How'd They Expect This To Work: Steam Boiler Installation Epic Fail

  Рет қаралды 29,680

Mikey Pipes - Pipe Doctor Plumbing & Heating & Air

Mikey Pipes - Pipe Doctor Plumbing & Heating & Air

5 ай бұрын

Boiler piping wrong, safety devices not wired, electrical secured with bubble gum and duct tape & wrong gas piping - just a short list of another steam boiler installation epic failure! Let's Make The Trades Great Again! Join Mikey Pipes Philanthropy, Inc., an IRS 501(c)(3) non-profit public charitable organization. Our mission is to offer free or low-cost plumbing, heating and cooling services to those in our community who can't afford to hire a professional. Help us here: www.paypal.com/donate/?hosted...
Curious on our dispatching and invoicing app? Check out HouseCallPro: tinyurl.com/MikeyPipesHCP
What’s in your Veto? Here is mine:
Veto TP-XXL amzn.to/3zX10vg
Testo Combustion Analyzer: amzn.to/3Zd7naH
Digital Manometer: amzn.to/3EDt5ey
Milwaukee M18 Blower: amzn.to/46iTo6j
Milwaukee M12 Fuel 1/4" Impact Driver amzn.to/3I9yLfI
Milwaukee PVC cutter: amzn.to/3sbrdUc
Mini Waterproof Storage bin: amzn.to/3yfgsEv
Wiha Allen Keys: amzn.to/33ipGmb
HIKMICRO B20 amzn.to/33iGklx
Furnace Switch amzn.to/31X89PT
Milwaukee Light amzn.to/3I38Lmh
Wagos amzn.to/34QoiaU
Milwaukee Set amzn.to/33vnQOz
Torpedo Level amzn.to/3no1oOk
Crescent set amzn.to/3GtZeV8
Wiha 7 piece set amzn.to/3rkISaK
Milwaukee step bit amzn.to/3I395Bv
Thermocouple Flare wrench: amzn.to/3noJZ8s
Ridgid 10” wrench amzn.to/3GvRnqa
Fluke non-contact tester amzn.to/31VQgAQ
Klein drivers amzn.to/3qoe21W
Knipex Wrenches amzn.to/3trzFjS
Klein 11-1 amzn.to/3tpsPLD
12” crescent amzn.to/3A0CZ6S
Gerber Gear Pocket Knife amzn.to/3foaW7I
Yellow Jacket Hand Ratchet amzn.to/3nrDgup
I am on Discord & WhatsApp!
Discord: / discord
WhatsApp Group: chat.whatsapp.com/CHZWtZe4KMG...
Mikey Pipes Uncensored: / @mikeypipesuncensored
New oval raised silver stickers are from:
Armored Decal Company Inc.
35 Victoria St. E, Unit 9
Alliston, Ontario L9R 1T3
(p) 705-435-6665
(e) ken@armoreddecal.com
(Tell them Mikey Pipes sent you)
Please support this channel and Mikey Pipes and consider the following…
Pipe Doctor FlexFit Embroidered Caps
Minimum donation of $37 is appreciated
(If you are international - please add a minimum of $40 for shipping/postage)
Shopping on Amazon? Please use my referral link amzn.to/2PjjS4v
Sticker Requests:
Do you want a sticker to show your support of this channel? Email your request to me! mike@mikeypipes.com
Name
Address
City, State, Zip
Consider making a donation of $5.00, or ANY amount, to the postage fund! I literally mail out stickers all over the globe. I've sent stickers to HVAC guys in Afghanistan, New Zealand & all over Europe.
PayPal is: office@pipedoc.net
Venmo: @PipeDoctor
CashApp: $mikeypipesny
Zelle: mike@mikeypipes.com
Want to send a love letter, note or gift? Our mailing address is:
Mikey Pipes, Inc.
1010 Central Avenue
Woodmere, NY 11598
#mikeypipes #hvac #COMFORTSPECIALIST

Пікірлер: 116
@chuckq54
@chuckq54 5 ай бұрын
Kudos to this new client that wants to learn about his system, and is learning a lot from Mikey Pipes videos 👍👍🏆🏆
@PipeDoctor
@PipeDoctor 5 ай бұрын
:)
@ThatEMOguy74
@ThatEMOguy74 5 ай бұрын
Wasn't expecting my comment that I left a few weeks ago about the magnetic filter coming up in a video and a customer asking about doing that to their system
@PipeDoctor
@PipeDoctor 5 ай бұрын
It’s actually a good idea.
