This Call Had Me Stumped | HVAC Service Call

  Рет қаралды 17,754

HVAC Tech Tips

HVAC Tech Tips

Күн бұрын

In this video I run into a situation I had never seen before, well kinda… this was a strange one. Make sure to watch til the end. Thanks for watching!
Join this channel to get access to perks:
/ @hvactechtips

Пікірлер: 92
@Sunrise_HVAC
@Sunrise_HVAC Жыл бұрын
Float switch hooked up on Yellow instead of RED. Will do it all the time. Needs to be on red so the whole system shuts down and then the delay kicks in. If not the compressor will go off and on and start going backwards.. Yep if you don’t see it you will have a hard time figuring it out.
@dporrasxtremeLS3
@dporrasxtremeLS3 4 ай бұрын
Thanks for this explanation! You are very easy to understand! Thanks!
@dustinpetty7352
@dustinpetty7352 2 ай бұрын
The compressor was spinning backwards . Originally, scroll compressors had an ant i-reverse rotation Mechanical catch built into the mechanism. That way this would never happen but they removed it years ago I believe for efficiency reasons and now these scroll compressors always do this. Time delays sometimes help, but if the power blip is less than a half a second, a time delay cannot see this and this ends up happening anyways. It's frustrating. I believe ICM sells a single phase phase monitor and I believe it has a time delay built into it as well. It's the best thing I've seen out there to help with this problem so far. We see this problem all the time in Florida. Customers call all the time saying that the unit's not cooling and the outside unit is making a funny noise. We just tell them to turn the unit off at the thermostat. Wait 5 minutes and turn it back on and everything works great after that. This happens a lot. When a technician is fooling around with a float switch on the condensate pump or one in the drain pan well the system is running and then this accidentally happens. Turn the unit off. Wait a minute or two and turn it back on and you'll be good to go. Have fun out there!
@rcinfla9017
@rcinfla9017 Жыл бұрын
Always good to have a short cycle timer on compressor 24vac contactor control. If not incorporated into unit you should add one in compressor control line. They are not expensive and good insurance. If you live in a place like Florida, the lightning capital of world, there are a lot of grid glitches that trip a short cycle on compressor. Copeland says running backward is not damaging but it does overheat compressor causing compressor internal protection breaker to trip. When it resets and starts up compressor again it runs in correct direction. However, too many trips on these compressor protection cutout switches can damage them, requiring a compressor replacement. BTW, some electronic thermostats claim to have short cycle protection but on some that is only for user tweaking controls reactivating cooling shortly after unit went off. If they do have short cycle protection and installed lacking 24vac return blue 'C' wire, opting to run thermostat on internal battery, there is no complete 24 vac power path from transformer to thermostat to detect a power short cycle glitch.
@jx5hficus176
@jx5hficus176 2 жыл бұрын
This has givin me answers for a couple calls that I was at for hours and left defeated.
@luismelchor744
@luismelchor744 Жыл бұрын
Appreciate this man trying to absorb as much info as possible. Just finished trade school hoping to get hired soon.
@HVACTechTips
@HVACTechTips Жыл бұрын
Hope all goes well for you. I hope the channel helps as you continue to learn.
@abrahamduran1952
@abrahamduran1952 Ай бұрын
Same here just trying to expand the knowledge
@keithmckay8746
@keithmckay8746 2 жыл бұрын
I've had this happen to me once or twice. First thing I thought immediately from the sound of it was it was running backwards because the compressor sounding a lil crunchy lol. Good on you for figuring it out man!
@thecoolguy23
@thecoolguy23 2 жыл бұрын
Maaaan that happened twice to me this week you know checking the float switch on the maintenance and by accident i engaged the switch really fast compressor got louder and it turned off thermal overload i let it cool and unit was working just fine! 😨 And i was struggling because i didn't think was the compressor. Thats why i like to cut the R from the board instead Y to avoid that! Didn't know that make the compressor run backwards sound like it's working but is not doing anything! Thanks for sharing it! 👍👍
@ogie5194
@ogie5194 2 жыл бұрын
I like watching hvac video's. But most are the same over and over. This my friend was a great little video of something you don't see everyday. Thanks.
@MariosACandRefrigeration
@MariosACandRefrigeration 2 жыл бұрын
we normally add a time delay to prevent this.thanks for sharing.
@Sunrise_HVAC
@Sunrise_HVAC Жыл бұрын
Has a time delay. A lot of installers hook them up to the yellow only. Contractor just goes off and there is no delay in between yellow to contactor…… RED is the one that the float switch should be breaking on if not it bypasses the delay..
@tonyd4346
@tonyd4346 Жыл бұрын
I’m new to service. I thought maybe it was a heat pump and the reversing valve was acting up. Great video! Thanks!
