HOW TO RACK OUT VACUUM CIRCUIT BREAKER | ETO TROUBLESHOOTING

  Рет қаралды 102,333

leckyjake

leckyjake

3 жыл бұрын

Here is the step by step procedure of the proper racking out of our onboard VCB.
***
DISCLAIMER: The views and opinions expressed in this video are those of the video owner and vlogger and do not necessarily reflect the policies and position of the employer, the company and its management.

Пікірлер: 150
@jeffcarter6516
@jeffcarter6516 2 жыл бұрын
As a power plant operator for 20+ years I have racked out thousands of breakers. 2 things, first where is your arc flash hood? Arc flash clothing is great but your face would be roasted. Secondly, where are you remote racking devices? 60 year old coal plants have remote devices. When you read the arc flash rating on switch gear there is a boundary to set-up. With remote racking device you can remain outside of boundary. Another great addition are arc sentry or maintenance mode on switchgear. Changes relay settings for when racking breakers for your safety.
@chrisharrell5945
@chrisharrell5945 Жыл бұрын
Exactly...there some things in life you just don't do and playing around switchgear and motor control centers without proper PPE is one of them. Remote actuator even better.
@crestfallenwarrior6996
@crestfallenwarrior6996 4 ай бұрын
Arc flash mode drops for load side. Still potential for line side arc flash energy. However , it would lower PPE requirements , in full agreement with this comment
@bryanp.1327
@bryanp.1327 2 жыл бұрын
I love the key interlock system, enforces steps in order to proceed. Very cool.
@juscelino2253
@juscelino2253 2 жыл бұрын
me too
@gorillaau
@gorillaau 2 жыл бұрын
I hope one of the keys do not go missing. That would be annoying.
@nikhillllLlllllllllllllllll
@nikhillllLlllllllllllllllll 3 жыл бұрын
Please make more videos. Utter respect for what you do for beginners
@davidgrisez
@davidgrisez 2 жыл бұрын
I am retired from working at the Los Angeles DWP Scattergood Generating Station. I have racked out and racked in 4160v circuit breakers and 480v circuit breakers. There was a set of safety procedures to rack in and rack out these circuit breakers that had to always be followed. The circuit breakers at Scattergood Generating Station were older than the circuit breakers in this video.
@tomasviane3844
@tomasviane3844 2 жыл бұрын
Thanks for the video. It made me feel more confident while changing the battery of my kitchen-clock!
@fudjeehaya2331
@fudjeehaya2331 3 жыл бұрын
It would be realy knowledgeable to be cadet electrician with you sir. 😁
@inothome
@inothome 2 жыл бұрын
Great video, but gloves always need to have glove protectors on them. Never use the bare rubber gloves.
@cliveramsbotty6077
@cliveramsbotty6077 2 жыл бұрын
never even heard of glove protectors before but now i know thanks
@electromechanicalstuff2602
@electromechanicalstuff2602 2 жыл бұрын
@@cliveramsbotty6077 leather gloves always go on top of the rubber otherwise they are one time use gloves per NFPA70E
@alterator
@alterator 3 жыл бұрын
This is one of the most useful video! Hello from Russia, my teacher!
@fredsalter1915
@fredsalter1915 2 жыл бұрын
This Filipino guy is the boss! He should have much more than 20k subs!
@leckyjake
@leckyjake 2 жыл бұрын
Thank you very much for this wonderful comment
@UB2KTV
@UB2KTV 3 жыл бұрын
keep your informative vlogs coming you educate many aspiring electrical fans
@alystair
@alystair 2 жыл бұрын
I've never seen this sort of thing before - the keying system is such an awesome idea that other industries should use - you can't access the next key without all previous steps.
@bt9604
@bt9604 Жыл бұрын
Hey why do we need excitation key, what is normal and DE excitation
@aaronfitzgerald9109
@aaronfitzgerald9109 Жыл бұрын
That's widely used in the electrical industry
@michaeljburt
@michaeljburt 3 жыл бұрын
Great video, I'm a sparky and I had a vague idea how this works but what a wonderful explanation!
