measureQuick Diagnostics: Behind The Curtain

  Рет қаралды 2,477

measureQuick

measureQuick

Күн бұрын

Jim demonstrates the power of measureQuick’s HVAC diagnostics using a live example of troubleshooting low superheat. All of measureQuick’s diagnostics are verified in the lab and in the field before they are integrated into the app.
0:00 - Introduction to MeasureQuick Diagnostics
0:17 - Misconceptions about Low Airflow and Superheat
0:37 - Overview of the System and Current Operation
1:00 - Creating a Low Airflow Situation
1:35 - Observing the Effects of Low Airflow
2:10 - Explanation of Pressure and Temperature Changes
2:58 - Superheat and Subcooling Trends
3:36 - Concept of Charge Migration
4:36 - Simulating a Blocked Evaporator Coil
5:20 - Stabilization of the System
6:20 - Reinstalling the Blower Door
6:58 - Effects of Restoring Airflow
7:56 - Hunting and Flooding Explained
8:40 - Testing and Engineering in MeasureQuick
9:01 - Key Takeaways

Пікірлер: 21
@arthurhartwick7974
@arthurhartwick7974 11 күн бұрын
It took me a while to realize the behavior of a "fixed" metering device is dynamic due to changes in the high side pressure. On a hot day when there's more load on the system pressures will go up and more refrigerant will go through the fixed metering device. In the experiment you ran, the high side pressure dropped, which lowered the amount of refrigerant going through the piston which helped the system stabilize in the low airflow condition.
@measureQuick
@measureQuick 11 күн бұрын
@@arthurhartwick7974 100% correct! I was thinking earlier I wish I had said that in the video.
@matthuss1914
@matthuss1914 11 күн бұрын
This software saves me hours of time doing math and guessing. It usually gets it right on the first or second fault. It has helped me immensely. Usually it describes the exact problem I I’m thinking and sometimes it surprises me. Some people think this is a shortcut, yes and no. It teaches you too. I spend less time on a service call often. Thanks for this!
@Andersonairchris
@Andersonairchris 11 күн бұрын
Can we please get a subscription service for the app instead of buying qbits!
@joeshearer1247
@joeshearer1247 11 күн бұрын
Yes please let us have a subscription level to pay to be allowed to take screenshots again
@jasontrammell7982
@jasontrammell7982 11 күн бұрын
I appreciate your contribution to moving the industry forward Jim. The MQ app is fantastic, recently it keeps saying the “seer rating is not possible”. In the real world the seer rating is almost never possible.
@measureQuick
@measureQuick 10 күн бұрын
Usually what happens in that case is the air handler and condenser amps are swapped.
@lynncomstock1255
@lynncomstock1255 11 күн бұрын
Twice in a 40-year career on water cooled, R22, TXV systems with low airflow I witnessed such severe flooding that the discharge lines were heavily frosted. The first one was a 100-ton Carrier system, the second was a 5-ton Chrysler Airtemp system. The compressors survived somehow. I swear that this is true. I never saw anything close to that on air to air systems.
@measureQuick
@measureQuick 10 күн бұрын
I’ve seen a hot gas line, frost, but never a discharge line. Sometimes the refrigerant would back up in the hot gas line and has the system ran it would’ve evaporate out and cause the frosting. We had to put a check valve on the packed tee on the expansion valve to stop it.
@brianmcdermott2430
@brianmcdermott2430 11 күн бұрын
Great info. to know. Thank you, Jim.
@AARONJL92
@AARONJL92 11 күн бұрын
Love these scenario training videos. Thanks Jim! Looking good too 😎
@horsth9566
@horsth9566 11 күн бұрын
….got a little bit out of this video? No, but a whole lot. Always looking for your videos, and always impressed how well it is presented. Beautiful!! Thank you Jim. I’m wrestling with low SC and low SH. Suspecting an oversized piston. Perhaps I should increase the blower speed?
@robertcherry4971
@robertcherry4971 6 күн бұрын
What are your saturation temperatures with the low superheat and low subcooling? Return temp Wet bulb and dry bulb? Supply temp dry bulb? Outdoor ambient? Thank You!!
@jimmylanders2175
@jimmylanders2175 11 күн бұрын
Awesome video
@pubchat2913
@pubchat2913 10 күн бұрын
Wicked good video Thank you
@realSamAndrew
@realSamAndrew 11 күн бұрын
If you increase airflow and the charge boils off quickly, why is there no superheat? Seems like you wind up with all vapor so no risk of liquid to the compressor.
@measureQuick
@measureQuick 11 күн бұрын
@@realSamAndrew 0 superheat means liquid flooding. The refrigerant boils so quickly that it carries the liquid with it. The rapid boiling basically pushes the liquid out of the evaporator.
@HVACRTECH-83
@HVACRTECH-83 4 күн бұрын
Well I was also wondering about this too. How do you know for sure it was flooding just because it says zero sh? I stopped the video when you put door on and asked what we thought was gunna happen,and thought about it and I predicted it would shoot strait to zero but for a different reason than you explained. So I thought it would instantly start raising in sat/ and pressure,which it did, but I thought the suction line would take 20 or 30 secs to start reading correctly. So if the vapor line was still reading around 28 and sat went up to 31 you'd be about 3 deg subcooled and since there's no negative sh it just says 0. Same exact thing as when the sh went up briefly when you first took the door off,then started coming down once pipe cooled down. Without a clear pipe there's no way to know unless you hear the compressor actually flood. Rite?
@measureQuick
@measureQuick 4 күн бұрын
@@HVACRTECH-83 I know for sure that it was flooding because when I was an instructor I put sight glasses in suction line and performed the same experiment. I have seen it. Subcooling cannot be negative. If it displays that way it is an error in the calculation.
@user-kn7cp4me8n
@user-kn7cp4me8n 10 күн бұрын
But what if we have a dirty condenser coil and low indoor air flow? In that case we would flood the compressor I think. What do you think? Thanks.
@measureQuick
@measureQuick 10 күн бұрын
@@user-kn7cp4me8n it likely still would not as your not moving enough heat. The low side has to absorb heat to reject it on the high side.
How to Use measureQuick with Variable Speed Equipment
18:40
measureQuick
Рет қаралды 4,9 М.
Air balancing - Intelligensen vezérelt PRO mérési program
3:15
Testo Magyarország
Рет қаралды 9
Вечный ДВИГАТЕЛЬ!⚙️ #shorts
00:27
Гараж 54
Рет қаралды 14 МЛН
I Can't Believe We Did This...
00:38
Stokes Twins
Рет қаралды 108 МЛН
Compressor Facts and Troubleshooting  (Don Gillis / Trevor Matthews)
3:13:28
Best Practices for Charging A System [2024 Version]
23:03
measureQuick
Рет қаралды 17 М.
"Flammable" Refrigerant Facts for Residential HVAC
1:02:01
HVAC School
Рет қаралды 42 М.
Low Suction Pressure Is Not Always Low Freon 🧐
4:13
ACTS Services
Рет қаралды 8 М.
Using measureQuick to Identify a Suction Line Restriction
10:16
measureQuick
Рет қаралды 14 М.
Biggest Megaprojects Under Construction in 2024
20:25
MegaBuilds
Рет қаралды 340 М.
Mastering Superheat: The Trick to Charging an HVAC Unit
15:33
Mechanical Pros
Рет қаралды 25 М.
Best Practices for System Evacuation [2024 Version]
16:07
measureQuick
Рет қаралды 8 М.
DIY Cascade Refrigeration System (Part I)
19:15
Hyperspace Pirate
Рет қаралды 256 М.