@musicnerd72
@musicnerd72 Жыл бұрын
Wow! Didn't know they could run backwards... Interesting!
@adamcraig1568
@adamcraig1568 2 жыл бұрын
Real life scenario. Thanks!
@MrMultitool
@MrMultitool 2 жыл бұрын
I've never seen that happen Good job! Everyday is a school day
@marcusmcduffie2106
@marcusmcduffie2106 Жыл бұрын
Thanks for the golden nuggets
@jmead6121
@jmead6121 Жыл бұрын
Wow exactly was my 1 st thought compressor running backwards but good find to find an safety switch problem ..ive had a only a few pumps do that over last 25 yrs in the business ive caught them bounce on & off on an pan switch when pan was full of water but that way more obvious , but always good idea to test & to fill an pump with water & make sure it cycles on & off ..Great Job / glad that was all there was
@miguelquiroz1550
@miguelquiroz1550 2 жыл бұрын
Wow. Who can tell that was the problem. Great info brother. Thanks!
@broderickbrownbrown4082
@broderickbrownbrown4082 4 ай бұрын
Sometime thunder, bad weather can cause a power surge that causes the compressor to function like that.
@dporrasxtremeLS3
@dporrasxtremeLS3 4 ай бұрын
Thanks, I did not know that. Weather! Woww! Surges, brown outs? Lighting !
@jfrancis98
@jfrancis98 2 жыл бұрын
Not sure if I would have checked the TXV first thing. Thank you for sharing and glad you ended up getting it!
@user-nh9ox4xw8o
@user-nh9ox4xw8o Ай бұрын
If you break red, you will head to the attic to see why the system is off. If you break yellow you head to the cu Drain issue will be at attic so red will save time wasted trying to troubleshoot the cu that isn’t the problem
@millertime3794
@millertime3794 2 жыл бұрын
Thanks for being humble
@Rccrdawgs
@Rccrdawgs 2 жыл бұрын
I was already thinking backwards right as you said that safety was bumping. Would've over heated soon and you would've been scratching your head want to know why it was getting hot! GOOD FIND
@jericosha2842
@jericosha2842 2 жыл бұрын
Daaang... That's crazy. Good catch.
@brownsugar9633
@brownsugar9633 2 жыл бұрын
I love your honesty
@chrissipple1018
@chrissipple1018 Жыл бұрын
Most of the new scroll compressors have an anti reverse mechanism built in. An easy way to check if the thermostatic expansion valve or TXV, I don't do the acronym thing I'm not that lazy yet. Put the system in cooling, let it run for a while and then shut off the condenser fan motor and let it run. Watch the high side pressure don't let it get over 400 psi R 410a. If the valve is working properly the low side pressure should stay the same. That shows that the valve is maintaining the superheat. It will raise a little when the high side pressure gets closer to the 400 psi mark. If the valve starts moving around it's not holding the superheat setting. Just some useless information.
@tonyd4346
@tonyd4346 Жыл бұрын
Not useless info! Good tip. Thanks, I’ll use it.
@ironavenger6615
@ironavenger6615 Жыл бұрын
Same happens if you have your run winding on your run cap rather then the start winding. Ive seen new techs do this same mistake. Id still look at it too due to it being new unit. People make mistakes
@ccthepope
@ccthepope 2 жыл бұрын
Thanks for sharing this video!
@codyharris8665
@codyharris8665 2 жыл бұрын
Had a Rheem AC do the exact same thing on me a few months back. New install with a condensate pump and all! I was by AC when it kicked off on me twice… unit made the most horrible noise and when it kicked off compressor ran backwards both times. Found out it was issue with condensate pump
@n.gineer8102
@n.gineer8102 Жыл бұрын
Usually a power blip but no point in asking as most people don’t notice. I’ve had power blips that did exactly that to compressors but they will usually overheat. The float switch doing it is really unique though. Noisy when they stall. Added a time delay cube so it can’t fast cycle. Problem solved.
@dmvhvactech
@dmvhvactech 2 жыл бұрын
Nice video figuring that out, thanks for sharing 👍
@tingo210
@tingo210 2 жыл бұрын
good explanation
@davidnelson4312
@davidnelson4312 Жыл бұрын
Compressor was running backwards. It happens all the time in Florida with lightning 🌩 and storms
@Ageehvac
@Ageehvac 2 жыл бұрын
I just learned something else to watch out for....thanks guy....hvac on.....
@jonathanraul4086
@jonathanraul4086 2 жыл бұрын
Great video! Thank you for sharing
@hrdworkin7633
@hrdworkin7633 2 жыл бұрын
Great Catch! Love your vids....thanks
@altyndom7039
@altyndom7039 Жыл бұрын
Didn’t check the filter or the either of the coils as well make sure all the vents re open.
