How to wire a 400 amp double transfer switch. Generac Generator 400 amp Automatic transfer switch

  Рет қаралды 23,283

Electrical Code Coach

Electrical Code Coach

Жыл бұрын

We offer the #1 Electrical Exam Prep Program
FREE VERSION
electricalcodecoach.com/free-...
PRO VERSION
www.electricalexamcoach.com/m...
USB OR DVD PROGRAM FREE SHIPPING!!
electricalcodecoach.com/shop/...
400x Practice Exam PDF Download for only 14.99 electricalcodecoach.com/shop/...
2017 Tabs with FREE SHIPPING
electricalcodecoach.com/shop/...
2020 NEC TABS with FREE Shipping
electricalcodecoach.com/shop/...
2023 NEC TABS with FREE SHIPPING
electricalcodecoach.com/shop/...

Пікірлер: 50
@wfrencher80
@wfrencher80 Жыл бұрын
Journeyman electrician here. I work for a company that specializes in whole-house GENERAC generator installs. I've literally done this install at a customer's home. What I did was I installed a wire way under the two transfer switches. I took the generator cable from the generator to the wire way, and took the splices I made in the wire way up to E1 and E2 terminals of the two transfer switches. For me it's a cleaner install because the 4/0 aluminum or 2/0 copper service conductors take up a lot of space in the transfer switch. So the wire way just helps me keep the transfer switches from being overcrowded with conductors. I as stated by a previous post, I've never read or talked to any GENERAC representative who said those lugs were rated to have two conductors terminated in them. I would much rather use Polaris taps. I do like the GENERAC tray cable that has both the control wires with the power conductors grouped together. I like that it's direct burial, and we can purchase the cable in either aluminum or copper.
@larryduwa9955
@larryduwa9955 Жыл бұрын
If it’s a 400 amp transfer switch splice the load wires instead of the incoming to feed both 200 amp panels with one switch
@wfrencher80
@wfrencher80 Жыл бұрын
​@@larryduwa9955 A 400 amp service rated transfer switch from generac cost over $3,000. I can get 2 - 200 amp ATS's for $1600. It's just cheaper to go that route. And I'm sure it would be much easier to get ahold of 200 amp ATS's than 400 amp ones. I've installed 100s of GENERAC whole home generators and have not once seen a 400 amp ATS. I suspect that the space inside a 400 amp ATS would have to be sufficient enough to fit 4-2/0 (rated at 350 amps in parallel) conductors or 2- 500 kcmil conductors (rated at 385 amp) for the service conductors. Just things to think about during installation
@retiredperson4054
@retiredperson4054 Жыл бұрын
@@wfrencher80 William -- I like the idea of using a wire way under the transfer switches and my idea is to mount the transfer switches to the right and left of the 320A Meter Base and running the majority of the wires in the type 2 wire-way (the 3 panels will be mounted side-by-side on the exterior of my garage). I just have one question, with using the (2) 200A Generac Transfer Switches -- would a Generac certified installer/dealer install this type of configuration -- or would this combination not be something they would install and warranty?
@wfrencher80
@wfrencher80 Жыл бұрын
​@@retiredperson4054 Hey, sorry about the delayed reply, it's the busy season for us, so I don't have a lot of free time. Generac does have requirements for where they want their generator installed, but how you install the generator and transfer switch is based on the NEC code and what your inspector in your area will pass. So installing two transfer switches on the left and right side of the meter with a wireway under the three panels sounds fine. From the meter you'll take one set of service conductors to one transfer switch and another set to the other ATS. You'll run feeders from the generator to your wireway, then splice those feeders in the wireway, and run your spliced feeders from the wireway to both ATS's. That's how I would do it. And this is all code compliant.
@robertapreston4200
@robertapreston4200 Жыл бұрын
Apprentice 😊well done
@rupe53
@rupe53 Жыл бұрын