@wizard3z868
@wizard3z868 5 ай бұрын
Lol kind of funny how simple things get attention I remember I made the joke of calling mikeys shortest time employee nicknamed him shake n bake 😅 and that took off 😮
@jayclark5912
@jayclark5912 5 ай бұрын
Doc Mikey definitely reads the comments. The more subs the more impressive that gets.
@PipeDoctor
@PipeDoctor 5 ай бұрын
even the replies to replies:)@@jayclark5912
@lakeshvac
@lakeshvac 5 ай бұрын
Many manufacturers recommend using them we use boiler mag. Can be installed in horizontal, vertical, or angle because the filter can be set as needed
@walterbordett2023
@walterbordett2023 5 ай бұрын
Kudos to the homeowner for learning about his system and how to operate and maintain it. Kudos to Mikey for the tutorial on how the system is not correctly installed and what that means to the homeowner. Hacks bring you stacks, and good work well explained brings you loyal customers.
@unknownvalor9755
@unknownvalor9755 5 ай бұрын
Mikey the thing I love most about your channel is you take time to explain WHY on everything! to the best of your ability so those watching can understand. I feel that Hvac trade schools should play your videos because of the real world problems you encounter and the way you explain what's wrong and how to fix it........ in detail.
@PipeDoctor
@PipeDoctor 5 ай бұрын
thank you. i value the feedback.
@BlahBlah-em2ed
@BlahBlah-em2ed 5 ай бұрын
Heart of a teacher.
@PipeDoctor
@PipeDoctor 5 ай бұрын
thank you!
@davidriccitiello6421
@davidriccitiello6421 4 ай бұрын
Mike, I've been spraying wd40 on my Isuzu Cabover NPR truck motor, 4.8 since 2003. They are built with lots of aluminum parts. This motor still looks new with no oxidation. WD is like magic, and it protects everything under the cab. Nice to see you're using it in the same manner. Another real good educational video.
@PipeDoctor
@PipeDoctor 4 ай бұрын
Thanks for sharing
@madusan1
@madusan1 5 ай бұрын
Mikey just shows how you are educating the masses! Great video!
@PipeDoctor
@PipeDoctor 5 ай бұрын
I appreciate that!
@theodorgiosan2570
@theodorgiosan2570 5 ай бұрын
The size of the vent tapping is unimportant. The size of the orifice on the vent is important. That is probably a straight Gorton D. It flows 0.330 CFM at 1 ounce of pressure as per the chart in Lost Art. A Gorton 1, which has a 3/4 inch tapping, also flows the exact same 0.330 CFM. Alternatively, the straight pattern Heat Timer Varivalve flows over 0.600 CFM, nearly double either of the Gortons, and has a 1/8 tapping. A 1/8 tapping is capable of flowing 1.200 CFM. A Barnes and Jones Big Mouth flows over 2 CFM and has a 1/2 or 3/4 tapping. So even the tiny Varivalve is a better bang for your buck than the #1. But a 1/8 tapping will flow more than 99% of the vents out there. The tapping is not the restriction, the top orifice is. Take a look at the vent CFM charts in Lost Art. Both the Radiator vents and Main Vents chart. Compare the Gorton D and 1. Both 0.330 CFM despite different tapping sizes.
@kdawson020279
@kdawson020279 4 ай бұрын
That's really useful info. I was aware of the differences in orifice size; in practice, people paint them and reduce that orifice sometimes dangerously. I'd love a good quick reference for a lot of this stuff; all the boiler guys bailed when stuff got crazy in 2020 and the brain drain has been nuts. It's worrisome as I know the boilers need more maintenance than they get and I am spread very thin at work.
@eldoradoboy
@eldoradoboy 5 ай бұрын
excellent video... Love this!! Lots to learn in here and see first hand how bad a system can act when its not piped correctl;y.. theres a lot of videos Talking about banging and water hammer and such when the piping is incorrect.. here it is right on video.. you can hear the pipes clamouring you can see the turbulence in the sight g;lass first hamd.. Love this!!