@user-nh9ox4xw8o
@user-nh9ox4xw8o Ай бұрын
Nest thermostat have a tendency to do the same fault
@soloch69
@soloch69 2 жыл бұрын
Great 👍🏻 video like always keep them videos coming
@smacleod69
@smacleod69 Жыл бұрын
I have definately turn the main power of and back on and get that sound on the compressor. Only once have I ever had the compressor with equal pressures. Adding or removing 410a didn't work. Even replaced TXV. Same problem. And all this was still under warranty.
@HVACTechTips
@HVACTechTips Жыл бұрын
Wow
@tyer7.628
@tyer7.628 2 ай бұрын
Compressor short cycled. Once reset you were good
@justinperry68
@justinperry68 2 жыл бұрын
I’ve scene super seal fuck with pressures that haven’t run for a few days(Customers have turned system off) bad cap, replaced started up, head pressure at 290, ran system for 15 minutes, then dropped to normal pressures, SH SC a perfect. Yellow dye and the smell of QuickStart when I took my gauges off.
@sknight0391
@sknight0391 2 жыл бұрын
Excellent! 😎👍
@donnellcairns3137
@donnellcairns3137 Жыл бұрын
Man !!! We are not perfect, that's happened to me one time and you would think the time delay would pick it up !!! But does not
@Slavelife9279
@Slavelife9279 11 ай бұрын
So that means your pump was wired to shut off the a/c only, if it was wired to break R to the digital thermostat the thermostat would go through time delay and that wouldn’t happen.
@gb3484
@gb3484 2 жыл бұрын
No worries, it happens to the best of us!
@MrLatenttraveler
@MrLatenttraveler 3 ай бұрын
Years ago mfgs put delay on em, now it’s in the circuit board but if the pump is breaking y it may not make board time out Add a delay on break timer … used to be 30 second on the mfg timers
@dipley3771
@dipley3771 2 жыл бұрын
So were they breaking y or r , cuz you would think if they were breaking r why would it not trigger that 5 min delay on the thermostat? If they were breaking Y they're chalked
@billj4859
@billj4859 2 жыл бұрын
Trane claims the Nest and Ecobee stats will do that. I keep tdr's on the truck for those.
@billy5032
@billy5032 Жыл бұрын
Next time break red wire thru condensation pump not yellow and use the thermostats time delay to prevent this from happening again
@tommymatthews4984
@tommymatthews4984 Жыл бұрын
Im kinda new to service and can say ive also experience this. We are paid a certain amount by the job and i was trying my best to figure out what was going on. I turned the unit off to check the caps and when i turned it back on equal pressures i was like what the hell. Can this happen with straight air?
@mp289634
@mp289634 Жыл бұрын
I see two possible causes of the equalized pressure. Yes when you cut the power off and on real quick it can trick fuck the compressor and sound like shit. Based on your pressures I’d have to guess it was cool day and cold nights season. With that being said I’d have to guess it was 60-65ish degrees outside when you were there and about 70 inside. I see an overcharged system that tried to run early in the morning when it was 50-55 degrees outside and caused the plates in the compressor to separate and pressures to equalize. The sub cooling is high for the given outdoor temp and your super heat is on low side… low super heat is either low airflow or overcharged system flooding the evap coil.
@michaelthurber2660
@michaelthurber2660 2 жыл бұрын
410-A?
@TNHVACLIFE
@TNHVACLIFE 2 жыл бұрын
I had that exact same thing on a trane unit the other day
@HVACShopTalk
@HVACShopTalk Жыл бұрын
Good video man
@HVACTechTips
@HVACTechTips Жыл бұрын
Thank you 🙏
@hvacrnortheastern2110
@hvacrnortheastern2110 2 жыл бұрын
Good catch great video.
@enriquepenuelas1084
@enriquepenuelas1084 2 жыл бұрын
Thanks buddy
@barbarafogle3541
@barbarafogle3541 Жыл бұрын
What did you do to resolve the problems or prevent it from reoccurring? What did you actually do to justify your fee?
@zoomergrrlinluv
@zoomergrrlinluv Жыл бұрын
Id think he changed the condensate pump,
@HVACTechTips
@HVACTechTips Жыл бұрын
Yes I did. And we went back and installed a break on make relay
@Godfearing2002
@Godfearing2002 Жыл бұрын
It’s raining you don’t think it had something to do with the pressures?
@juanrobles9511
@juanrobles9511 2 жыл бұрын
Will a time delay switch work ? It would keep the compressor from coming on after a small power surge. By the way good video👍
@kdmq
@kdmq 2 жыл бұрын
Beat me to it I was thinking the same thing.