@SedatedByLife
@SedatedByLife 2 жыл бұрын
And to think my love of electricity and troubleshooting brought me to this channel and can't get enough now...
@akshaydevadiga6838
@akshaydevadiga6838 3 жыл бұрын
Great job sir. Your videos are very helpful. Love to watch more videos from you. Thank you.
@sandeepsrinivassinghkshatr1906
@sandeepsrinivassinghkshatr1906 3 жыл бұрын
Great effort sir ...... u make useful vedios which no other ETO do apart from the heavy work u have onboard u Take extra effort in doing such a wonderful videos and helping others great respect to u sir love u keep on making videos.........
@leckyjake
@leckyjake 3 жыл бұрын
Thank you for your wonderful comment. Please do not forget to share the video
@juscelino2253
@juscelino2253 2 жыл бұрын
so useful, i can learn more from this video than from the dudes in my job. thanks sir
@gearroompayrush42
@gearroompayrush42 2 жыл бұрын
nice one boss..ganyan yung work ko sa dubai electrcity..more power
@PracticalMECEngineStudy
@PracticalMECEngineStudy 2 жыл бұрын
Thanks a lot for making such videos. Its really helpful for us . It also enhances confidence in us.Thanks.
@relaxtv7733
@relaxtv7733 3 жыл бұрын
this kind of video must be watching of all youth in this generation... knowledge video so they explore some good things and it will be useful in their life someday... but so sad that all youth today is more attracted to none sense video... vlogger sorry to say to this generation.. goodluck sir keep it up and inspire others that one to learn more in tech world..
@Tulfonatic-sarcasticsm
@Tulfonatic-sarcasticsm 3 жыл бұрын
astig sir... thanks very informative
@rodeldurban4534
@rodeldurban4534 3 жыл бұрын
Nice video sir.. Very informative and helpful.. Bka meron po kyo video ng replacement ng crank angle encoder, mpc replacement at me overspeed test.. Thanks in advance..
@josephpaulabapo4796
@josephpaulabapo4796 2 жыл бұрын
Thank you for portion out of your actual experience and idea.
@murugaperumal6823
@murugaperumal6823 2 жыл бұрын
awesome bro, I am going to join ETO Course coming march,. It Will definitely help me in future .....
@patsroll
@patsroll 3 жыл бұрын
Awesome stuff doing this in college in high volage with sf6 gas circuits breaker
@aldrincutarra4198
@aldrincutarra4198 Жыл бұрын
Thanks for the video sir. It helps me a lot for my MHV training
@jonahtacastacas8672
@jonahtacastacas8672 3 жыл бұрын
Kirk key interlock for safety operation. Thank you for sharing this video. 👍
@25denzil
@25denzil 3 жыл бұрын
Thanks for sharing the procedure
@reohsamjale6116
@reohsamjale6116 3 жыл бұрын
thank you for sharing. your knowledge sir
@manuellastrollo2168
@manuellastrollo2168 Жыл бұрын
master gawa ka rin ng video ng difference ng ACB & VCB. Salamat. Abangan ko yun master👍
@johnwilliampolicarpio
@johnwilliampolicarpio 3 жыл бұрын
Sir ang galing nyo po sana ma experience ko din yan low voltage po kasi minimaintain namin ,,
@Electronzap
@Electronzap 3 жыл бұрын
Those are interesting looking keys at 02:00 . Cool video!
@alexivin3533
@alexivin3533 3 жыл бұрын
Thank you!
@ahmadradhi6168
@ahmadradhi6168 2 жыл бұрын
tq for the sharing sir.. hope to see more vids from u sir 👍
@richardlanuza8341
@richardlanuza8341 Жыл бұрын
Appreciate lecky jake:salamat sa info
@user-ux8ye1zi2d
@user-ux8ye1zi2d 2 жыл бұрын
Super interesting, thanks!