@kens.3729
@kens.3729 5 ай бұрын
Many Don’t know there is a BIG Difference in Every Field and HVAC is NO Different. I Won’t Trust just Anybody with my Families Life. Quality is Worth Paying for. 👍🙏
@paulphillips4148
@paulphillips4148 5 ай бұрын
Your motto hacks bring me stacks comes to life with this boiler.
@HERITAGEWV
@HERITAGEWV 5 ай бұрын
Tap out the burner tubes After you brush them that way you dump out any of the debris that you brush and knock loose into the burner tube. Might not really matter, that’s just how I do it to get all the crap out of tubes that gets brushed loose
@compactc9
@compactc9 5 ай бұрын
I wish they made a cordless vacuum that actually had enough suction to hurt my hand, like my corded Henry work vacuum. Cords can be inconvenient, but Ive yet to see a cordless that can unclog a central vac system.
@PipeDoctor
@PipeDoctor 5 ай бұрын
👌
@citylockapolytechnikeyllcc7936
@citylockapolytechnikeyllcc7936 5 ай бұрын
I am at 9:09 in, and you have not even MENTIONED the OIL BURNER switchplate! Mikey.... Aware of surroundings? Forget the wrong Hartford Loop, get a sticker on that switchplate! lol
@TheRAMBO9191
@TheRAMBO9191 5 ай бұрын
Just in time for dinner
@PipeDoctor
@PipeDoctor 5 ай бұрын
Dinner is served.
@TheRAMBO9191
@TheRAMBO9191 5 ай бұрын
@@PipeDoctor just finished. Sounds like it could be a hefty repair for that poor guy due to hacks. If he wants to pursue it being done correctly for long time could be well worth it. Hopfully he gives you guys the job for a video, would love to see the fix.
@scotts4125
@scotts4125 5 ай бұрын
When I saw the thumbnail I thought Pipe Doctor is not so proudly expanding to Bedford Mass. :)
@PipeDoctor
@PipeDoctor 5 ай бұрын
lol
@GoldenPlumbingNaples
@GoldenPlumbingNaples 5 ай бұрын
How many of ya’ll know that the Hartford Loop is named after the insurance company The Hartford that is still around today
@captainwho1
@captainwho1 5 ай бұрын
Just curious about the high stack temperature. Does it mean that the heat transfer of the combustion gases to the boiler is inhibited by carbon buildup and needs cleaning? How would you clean it, do you have to remove the jacket from the boiler or can you clean it with a bottle brush from underneath? Nice video thanks!
@aaronkoster3940
@aaronkoster3940 5 ай бұрын
Issue with magnetic filtration is that creates larger pressure drop, which may require additional A dimension height, to overcome the pressure drop(see Dan Holohans Lost Art of Steam Heating).
@jcaleca60
@jcaleca60 5 ай бұрын
Amazing how you disconnected the pressure control and the low water cut off went off at the same time play the lotto😊 that some coincidence
@compactc9
@compactc9 5 ай бұрын
I love informed customers. Some people seem to prefer clueless ones, but I find the more the customer knows, the easier my job is. As long as you're not full of shit, a smart customer is your friend.
@PipeDoctor
@PipeDoctor 5 ай бұрын
Bingo
@ThumperKJFK
@ThumperKJFK 5 ай бұрын
Wow. you cannot make this stuff up. Mikey you do great service, and keep it real. No Bull S***. Another great video. Thanks 👍✌
@BkSmoke-xr3dy
@BkSmoke-xr3dy 2 ай бұрын
Mike pipes = Mikey the hack 😂
@TasoV.
@TasoV. 5 ай бұрын
Wonderful stuff Mikey Pipes...if anything now I know WD-40 is good for bird poop on a car 😁Always enjoy watching and learning, see you on the next one!
@stanthurman9008
@stanthurman9008 4 ай бұрын
Your brakes don’t work to well at stop signs , huh , sorry , liked your show , but where I live they write tickets for non stopping , and I’m jealous yaw got snow , keep up the awesome job .