@Karl-bc2os
@Karl-bc2os 2 жыл бұрын
Most thermostat have a time delay built in. Some have installation settings where it can be turned off but if the unit loses power for a fraction of a second it isn’t always registered by a time delay. I had a system where the contactor would flicker really fast after a couple minutes of running and they compressor would start screaming. Every time I checked the system everything looked great. Thought it might have been a bad defrost board intermittently working but it was just a float switch that wasn’t fully seated and the water would lift it just enough where the float made a partial disconnect
@chuckferraris8489
@chuckferraris8489 2 жыл бұрын
Mount a time delay in the condenser for 30 seconds or break the r for the thermostat.. if the drain pump did it once, there’s a good chance it’ll do it again..
@Raysmaintenance
@Raysmaintenance 2 жыл бұрын
good info to know thanks
@michaelthurber2660
@michaelthurber2660 2 жыл бұрын
What ref? Out door ambient? Seen the SH, but did you measure it? Just currious.
@c21meister
@c21meister 2 жыл бұрын
Oh I was way off they definitely is a new one
@stephwaylonwells3218
@stephwaylonwells3218 2 жыл бұрын
👍
@marvin7048
@marvin7048 Жыл бұрын
Looked like a weak compressor
@J9993x
@J9993x 2 жыл бұрын
Thank you so much I just got out of trade school last year looking for jobs any tips on being a good tech ?
@HVACTechTips
@HVACTechTips Жыл бұрын
Be honest
@Gamespeed01
@Gamespeed01 Жыл бұрын
Put that seatbelt on
@junior-hk2jt
@junior-hk2jt 2 жыл бұрын
Question do they have an SS2 if so it happens all the time here in Florida either the SS2 trips it or the power came and went and the compressor just kind of went out of sync. Usually if you shut it off and turn it back on it'll be fine to remedy this put in a time delay on break
@junior-hk2jt
@junior-hk2jt 2 жыл бұрын
Oh check and flush drain if necessary
@tyer7.628
@tyer7.628 2 жыл бұрын
Yup wee see it so often. Just enough water to push the float up a little and the compressor will start to run backwards.
@thisisyourcaptainspeaking2259
@thisisyourcaptainspeaking2259 2 жыл бұрын
Good catch, so no compressor delay time involved with condensate pump interrupt?
@lewissiegler1025
@lewissiegler1025 2 жыл бұрын
Great info. Why aren't you wearing your seat belt?
@alross18058
@alross18058 2 жыл бұрын
short cycle timer
@1984juant
@1984juant 2 жыл бұрын
Sybscribed!
@nicholasmendrz8235
@nicholasmendrz8235 2 жыл бұрын
🤯
@wd8557
@wd8557 2 жыл бұрын
Take that pump out of the system problem solved.
@c21meister
@c21meister 2 жыл бұрын
That compressor looks bad the valves maybe shot
@markbeiser
@markbeiser 2 жыл бұрын
Scroll compressor, no valves.
@eric4467
@eric4467 Жыл бұрын
A three phase compressor wired incorrectly will run backwards with equalized pressures. Never seen it on a single phase unit.That’s interesting. Good catch.
TXV Troubles... HVAC Service Call
14:47
HVAC Tech Tips
Рет қаралды 43 М.
You're wasting money on heating! Use your A/C!
17:11
Tech Ingredients
Рет қаралды 461 М.
What will he say ? 😱 #smarthome #cleaning #homecleaning #gadgets
01:00
If Barbie came to life! 💝
00:37
Meow-some! Reacts
Рет қаралды 75 МЛН
Get 10 Mega Boxes OR 60 Starr Drops!!
01:39
Brawl Stars
Рет қаралды 19 МЛН
UNO!
00:18
БРУНО
Рет қаралды 5 МЛН
No AC Service Call
15:08
HughesMan HVAC
Рет қаралды 13 М.
No AC Service Call
14:09
HughesMan HVAC
Рет қаралды 3,2 М.
Locked Compressors
20:13
HVAC School
Рет қаралды 112 М.
2 Furnaces Not Heating | Service Call | Dual Diagnoses
12:01
HVAC Tech Tips
Рет қаралды 7 М.
When Should Air Conditioner or Furnace be Replaced?
10:47
Word of Advice TV
Рет қаралды 260 М.
How Many Calls In ONE Day Is Too Much?? | HVAC Life
14:32
Quality HVACR
Рет қаралды 185 М.
No Cooling Calls On Several AC Units!
24:52
Jeff’s HVAC Adventures
Рет қаралды 5 М.
Odd Complaints Lead to Scary Find! #hvacguy #hvaclife
29:11
HVAC GUY
Рет қаралды 86 М.
What will he say ? 😱 #smarthome #cleaning #homecleaning #gadgets
01:00