@mithileshramteke3882
@mithileshramteke3882 3 жыл бұрын
Nice explanation thank you 😊
@AbhilashKsupernovaabhi
@AbhilashKsupernovaabhi 3 жыл бұрын
Nice video 🙂good work
@terencewright2223
@terencewright2223 Жыл бұрын
Excellent video, thank you very much.
@johnelduroya6233
@johnelduroya6233 3 жыл бұрын
Maraming salamat sir
@HectorideMoto
@HectorideMoto 3 жыл бұрын
nice video... keep safe always po and keep it up...
@aliciaadriano8751
@aliciaadriano8751 7 ай бұрын
Ser mam chinise che Ang galing naman ng Employee n'yo sana; @LL
@godfreydubrea8847
@godfreydubrea8847 3 жыл бұрын
Thank you very much sir we learned a lot on your channel
@leckyjake
@leckyjake 3 жыл бұрын
Thank you very much for your support. Please do continue to support my channel and do not forget to share
@twinsaviabrailee5176
@twinsaviabrailee5176 2 жыл бұрын
Nice learning bro.
@deesteps2880
@deesteps2880 2 жыл бұрын
Very useful electrician from zimbabwe
@leckyjake
@leckyjake 2 жыл бұрын
Thank you. Regards
@abdullahseba4375
@abdullahseba4375 2 жыл бұрын
Really interesting to see ship electrics!
@sohailjanjua123
@sohailjanjua123 2 жыл бұрын
Hi I Like your video. Thanks
@Arunkumar-lp1pk
@Arunkumar-lp1pk 3 жыл бұрын
Awesome video sir!!
@leckyjake
@leckyjake 3 жыл бұрын
Thank you
@upendraraju7903
@upendraraju7903 3 жыл бұрын
Sir please make a video of synchronization of generators please sir i am big of fan of u from India 🇮🇳
@ronnieluzon8646
@ronnieluzon8646 3 жыл бұрын
its same function of my work as electrical maintenance in industrial plant.
@runtowinmotivation3346
@runtowinmotivation3346 3 жыл бұрын
Super sir
@2loco
@2loco 2 жыл бұрын
Thank you for sharing. Now when my circuit breaker in my home trips I'll know what not to do to reset it 🤣🙃
@hancecrawford
@hancecrawford 7 ай бұрын
I have worked on 6.6 KV always check everytime so no mistakes
@surendrakverma555
@surendrakverma555 Жыл бұрын
Thanks 🙏🙏🙏🙏🙏🙏
@Automationacademytv
@Automationacademytv 2 жыл бұрын
THANKS IDOL
@andrewtan9687
@andrewtan9687 5 ай бұрын
May I suggest that if you want to refine this video, please include "turn the Local/Remote switch to Local" before you start the isolation process and only turn the "Local/Remote switch to Remote" when the Circuit Breaker is in Service position. The purpose being to be in full control of your switching operations. If you have competent persons working at the Marshalling box, there is a possibility that they may short two points to close the Circuit Breaker accidentally remotely from where you are operating the circuit breaker, don't you agree? Part of reason for Lockout and Tagout is to ensure there is no chance of erroneous switching during switching operations. My thoughts as an Authorised Person for voltages up to and including 22kV switching in Singapore. Anyway thanks for your sharing of circuit breaker operations. Have a great day.
@alanalanis1676
@alanalanis1676 3 жыл бұрын
Greetings from Mexico my ETO friend, great videos
@leckyjake
@leckyjake 3 жыл бұрын
Thank you for the support. Please do not forget to share the videos so that we can help others too :)
@alanalanis1676
@alanalanis1676 3 жыл бұрын
@@leckyjake done!
@leckyjake
@leckyjake 3 жыл бұрын
That’s so nice of you.
@eternityandinfinity5292
@eternityandinfinity5292 3 жыл бұрын
Sir, what specific job have you done after drawing out the VCB?
@orlevillacarlos5402
@orlevillacarlos5402 Жыл бұрын
sir just want to ask, is there a specific counting of turns when racking-in the vcb?
