
Not load power pault
@madchillen4205
@madchillen4205 7 жыл бұрын
What is a fault overload?
@jasmany19
@jasmany19 6 жыл бұрын
When the motor is drawing more current than what the motor name plate is rated for.
@feedyourfaith7392
@feedyourfaith7392 6 жыл бұрын
What is a current overload?
@ahmedbouroga7304
@ahmedbouroga7304 5 ай бұрын
@mikeadler434
@mikeadler434 Жыл бұрын
👍👍
@Reowasolar
@Reowasolar 5 жыл бұрын
5:09
@krankransegpatel991
@krankransegpatel991 5 жыл бұрын
Hello
@isaacyaw7931
@isaacyaw7931 Жыл бұрын
Great video. Thanks a lot. This man looks a little like Ex. Prez Trump haha
@xLSClanx
@xLSClanx 4 жыл бұрын
😐
@creativeweirdo6193
@creativeweirdo6193 3 жыл бұрын
Lol wut
@jasoncalangas7552
@jasoncalangas7552 3 жыл бұрын
Cc
@rockskipper5353
@rockskipper5353 Жыл бұрын
I need a professional lol
@laboratoriocotear1949
@laboratoriocotear1949 2 жыл бұрын
Thanks Mr Donald Trump
@antonioborges2576
@antonioborges2576 4 жыл бұрын
Great info
@drilonmuslii7725
@drilonmuslii7725 7 жыл бұрын
VFD is not giving any output voltage. It seems that everything is OK with the wiring and the program but still I cannot get any output voltage. What can be the reason for this?
@VFDscom
@VFDscom 7 жыл бұрын
If the RUN light blinks then there is no Speed Reference.
@drilonmuslii7725
@drilonmuslii7725 7 жыл бұрын
Thank you for your response. I've adjusted speed and other parameters but still I cannot get any output voltage.
@VFDscom
@VFDscom 7 жыл бұрын
Did you set your maximum speed to 60 or 50Hz? Did you set your run speed? Have you metered the input terminals to see if there are voltage on the inputs?
@drilonmuslii7725
@drilonmuslii7725 7 жыл бұрын
there's voltage in input terminals. Also the the parameters are adjusted as they should be but still no output voltage.
@VFDscom
@VFDscom 7 жыл бұрын
What lights are on when it is running? Any error codes?
Drive Basics
25:33
Yaskawa America - Drives & Motion Division
Рет қаралды 501 М.
Before VS during the CONCERT 🔥 "Aliby" | Andra Gogan
00:13
Andra Gogan
Рет қаралды 10 МЛН
Gli occhiali da sole non mi hanno coperto! 😎
00:13
Senza Limiti
Рет қаралды 22 МЛН
ROLLING DOWN
00:20
Natan por Aí
Рет қаралды 11 МЛН
❌Разве такое возможно? #story
01:00
Кэри Найс
Рет қаралды 3,8 МЛН
Troubleshooting a PLC Output
7:25
KletteTech
Рет қаралды 47 М.
VFD Buying Guide
7:26
VFDs.com
Рет қаралды 56 М.
How To Measure Variable Frequency Drives (VFD) - Filtered vs. Unfiltered
9:40
Engineered Air Balance
Рет қаралды 31 М.
HOW TO TEST IF A VFD ( Variable Frequency Drive ) IS BAD WITH A MULTIMETER
11:57
VFD 101 Basics
15:52
Eaton
Рет қаралды 919 М.
How To: Troubleshoot VFDs
11:30
Radwell International
Рет қаралды 32 М.
MULTIPLE CARRIER VFD FAILURES
12:42
HVACR VIDEOS
Рет қаралды 46 М.
Burnt VFD, Why?????
8:45
leckyjake
Рет қаралды 23 М.
How to bypass the VFD?
10:52
Taddy Digest
Рет қаралды 26 М.
CAN Bus Properties and Troubleshooting
18:09
Enovation Controls
Рет қаралды 1,3 МЛН
Before VS during the CONCERT 🔥 "Aliby" | Andra Gogan
00:13
Andra Gogan
Рет қаралды 10 МЛН