Diagnosing Daikin U0 Error⎪2

  Рет қаралды 15,512

Mitch Attwood

Mitch Attwood

Жыл бұрын

HVACR⎪HVAC⎪REFRIGERATION⎪AIR CONDITIONING⎪AIR CONDITIONER VIDEOS
In this video I attend a break down where the unit is displaying a U0 Fault Code and won't run. I found the Outdoor Printed Circuit Board to be faulty.

Пікірлер: 41
@MentalLapse09
@MentalLapse09 Жыл бұрын
Yeah definitely agree that inverter air conditioning pcbs are fragile when it comes to storms/surges. I like to put surge diverters in my quotes as a recommended option.
@maracservices
@maracservices Жыл бұрын
That’s a good idea. I’ll have to start doing the same thing!
@robalexander7348
@robalexander7348 Жыл бұрын
Nice vid Mitch, and good to see you on the job bright n early 08.10 👍 and luv the way that outdoor compressor is only mounted on loose bricks, also No 240v isolator 🙄
@maracservices
@maracservices Жыл бұрын
Definitely wasn’t installed by me that’s for sure 😂
@robalexander7348
@robalexander7348 Жыл бұрын
@@maracservices Mate, it's sure not your work, we all now your quality work by now, maybe the owner would agree to wall mounting brackets being fitted as well 👍
@BERESHIDA2008
@BERESHIDA2008 Жыл бұрын
Great videos
@maracservices
@maracservices Жыл бұрын
Thanks!
@liqfx982
@liqfx982 Жыл бұрын
Informative video mate. I’m Keen to see the board replacement if you film it when you go back
@maracservices
@maracservices Жыл бұрын
Thanks mate, I’ll definitely record it but I’m not sure when because according to Daikin’s Global Data Bank there are no PCB’s available in Sydney. Which normally means none in Australia. Hopefully soon though.
@nguyenthechung
@nguyenthechung Жыл бұрын
Thanks for your's share...!
@softroadingnewzealand5210
@softroadingnewzealand5210 Жыл бұрын
I need to ship you a proper LA Dodgers hat haha. Great video and learning a lot from your channel…
@maracservices
@maracservices Жыл бұрын
Haha this hats the best mate. Been through a lot together!
@FreedomInMindtv
@FreedomInMindtv Жыл бұрын
Nice one Rodney 🤙🏻
@maracservices
@maracservices Жыл бұрын
Out of control on a regular basis
@rodneycooper5474
@rodneycooper5474 Жыл бұрын
Hey mate just wondering why all the resistance readings the same? For single phase shouldn’t the highest be between run and start, then start and common, then run and common?
@maracservices
@maracservices Жыл бұрын
It’s because it’s a 3 phase DC Compressor mate. Good question though!
@BERESHIDA2008
@BERESHIDA2008 Жыл бұрын
In iverter motor it should read the same reading
@marzgtp
@marzgtp Жыл бұрын
what is a U4 long beep? And what should I look for on my Daikin unit
@maracservices
@maracservices Жыл бұрын
Communication error between indoor and outdoor unit. It could be a fault in the interconnect wiring but most likely a faulty PCB.
@Rayray_unicornplayz567
@Rayray_unicornplayz567 Жыл бұрын
Are you going to make a part 2 for it?
@maracservices
@maracservices Жыл бұрын
I am however Daikin don’t have any of those PCB’s in stock so we are currently waiting unfortunately.
@nettoyageplusplus4947
@nettoyageplusplus4947 2 ай бұрын
Comment vous avez testez la carte électronique ? Merci
@kcomfortsystemshvac7060
@kcomfortsystemshvac7060 Жыл бұрын
Nice video 👍 let’s say if you the unit it short the gas …what the best away to add r32 ? What type tecnic are you use it ? Thank you
@BERESHIDA2008
@BERESHIDA2008 Жыл бұрын
when ever posible with a scale by weight , the unit has a label indicating how much the unit takes
@maracservices
@maracservices Жыл бұрын
Find the leak, fix the leak, evacuate the system and then weigh charge the gas back in 👍🏻
@olliebulldog951
@olliebulldog951 Жыл бұрын