@user-jq1yj3mp2u
@user-jq1yj3mp2u 3 жыл бұрын
Eto job onboard keep safe.
@danzelwesingtone7413
@danzelwesingtone7413 Жыл бұрын
tysm boss
@udaynarayansishodia
@udaynarayansishodia 2 жыл бұрын
Hello sir, before disconnecting VCB do we remove supply to that particlar busbarto which vcb is connected?
@lecmen47
@lecmen47 2 жыл бұрын
Me encantaría trabajar como tú ayudante
@gufranshaikh4536
@gufranshaikh4536 Жыл бұрын
What ain’t you wearing Arc flash suit only 7.5 KV gloves were used while rack in rack out ??? What is the protection if there will be any flash over while Rack in ?
@gregparker8349
@gregparker8349 3 жыл бұрын
No worry of arc flash during rack out procedure? Take care nice work! Good video Sent from USA 🇺🇸
@johnangelodelacruz6431
@johnangelodelacruz6431 3 жыл бұрын
No mate because the system was already isolated, grounded and disconnected.safety first
@danielwinsor6018
@danielwinsor6018 2 жыл бұрын
Arc flash gear is necessary until the system is verified dead. Looks like this fella verified the system dead by earthing it. Oof. All it takes is one missed lock and you’re another arc flash horror story.
@bt9604
@bt9604 Жыл бұрын
@@johnangelodelacruz6431 Hey why do we need excitation key, what is normal and DE excitation
@donniever
@donniever 3 жыл бұрын
Sir, how about bucket type circuit breakers (low voltage breakers) if you have any, Thanks.
@electromechanicalstuff2602
@electromechanicalstuff2602 2 жыл бұрын
NFPA 70E gloves without leather can only be used once. No flash shield or balaclava. Arc flash potential in that cabinet most like requires 40 cal suit not 12 cal stuff it looks like he's wearing.
@rahamathkhan4019
@rahamathkhan4019 2 жыл бұрын
Sir could you please .. provide a cc caption below the video..it will understand easily 🤗
@subhashisbag6158
@subhashisbag6158 3 жыл бұрын
Grt job bro. Can u pls write the steps??
@anilkumar-wr3eh
@anilkumar-wr3eh 3 жыл бұрын
Make a video on DG syncronizing
@sanketkolhe5145
@sanketkolhe5145 3 жыл бұрын
Txx
@leckyjake
@leckyjake 3 жыл бұрын
👍👍
@life_xplorer
@life_xplorer 3 жыл бұрын
God bless u Lecky jeck... U will be at big possion one day.. thanx for video... Keep making videos... Nd keep spreading love with us
@jhova6542
@jhova6542 2 жыл бұрын
Hey folks you should really wear arc flash (not fr) Ppe including proper rated face shield and balaclava
@denis_ETO
@denis_ETO 2 жыл бұрын
hi! Which name your vessel ?
@temp229009
@temp229009 2 жыл бұрын
what's being grounded? the enclosure?
@halasanalexandergringop.6935
@halasanalexandergringop.6935 3 жыл бұрын
Hello Sir, how to apply to be an electrician on board? What are the processes?
@OtaniumPlanet
@OtaniumPlanet 3 жыл бұрын
Nice one! Why rack out the VCB...Was it faulty? and how do we tell when it's faulty?
@leckyjake
@leckyjake 3 жыл бұрын
Video for the reason will be uploaded soon
@hritikvasuja6250
@hritikvasuja6250 3 ай бұрын
sir which camera for shooting?
@coachhunter4412
@coachhunter4412 2 жыл бұрын
What is the purpose of de excitation key
@whatevernamegoeshere3644
@whatevernamegoeshere3644 2 жыл бұрын
What exactly is excitation?
