Рет қаралды 5,805
In part 2 Marcus looks once again at calculating the total earth fault loop impedance of a circuit and explains the elements of the formula Zs = Ze + (R1 + R2). The video looks at how we can add a temperature factor to the calculated values of R1 + R2 which is the the resistance of the line conductor added to the resistance of the CPC. By using the temperature factors found in the On-Ste Guide this means the designer of the circuit can use the 100% values of the maximum earth fault loop impedance found in BS7671 and not the rule of thumb 80% of this value.
🔔 Subscribe for more free electrical training videos kzfaq.info?s...
== 🕐 Time Stamps - Cut to the action 🕕 ==
00:00 - Calculating total earth fault loop impedance Pt2
00:38 - Calculation parameters
01:20 - Use the latest On-Site Guide
01:31 - Size the conductors
01:58 - Temperature factors
02:37 - R1 + R2 allowing for a temperature factor of 1.2
03:42 - Total earth fault loop impedance
04:43 - 6 amp type C BSEN60898 MCB
04:53 - Maximum Zs values in BS7671
🔵 How to Calculate Total Earth Fault Loop Impedance - Applying a Temperature Factor to R1 + R2 • How to Calculate Total...
🔵 Earth Fault Loop Impedance (Zs) - Testing 16 Amp Industrial Socket Outlets Both Single and 3 Phase • Earth Fault Loop Imped...
🔵 Earth Fault Loop Path for a TN-S Earthing Arrangement & Formula For Total Earth Fault Loop Impedance • Earth Fault Loop Imped...
🔵 Total Earth Fault Loop Impedance Zs = Ze + R1 + R2 for TN-S and TN-C-S Earthing Arrangements
• Total Earth Fault Loop...
Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.
You can follow me day by day on Facebook, Instagram, Twitter and TikTok lookout for "GSH Electrical.