@PipeDoctor
@PipeDoctor 4 ай бұрын
Good thing I don’t drive where you live
@Joop5000
@Joop5000 5 ай бұрын
Hey Mikey, Great video! Now that is one smart customer, he wanted Mikey the man and only the man to come help him out and Mikey the man obliged! How many companies would honor a request as such and make the customer happy? Also, i was thinking, perhaps when you disconnected the pressure trol wire and the low water light come on, it could only be that the 24 volts was interrupted at the low water unit and was just going through it's cycle when you reconnected it. The customer did drain water while you were there and even though it looked as though there was enough water to satisfy the low water unit, perhaps the low water cut off probe is a little dirty.
@scottmaz4063
@scottmaz4063 5 ай бұрын
That return is loaded with water
@cetewayotyson9889
@cetewayotyson9889 5 ай бұрын
All day long
@geneticdisorder1900
@geneticdisorder1900 5 ай бұрын
@@cetewayotyson9889 and nights, weekends and holidays
@gmard1
@gmard1 5 ай бұрын
Mike you know your stuff. That looks like a mess
@PipeDoctor
@PipeDoctor 5 ай бұрын
Thanks.
@xmonte7835
@xmonte7835 5 ай бұрын
Love the random fuzzywuzzy lol
@PipeDoctor
@PipeDoctor 5 ай бұрын
Sorry
@Jimmypupkin
@Jimmypupkin 5 ай бұрын
Nothing stops the pipe Dr. not even a 🛑
@PipeDoctor
@PipeDoctor 5 ай бұрын
sure dont
@Evansautorepair
@Evansautorepair 5 ай бұрын
How Mike you should hire that guy as a technician.
@PipeDoctor
@PipeDoctor 5 ай бұрын
:)
@michaelknapp9296
@michaelknapp9296 4 ай бұрын
Mikey pipez doesn’t do push ups, he pushes the earth down.
@PipeDoctor
@PipeDoctor 4 ай бұрын
@MikeyPipesOrlando is looking forward to a personal factory tour with his iphone in hand! Will make great content to share with the entire WORLD!! #WeInstallLochinvar
@deanguando1335
@deanguando1335 5 ай бұрын
Those 2 pipes leading underground are ticking time bombs.
@throttlebottle5906
@throttlebottle5906 5 ай бұрын
very likely leaking all the condensate return into the ground and refilling constantly.
@JT-qf4it
@JT-qf4it 5 ай бұрын
The WD40 may seem like a good idea but it does not add any protection to the metal pipe. The protection it does give is gone as soon as it evaporates.
@JT-qf4it
@JT-qf4it 4 ай бұрын
@MMattesIt depends on the application. If some of it is trapped within the joint, it may last longer. WD stands for "Water Disspersent" It was not made to be a lubricant. It only lubricates because it has an oil base.
@lg3187
@lg3187 5 ай бұрын
I would install a proper reducer inn the flue and check the temp again. you may have air from the room going up the chimney instead of from the boiler
@davidlampe4153
@davidlampe4153 5 ай бұрын
Very interesting video thank you. Why not use the Gifford loop instead of the Hartford loop? The Bottom of the Gifford loop should be equal to the top of the water line. Returning the condensate from the Gifford loop will be quieter than the Hartford loop.
@danguib9061
@danguib9061 5 ай бұрын
Mikey you roll through 2 stop signs in your intro not good be careful 😂😂😂😂
@NuncNuncNuncNunc
@NuncNuncNuncNunc 5 ай бұрын
"If you're not testing, you're guessing." You can tell a Mikey Pipes client...and you can tell him much.
@Ariccio123
@Ariccio123 5 ай бұрын
13:37 does anybody use some kind of deaerator for boiler feed water? I don't know how it would work for residential heat, but I know they're common with industrial boilers
@petersamios5409
@petersamios5409 5 ай бұрын
Once again - nice descriptions for what and why you were doing things. As for the Hartford loop being missing - I thought it was required by law to be there. At a minimum, it is required for the warranty of the boiler (and probably for home insurance on the boiler). I understand your wariness of the old black pipe from the ground, but I believe you could mega press a fitting - especially if you are below the water line. I'd push the homeowner to change the piping - from both a safety and a warranty perspective. As for the previous installer, it looks like they were used to water boilers and not steam and just cludged he rest.