@cyrildelacruzjr4365
@cyrildelacruzjr4365 3 жыл бұрын
Maganda Sana Kung Tagalog nalang para intindihan nila.. salamat SA magandang tutorial
@ThePhoenixAscendant
@ThePhoenixAscendant 3 жыл бұрын
Watching you is like watching a Resident Evil walk through... use this key to unlock that door to get that key to access a port to use a tool that then frees another key... lol
@leckyjake
@leckyjake 3 жыл бұрын
Thank you for watching
@aaronfitzgerald9109
@aaronfitzgerald9109 Жыл бұрын
Where is this?
@5Dale65
@5Dale65 2 жыл бұрын
No face protection?
@kishorkc4756
@kishorkc4756 2 жыл бұрын
What is really the grounding in a vessel the body of the vessel itself or anything else like any elctrode or cathode which is touching the sea water ??
@chrisharrell5945
@chrisharrell5945 Жыл бұрын
I guess it would depend on the coatings applied to the vessels...I know most saltwater sea fare worthies get ablative paints to their hulls, which shedding of electrons is how they peel off old dead cells to expose better layers of protection in the paint layers. Depending upon the voltage class we're considering in this conversation and some other factors, I would venture to say that the paint layers constitute some form of insulation. That said, I'm certain no vessel is sealed completely along every single facet of it's structure and ports, etc;. I don't know all the intricacies of those ships though...not certain the practice out there on the water but I would think, just like on land, bonding all of the metal structure to bring to water potential would be the ultimate and to achieve that a 'designated grounding electrode', perhaps something altogether separate from the hull would be the order of the day.
@hopiegil6141
@hopiegil6141 Жыл бұрын
Sir do you ever experience over feed of vcb?..if yes what counter measure you apply?
@leckyjake
@leckyjake Жыл бұрын
the vcb has always protection for over fee, reverese power and preferential
@michaelmorrison4201
@michaelmorrison4201 3 жыл бұрын
I have no idea what any of this is so forgive me when I ask what exactly goes wrong that requires this procedure?
@Techtronica99
@Techtronica99 2 жыл бұрын
Thanks for the video! Looks like the inspection on your gloves is expired. They need the be inspected annually or after each use if not using the leather insert. You can get little pinholes in the rubber. Your company needs to do this for you, and in the US is a big fine if they don’t.
@leckyjake
@leckyjake 2 жыл бұрын
We have spare and the expiry date is always written on the boxes. We are serious in dealing with safety.
@dmitrijborcov6481
@dmitrijborcov6481 2 жыл бұрын
Hi, did the busbar side is also deenergized or only gen side?
@leckyjake
@leckyjake 2 жыл бұрын
Bus bar is always energized
@dmitrijborcov6481
@dmitrijborcov6481 2 жыл бұрын
@@leckyjake thanks, you the best
@abhishekshekhar32
@abhishekshekhar32 3 жыл бұрын
Sir apart from ACB and VCB do we have other types of ckt breaker and does every ship have Vcb
@InTransitGaming
@InTransitGaming 3 жыл бұрын
you have SF6 breakers also
@rajeshloganathan6910
@rajeshloganathan6910 2 жыл бұрын
Sf6 not used in ship it liberate hazard gas in closed space mixed with air
@pgobservers
@pgobservers 2 жыл бұрын
SF6 gas itself is not toxic at all yet until it burns and that is super toxic. So whenever there is a S/G explosion, do not enter the switch room unless you are putting on proper respirators. It’s Hazmat zone. Toxicity. FAULTED SF6 GAS - Faulted SF6 gas smells like rotten eggs and can cause nausea and minor irritation of the eyes and upper respiratory tract. Normally, faulted SF6 gas is so foul smelling no one can stand exposure long enough at a concentration high enough to cause permanent damage. It is a potent greenhouse gas with a high global warming potential, and its concentration in the earth atmosphere is rapidly increasing. During its working cycle, SF6 decomposes under electrical stress, forming toxic byproducts that are a health threat for working personnel in the event of exposure.
@andyvan5692
@andyvan5692 Жыл бұрын
hey, you forgot to turn the vcb OFF, and depower the whole cabinet, before you earthed and racked out the breaker, you pulled the vcb with the power ON!!