as a Generac trained tech, I can say those contactor lugs were not rated for 2 wires originally and if they changed something recently it would state that in the manual or on the lug. Best to install some insulated wire bugs to make the branch for generator load wires. Also, while working on the signal wires, disconnect the molded plug (white connector) at each module to prevent accidental powering of contactor solenoids too early in the game. Those load-shed modules must be used with central AC units, and they can be wired directly in series with the 24 volt AC contactor circuit. (at the air handler or outside unit) The modules have a preset time delay (3 minutes) after a power failure to eliminate multiple hard start attempts under high head pressure. They are marked "unit 1, 2, 3, 4" and each has another delay (spaced apart) so things don't restart all at once while the rest of the house is coming on-line. Best to wire all the AC units on the same module or you will have two AC units starting at the same time. The nice thing about the load-shed system is it's smart enough to watch the gen load (via frequency) and if the load is too great, it will shut down the last load for 5 minutes, then try again. It will do that 3 times then wait 20 minutes for another attempt. The idea is to allow another heavy appliance (water heater or well pump?) to finish a cycle. That load-shed is only rated for pilot duty, so any heavy loads like a pump or water heater must also have a relay system to tie into the module. Generac sells relay kits rated for these things, if necessary. Oh, Generac just upped their game to 26kw on the air-cooled sets. I don't think any of the other major players has an air-cooled that large.
@ElectricalCodeCoach
@ElectricalCodeCoach Жыл бұрын
Thank you for sharing!
@billwalton4120
@billwalton4120 Жыл бұрын
These are the comments I love to see. Thanks
@fernandogonzalez6617
@fernandogonzalez6617 5 күн бұрын
Great work and information.
@knighttrain2579
@knighttrain2579 Жыл бұрын
I’ve done several of these. The schematic only shows connecting the white and red low voltage wires to the second switch for transfer. Learned the hard way. The black ground wire must be present to the second switch for automatic transfer. Generac didn’t suggest this through tech support. Great job coach.
@jorgehuizarsr8519
@jorgehuizarsr8519 Жыл бұрын
Hi from Southern California Thanks coach ✌️👌
@juanjr330
@juanjr330 Жыл бұрын
Best video yet great examples
@aranathm2818
@aranathm2818 Жыл бұрын
Thank you for this great material and explained very well.
@davidkespo1437
@davidkespo1437 6 ай бұрын
Great video. Thank you so much. I have been trying to understand this setup for months. This was very clear. You explain things very well.
@ElectricalCodeCoach
@ElectricalCodeCoach 6 ай бұрын
Lets Go!! Thank you so very much for your feedback!
@stanleykania7184
@stanleykania7184 Жыл бұрын
Thank you, I'll be installing one soon..
@leviallen2556
@leviallen2556 Жыл бұрын
Thank you!
@ronbonick4265
@ronbonick4265 Жыл бұрын
EXCELLENT INFO Thanks Bruh !!!!!!!!!!!
@ElectricalCodeCoach
@ElectricalCodeCoach Жыл бұрын
Let's get to it!
@kangaroogod
@kangaroogod Жыл бұрын
Thanks
@Eridan3766
@Eridan3766 Жыл бұрын
Awesome lesson Thanks
@ElectricalCodeCoach
@ElectricalCodeCoach Жыл бұрын
You bet Eric!
@charles-hu8ru
@charles-hu8ru 5 ай бұрын
Hey code coach, please explain to me how can you back up (2) 200 amp panels with a 100 amp generator? Are you using alot of SMM and load shedding? The nec says the generator has to be capable of carrying the full calculated load applied 702.4(B)(2)a. Thanks for any help in understanding.
@lindseyyah1
@lindseyyah1 5 ай бұрын
Very good explanation...
@ElectricalCodeCoach
@ElectricalCodeCoach 4 ай бұрын
Glad you liked it
@andrein9276
@andrein9276 10 ай бұрын
Question I know the lugs are probably not rated for a double tap but is it okay if I add a surge protector onto the load side lugs double tap it with the panel load wires on the lug. What’s the correct way to install a surge protector in a generac ATS
@Timeelectric29
@Timeelectric29 Жыл бұрын
Thank You Coach It was Really Helpful What is the maximum distance between Generator to the meter base or transformer Switch ?
@edgaranma23
@edgaranma23 6 ай бұрын
Great video! I think that would give me an answer to my problem, l have all the communication wires on both transfer switches, instead to connect only the black,white and blue wire between transfer #1 and transfer #2, l think thats the reason why fuses n1 on both transfer switches are blowing out.
@myles5150
@myles5150 Жыл бұрын
In the case of a 320 meter base with parallel lugs (2 200a panels) is there any nec rule against putting one panel through a 200a t switch and leave the other 200a panel fed straight from 320 meter base?
@birdielizard
@birdielizard 7 ай бұрын
If a lug is suitable for two conductors is is clearly marked on the lug......one indication is if the lug is oblong it will be rated for two conductors. Normally 200 amp load centers will not be supplied with 2 conductor rated lugs as only one conductor will accommodate 200 amp residential load center panels. Panelboards rated 225 amp 3 phase, and larger are common for two conductor terminal lugs.