@aaronkoster3940
@aaronkoster3940 5 ай бұрын
The current boiler has the protection of the Hartford Loop. Just the excess height can contribute to water backing up in the main
@aaronkoster3940
@aaronkoster3940 5 ай бұрын
There is a Hartford loop. Just it's way to high
@rickchapman9232
@rickchapman9232 5 ай бұрын
I thought you were going to work on one of those fire tube boilers.
@aaronkoster3940
@aaronkoster3940 5 ай бұрын
After filling boiler with new water, run boiler for at least 20 minutes, to boil out the oxygen.
@josephholcombe78
@josephholcombe78 5 ай бұрын
You should start a pipe doctor university
@dominicm2175
@dominicm2175 4 ай бұрын
The steam pipes are clearly pre-existing to the boiler, and has likely been fine for the 80 years the house has been there. I’d bet anything the newer boiler was installed by the previous homeowner.
@PipeDoctor
@PipeDoctor 4 ай бұрын
Sorry. You are wrong. Modifications made by idiots who have no right touching it.
@jasongeo2
@jasongeo2 5 ай бұрын
Great video....now bring out the Latinas Chicas 🎉
@oscarmoreno768
@oscarmoreno768 5 ай бұрын
Let the boiler to cool and then flush it to prevent degradation of the heater exchanger
@KevinKinder-ey9gv
@KevinKinder-ey9gv 5 ай бұрын
Diy install on that boiler
@GranolaEngineering
@GranolaEngineering 4 ай бұрын
Gd Morning . Once you referred to an author who wrote couple of books on steam heating systems . would you again ?
@PipeDoctor
@PipeDoctor 4 ай бұрын
Dan Holohan
@robertconreux8079
@robertconreux8079 5 ай бұрын
The way the boiler is piped is very inefficient the vent needs to be connected correctly he needs to have you correct the piping and venting then retest the efficiency! This customer was very wise to call you!
@domenicdalleva1045
@domenicdalleva1045 5 ай бұрын
Should the boiler have a safety valve instead of a relief valve. I have learned that safety valves are for steam. And relief is for water units, the safety will prevent a boiler from blowing up.
@geneticdisorder1900
@geneticdisorder1900 5 ай бұрын
Haaaaah, I saw that reducer in the pressure blow drain line, I first thought the copper 90 was jammed onto a blk nipple. Slap dat hack Mikey !!
@PipeDoctor
@PipeDoctor 5 ай бұрын
f'en hacks
@damionfragoso2655
@damionfragoso2655 5 ай бұрын
Slant fin?
@PipeDoctor
@PipeDoctor 5 ай бұрын
Yes
@andyvitz
@andyvitz 5 ай бұрын
By the way the date is right now the 21st
@throttlebottle5906
@throttlebottle5906 5 ай бұрын
that is one of the homes you'd normally see have an boiler explosion, fire and deaths! it needs turned off, disabled and whomever installed, sold, rented, leased the place needs a big lawsuit.
@jakobporterz3211
@jakobporterz3211 4 ай бұрын
Did you just blow that stop sign
@PipeDoctor
@PipeDoctor 4 ай бұрын
yes
@scottvolage1752
@scottvolage1752 5 ай бұрын
Another fine video by Mikey Pipes. Keep up the good work and Smash the like and Subscribe please folks. Welcome to the new guy.
@PMG526
@PMG526 5 ай бұрын
🥇
@jimmy8653
@jimmy8653 5 ай бұрын
Amazon boiler
@PipeDoctor
@PipeDoctor 5 ай бұрын
lol. Damnit Jeff Bezos
@jayclark5912
@jayclark5912 5 ай бұрын
People out there getting work done. Contractors are also guests. Shovel the snow and pick the dog shit. You may get a better quote if you show a little respect.
@jasonthewiczman5442
@jasonthewiczman5442 5 ай бұрын
Simple things in steam boiler policy not being enforced by tom - your right'
@apollorobb
@apollorobb 5 ай бұрын
Weakest attempt ever to hide an identity lol
@PipeDoctor
@PipeDoctor 5 ай бұрын
Huh?
@apollorobb
@apollorobb 5 ай бұрын
@@PipeDoctor The Blurs?
@johnwalker890
@johnwalker890 5 ай бұрын
Maybe they don't call themselves professionals, and they are fly by night boiler installers.