@lorrylumberto2023
@lorrylumberto2023 3 жыл бұрын
Verynice leckyjake idol
@stevenormandin2059
@stevenormandin2059 2 жыл бұрын
can someone explain me how the heck you have high primary voltage in a ship WITHOUT watertight switchgears any water leaks in those rooms would be a death treat to any worker near by! need an explanation here?
@leckyjake
@leckyjake 2 жыл бұрын
The room, the engine room, the engine control room and all entry points are watertight.
@JohnInotgzgshfdhfdhgh
@JohnInotgzgshfdhfdhgh 3 жыл бұрын
if u dnt mind sir, why you need to racking out the VCB? AND what is the purpose?thnks.more power,godbless
@leckyjake
@leckyjake 3 жыл бұрын
You will find out in my next upload. VCB troubleshooting
@aldrinempalmado1774
@aldrinempalmado1774 2 жыл бұрын
Sir anung specific training kaya kelangan pra matutunan yan?.. Tnx
@leckyjake
@leckyjake 2 жыл бұрын
Marine high voltage sir
@astifcaulkinyeras
@astifcaulkinyeras 3 жыл бұрын
Might want to keep the racking handle off your leg and only let it touch your gloves.
@Marineelectricalknowledge
@Marineelectricalknowledge 3 жыл бұрын
Whereis high voltage ppe?
@jovencioperez5243
@jovencioperez5243 2 жыл бұрын
ano ung main trouble un lecky..
@510purple
@510purple 2 жыл бұрын
no arc flash gear?
@bt9604
@bt9604 Жыл бұрын
Hey why do we need excitation key, what is normal and DE excitation
@adamdeguzman3238
@adamdeguzman3238 3 ай бұрын
No need
@MuhammadQasim-fj5bn
@MuhammadQasim-fj5bn Жыл бұрын
Where is the face shield helmets?
@bt9604
@bt9604 Жыл бұрын
Hey why do we need excitation key, what is normal and DE excitation
@macangunung8969
@macangunung8969 2 жыл бұрын
Incorrect PPE...
VCB TRIP ALARM (VACUUM CIRCUIT BREAKER) | ETO TROUBLESHOOTING
11:47
BLACK OUT AND EMERGENCY GENERATOR, THINGS YOU NEED TO DO
11:20
Мы никогда не были так напуганы!
00:15
Аришнев
Рет қаралды 6 МЛН
HOW DID HE WIN? 😱
00:33
Topper Guild
Рет қаралды 45 МЛН
Дарю Самокат Скейтеру !
00:42
Vlad Samokatchik
Рет қаралды 7 МЛН
Русалка
01:00
История одного вокалиста
Рет қаралды 6 МЛН
BOW THRUSTER HIGH VOLTAGE TROUBLE | MARINE ELECTRICIAN
9:44
leckyjake
Рет қаралды 217 М.
Components of Vacuum Circuit Breaker | TheElectricalGuy
8:30
Gaurav J - TheElectricalGuy
Рет қаралды 5 М.
inoRAC2 Overview - Racking of 15kv PowlVac Circuit Breaker
2:49
LOGBULKER - loading logs operations
13:30
Log Bulker
Рет қаралды 394 М.
How Do Vacuum Circuit Breakers Work?
3:02
Circuit Breaker Wholesale
Рет қаралды 114 М.
Siemens spring loaded breaker
3:19
powersolverinfo
Рет қаралды 27 М.
Burnt VFD, Why?????
8:45
leckyjake
Рет қаралды 22 М.
Switching 11kV VCB Tamco
7:34
competence 33kv
Рет қаралды 2,5 МЛН
Vacuum Circuit Breaker - Drawout  "High Voltage Switchboard"
16:25
ACB Rack in Rack out Procedure.
6:36
The Rich Engineer
Рет қаралды 14 М.
Мы никогда не были так напуганы!
00:15
Аришнев
Рет қаралды 6 МЛН