hi thanks for the detailed video , just got Deye hybrid, its an amazing inverter. I have 200 amp c20 batteries can i do time schedule with these batteries in the system work mode?
@kylezhang8343 Жыл бұрын
HI yes can
@georgenicola67727 ай бұрын
hello, I installed a sun-8K-SG01LP1-US/EU hybrid Deye inverter, on which I mounted a 10kw battery with bms jk, during the day when I disconnect the electrical network it is ok, but at night when the panels no longer I produce and disconnect the network, the battery enters the load after 3 minutes, can it be set to enter the load immediately??? (I mention that in the manual it is written that it can also work with agm, gel battery, i.e. not with a dedicated battery) the inverter detects the battery but on application is not visible, what settings can be made or can be made ???? anticipated thanks for the answer.
@arturosekijima7142 Жыл бұрын
Amazing video! One question: I have a small battery bank. Is there a way of setting it up to use just as a no-break? Not draining from battery unless PV is insufficient and grid is out? I assume it would be Zero export to Load, Load First, grid charge. Am I right? Thanks for the work
@kylezhang834311 ай бұрын
if using very small size battery, it may damage the battery.
@coolestspott693 жыл бұрын
nice! 1. is there anyway to completely disable charging of batteries from grid? 2. can we set the amount of voltage or amps if we need to charge batteries from grid?
@kylezhang8343 Жыл бұрын
1, yes, please don't tick "grid charge" on the battery setting, then the grid won't charge the battery. 2, yes, can . you need to choose battery V or battery % mode, then you can change the battery charge voltage. for the current, you just need to setup the grid charge current on the battery setting.
@ilimuthabiti93972 жыл бұрын
Je naweza kuto kutiki Grid charge ili kuondoa gharama ya umeme wa Grid kuchaji battery zangu?. Ninachotaka nikuona panakuwa na Grid passthroug to the load.
@frankfehlmann2083 Жыл бұрын
What does CT stand for?
@kylezhang834311 ай бұрын
Current transformer
@etv40753 жыл бұрын
What happen if the grid failed during daytime?
@kylezhang8343 Жыл бұрын
the battery and PV will power the load when grid failed
@GreekSIMRACING2 жыл бұрын
Is their any option to prevent power going to Grid if Net metering is not option on our country.
@ilimuthabiti93972 жыл бұрын
Good question sir.
@kylezhang8343 Жыл бұрын
don't tick “solar sell and selling first” then PV energy won't flow to the grid
@rcclim Жыл бұрын
@@kylezhang8343 What is the different between Zero export to load and zero export to CT ?
@MrSudeshm2 жыл бұрын
what is the setting for CT Ration
@kylezhang8343 Жыл бұрын
the default setting is 2000:1
@coolestspott69 Жыл бұрын
hello, is there any way of locking my screen using a password? so that no one can change my settings ?
@kylezhang834311 ай бұрын
there's password to lock the parameters setting. four 9
@JM-nc8cu5 ай бұрын