@PipeDoctor
@PipeDoctor 5 ай бұрын
With a tail light warranty
@scottmaz4063
@scottmaz4063 5 ай бұрын
#1🎉🎉😂😂😂
@PipeDoctor
@PipeDoctor 5 ай бұрын
fast!
@scottmaz4063
@scottmaz4063 5 ай бұрын
Mike if your going to work on this mess cut that return high just below elbow then put hose in to pump out the return.
@steveblake8766
@steveblake8766 5 ай бұрын
409 thumbs up
@PipeDoctor
@PipeDoctor 5 ай бұрын
Thanks
@Mridgwell
@Mridgwell 5 ай бұрын
Uno!
@KevinSmith-be3or
@KevinSmith-be3or 5 ай бұрын
You’re good at what you do, no questions asked! But good lord my guy stop acting like you’re the only guy who does plumbing or HVAC. Your channel has lost a lot of followers cause the way you act. I’m a follower but you never show up on my subs.
@dennisdorn1404
@dennisdorn1404 5 ай бұрын
There are Master Plumbers cutting corners or just forgetting the proper way . Seems Mickey stating the correct way to Plumb is his way of making the trades great again .
@paulyanega2373
@paulyanega2373 5 ай бұрын
what a shit show
@PipeDoctor
@PipeDoctor 5 ай бұрын
Exactly
@paulmillner
@paulmillner 5 ай бұрын
Iron or steel are magnetic... rust is not. So how would a magnetic filter help?
@throttlebottle5906
@throttlebottle5906 5 ай бұрын
@@paulmillneryou do realize rust is just small to micro-particles of common ferrous magnetic metals right? 😶
@lancepushy7783
@lancepushy7783 5 ай бұрын
MYKEY u keep leaving to garbage Florida and letting the hacks roam New York
@user-zc4zf7wg9d
@user-zc4zf7wg9d 4 ай бұрын
Yes let’s get it This is cool. I watch the Boiler Hero videos he’s a awesome teacher. Boiler mechanics are the truth! Treat them all with respect 🫡
New Hire Has Seizure During 1st Hour on Job & Leaves in Ambulance - Didn't Disclose Medical Issues
34:44
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 25 М.
Neighbor Thought He Was an HVAC Tech or Plumber Didn't Help - Burnham Gas Boiler No Heat
21:22
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 102 М.
Now THIS is entertainment! 🤣
00:59
America's Got Talent
Рет қаралды 40 МЛН
Nastya and SeanDoesMagic
00:16
Nastya
Рет қаралды 31 МЛН
World’s Largest Jello Pool
01:00
Mark Rober
Рет қаралды 57 МЛН
New Hire: Last Service Call House Water Main Shut Off & Entire House Valve Replacement
31:19
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 21 М.
Another HVAC Contractor Condemned AC System We Brought Back to Life!
23:23
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 37 М.
GAS PIPE IN HOME BROKE FILLED HOUSE WITH GAS
37:11
steven lavimoniere
Рет қаралды 44 М.
Steam Boiler Would Have Exploded Resulting in Deaths - Found T&P Relief & Defective Pressuretrole
1:12:41
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 30 М.
Pilot Refuses to Land
17:49
74 Gear
Рет қаралды 1,6 МЛН
If I touch this tower, I die
43:19
Geerling Engineering
Рет қаралды 1,1 МЛН
30 Minute Secret Makes Your Water Heater Last Decades
13:03
LRN2DIY
Рет қаралды 2,1 МЛН
What is a Combi Boiler? Compact Mechanicals with Wade Paquin!
11:49
Matt Risinger
Рет қаралды 35 М.
Who Sent This Gift From Ms. Molly - Burnham SIN5 Installation - Oil to Gas Steam Conversion Giveaway
56:48
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 26 М.
Homeowner Tries To Fix Gas Boiler and Fails Miserably How to Bled or Purge Zones
31:54
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 113 М.
Small Act of Kindness is also a charity
1:00
PainCare _Trust
Рет қаралды 25 МЛН
РЫБАЛКА ДОМА
0:17
KINO KAIF
Рет қаралды 13 МЛН
No empty
0:35
Mamasoboliha
Рет қаралды 3 МЛН