Hi, have you ever had a u0 04 error? Daikin cant seem to figure it out and blaming airflow, however system was working fine for 3 years through many 40c days. Gas has been reclaimed and checked. Indoor coil thermistor replaced.
@maracservices
@maracservices Жыл бұрын
If it’s not short on refrigerant and a technician has confirmed this. You need to test the low pressure transducer is actually working. It might think it’s low on refrigerant when it actually isn’t.
@bmiadmin5784
@bmiadmin5784 6 ай бұрын
Change brand next time mate, this brand is too much problem and gives you headaches....
@ClimateAdaptation
@ClimateAdaptation Жыл бұрын
If the fuses don't have continuity could you replace them to try and get the PCB working again?
@maracservices
@maracservices Жыл бұрын
Yeah definitely however unfortunately in this case the fuses are fine and do have continuity. The issue is in the board.
@adrianvisintin1961
@adrianvisintin1961 Жыл бұрын
@@maracservices I love how air conditioning company’s don’t put replaceable fuses 😅 . Can I ask what props you use to test small components
@maracservices
@maracservices Жыл бұрын
@@adrianvisintin1961 I know it’s so ridiculous hey. So my fluke meter came with prongs that I use 99% of the time but I found a really cheap no name multi meter laying around that had really sharp prongs. So basically I put the prongs in my bag to test plugs and what not. So to answer your question, I use no name Chinese leads for plugs and decent fluke leads for everything else haha.
@chiller-on
@chiller-on Жыл бұрын
Well, at least they put it on the stones, they could just put it on the ground😁
@maracservices
@maracservices Жыл бұрын
Quality install 😂
@myrah_adzy
@myrah_adzy Жыл бұрын
hi mate ever had an e5 error?
@maracservices
@maracservices Жыл бұрын
Yeah mate that’s just an error code that comes up when the compressor gets to hot. Unfortunately there’s many things that could cause that so it’s impossible to tell you the exact problem without checking stuff but I can tell you that the compressor got too hot. Error comes on when the thermal overload is tripped which is located on top of compressor.
@thomasmarchant4054
@thomasmarchant4054 Жыл бұрын
Had this error before turned out to be eev. System was pumping itself down into a vacuum.
@josephwhite373
@josephwhite373 6 ай бұрын
Was there frost on one side of eev
@tarekabuhijleh5638
@tarekabuhijleh5638 4 ай бұрын
U0 error REFRIGERANT SHORTAGE
@maracservices
@maracservices 4 ай бұрын
lol I know but it was not short on refrigerant. It had a faulty board
@tarekabuhijleh5638
@tarekabuhijleh5638 4 ай бұрын
@@maracservices ok
Diagnosing Daikin E5 Error
15:50
Mitch Attwood
Рет қаралды 4 М.
Daikin | How to rectify(error code UO)
4:36
Bon Mj
Рет қаралды 41 М.
THEY WANTED TO TAKE ALL HIS GOODIES 🍫🥤🍟😂
00:17
OKUNJATA
Рет қаралды 22 МЛН
THE POLICE TAKES ME! feat @PANDAGIRLOFFICIAL #shorts
00:31
PANDA BOI
Рет қаралды 25 МЛН
КАРМАНЧИК 2 СЕЗОН 7 СЕРИЯ ФИНАЛ
21:37
Inter Production
Рет қаралды 543 М.
Heartwarming: Stranger Saves Puppy from Hot Car #shorts
00:22
Fabiosa Best Lifehacks
Рет қаралды 21 МЛН
Diagnosing Daikin U0 Error
7:29
Mitch Attwood
Рет қаралды 50 М.
Diagnosing Daikin E7 Error (EP 1)
12:38
Mitch Attwood
Рет қаралды 28 М.
The Most Difficult Air Conditioning Installation EVER
6:24
Electrum Electrical
Рет қаралды 2,5 М.
Diagnosing Daikin U2 Error
20:22
Mitch Attwood
Рет қаралды 18 М.
NOT COOLING | DAIKIN | NO ERROR
22:12
JDL ELECTRONICS SERVICE CENTER
Рет қаралды 34 М.
code défaut Daikin
2:18
Julien F
Рет қаралды 6 М.
How To Install A Daikin Dual Zone Ductless Mini Split
33:45
The DIY HVAC Guy
Рет қаралды 47 М.
Подробный монтаж кондиционера в квартире
55:16
Стройплощадка
Рет қаралды 388 М.
THEY WANTED TO TAKE ALL HIS GOODIES 🍫🥤🍟😂
00:17
OKUNJATA
Рет қаралды 22 МЛН