@bradcors7143
@bradcors7143 11 ай бұрын
Do you have a video showing how you would incorporate a 400 amp disconnect when there is a disconnect combo with (2) 200 amp disconnects? Does this require two separate 200 amp transfer switches?
@Lilflippa713
@Lilflippa713 11 ай бұрын
Do I need separate ground rods for each transfer switch?
@emanuelemanuel7594
@emanuelemanuel7594 Жыл бұрын
Another one,i have two 1.5 ton and two 3.5 ton ac with 4 furnaces, dryer,fridge,stove,light,and more on two 200A panel can put all things on 24kw generator with 2 transfer switch and one generator as your teaching?24kw can hande it all my stuff? Thanks again
@emanuelemanuel7594
@emanuelemanuel7594 Жыл бұрын
Grate video, I have question.my meterbase is 400A from hydro side and I have two 200A panel can I use 400A transfer switch for both?and I want to buy two 22kw generator one for each panel 400A transfer switch can handle it both generator at the same time? Thanks
@retiredperson4054
@retiredperson4054 Жыл бұрын
did you ever make that video with the Meter Main Disconnect combo?
@ElectricalCodeCoach
@ElectricalCodeCoach Жыл бұрын
Not yet
@shawnkegel6526
@shawnkegel6526 Жыл бұрын
👍👍
@jonbaxter5074
@jonbaxter5074 Жыл бұрын
22 kw is the biggest one ive installed. Do they make a larger generator that would be more suitable for a 400 amp service?
@wfrencher80
@wfrencher80 Жыл бұрын
Recently GENERAC released a 26kw air cooled generator. I've installed one at a customer's residence recently. You can only go so big with air cooled generators though, so the bigger generators are typically oil-cooled and they're usually built for commercial use. Ive installed 24 kw generators on homes that have 2-200 amp panels, which is essentially a 400 amp service. When the power goes out at your home, typically you want the essential appliances working. These are usually water heaters, washer and dryers, furnace, AC, fridge, lights, and receptacle outlets. Sometimes some of these appliances aren't even electric powered, but are actually gas powered appliances. 22-26kw generators are generally capable of running these appliances, plus the lights and receptacles. I've taken an amperage reading of these homes that have larger services, and generally these homes aren't producing more than 50 amps on average.
@popstream4972
@popstream4972 Жыл бұрын
What size all in one wire for the new lp 26 kw Generac
@ElectricalCodeCoach
@ElectricalCodeCoach Жыл бұрын
Just have to go off the amperage
@joeycrapps
@joeycrapps Жыл бұрын
Why bond if house is already grounded it is ok with just house ground before what changed so much I couldn't just ground normal
@Hero1395
@Hero1395 Жыл бұрын
Because the house is not he first disconnect point anymore
@alvilla701
@alvilla701 Жыл бұрын
What about one panel, one generator and also solar together?
@coreyfranco7060
@coreyfranco7060 Жыл бұрын
Pretty sure i did this with (1) 400a transfer switch, no?
@coreyfranco7060
@coreyfranco7060 Жыл бұрын
Also mis-use or changing lugs is not allowed per generac and voids the warranty on the transfer switch
@TheMentch171
@TheMentch171 4 ай бұрын
Why not just one 400A transfer switch?
@retiredperson4054
@retiredperson4054 Жыл бұрын
Why use 2 200Amp Transfer Switches? Generac makes a 400Amp transfer switch.
@ElectricalCodeCoach
@ElectricalCodeCoach Жыл бұрын
Correct, they are very expensive and I am not sure you can get them right now, but I have not tried.
Wiring our Generac generator transfer switch to the meter can
21:55
Maynard Family Homestead
Рет қаралды 667 М.
E.I.A 🎬 automatic transfer switches
5:03
Electrical Code Coach
Рет қаралды 26 М.
ИРИНА КАЙРАТОВНА - АЙДАХАР (БЕКА) [MV]
02:51
ГОСТ ENTERTAINMENT
Рет қаралды 14 МЛН
Alat Seru Penolong untuk Mimpi Indah Bayi!
00:31
Let's GLOW! Indonesian
Рет қаралды 15 МЛН
Я нашел кто меня пранкует!
00:51
Аришнев
Рет қаралды 4 МЛН
HAD TO STOP THE APPRENTICE - FIRST BOARD SWAP
15:55
Bright Spark Electrical (midlands)
Рет қаралды 7 М.
Untangle the Mysteries of Control Panel Wiring!
6:05
eFIXX
Рет қаралды 23 М.
5 ways ways to fix an "open ground" UPDATED Video in description!!
14:56
Electrical Code Coach
Рет қаралды 170 М.
24KW, 200A Panel, Home Generator Hookup (GENERAC)
6:50
Karly the Sparky
Рет қаралды 79 М.
How To Wire a Two Way | One Lighting Point System.   (Practical Demonstration)
7:58
TOPHEIGHTS ELECTRICIANS, PLC
Рет қаралды 143 М.
Generac Generator Installation Part 1  | Clark, NJ
22:26
Electrician Ron
Рет қаралды 62 М.