Vaillant Ecotec pump change

  Рет қаралды 23,286

CP Utility Solutions

CP Utility Solutions

3 жыл бұрын

DISCLAIMER:
This video is only intended for use by qualified Gas Safe Registered engineers. You must not attempt any work on your boiler if you are not qualified. You must always carry out 26.9 checks upon completion of works on a boiler.
~
So in this video I show how to change the complete pump with the housing. On this older model pump with the white face you can't just swap the heads over as the fittings are the wrong size.
There's a few different ways of doing this, but I find removing the diverter valve completely with the pump attached is the easiest way.
The bottom return nut connection always seems to give me a bit of trouble to get it back on, but perserverance gets it done.
Hope you guys find this useful!

Пікірлер: 51
@chohanchohan8208
@chohanchohan8208 3 жыл бұрын
One of the Best Pump changes videos on the Net ...👏🏽👏🏽👏🏽👏🏽
@steventurner13
@steventurner13 2 жыл бұрын
Brilliant video, I have just changed a pump and it went perfectly following this method and in particularly the greasing of the seals to stick them in place.
@cputilitysolutions
@cputilitysolutions 2 жыл бұрын
Nice one mate 👍🏽
@paulrossiter9567
@paulrossiter9567 3 жыл бұрын
Brilliant work .....definitely looks like the way forward with these pumps 👏👏👏
@Viena-qrirwn3jjvgggvjm
@Viena-qrirwn3jjvgggvjm 6 ай бұрын
Bye btell me the nearest gamma for summer close baba, who is abraham lincplease tell me the metallica on the bottom of town
@Viena-qrirwn3jjvgggvjm
@Viena-qrirwn3jjvgggvjm 6 ай бұрын
134253
@Viena-qrirwn3jjvgggvjm
@Viena-qrirwn3jjvgggvjm 6 ай бұрын
Maybe that a bit sweet, buddy two thousand and thirtyeah buddy ba ba ba ba ba la bi baby whereabouts, baby rabbit, please bixby
@dawsonshaul7832
@dawsonshaul7832 Жыл бұрын
Good video mate very clear. If you don't want to take diverter out you can remove the side of the boiler case and the condense trap instead.
@cputilitysolutions
@cputilitysolutions Жыл бұрын
This was the R1 model so the side panels don't come off unfortunately, you can on the later models though 👍🏽
@gsraja2966
@gsraja2966 3 жыл бұрын
Nice enjoyed watching the video
@aminsajawal3935
@aminsajawal3935 3 жыл бұрын
Nice video learn a lot , u make it look so easy lol 😂 keep up the good work
@cputilitysolutions
@cputilitysolutions 3 жыл бұрын
Thanks man, it all comes with practice. The more you do you find your own routine and it becomes quicker and easier
@BaileysFace8
@BaileysFace8 2 жыл бұрын
Thank you Much easier way Noted.
@zali1457
@zali1457 3 жыл бұрын
Nice one keep it coming
@cputilitysolutions
@cputilitysolutions 3 жыл бұрын
Thank you mate!
@jonathanwilliams5471
@jonathanwilliams5471 3 жыл бұрын
Good video pal
@cputilitysolutions
@cputilitysolutions 3 жыл бұрын
Thanks mate
@fanyeros123
@fanyeros123 3 жыл бұрын
Great 👍 thanks 😊
@benscoey9675
@benscoey9675 2 жыл бұрын
Good stuff mate. Although just a tip, Diverter doesn't need to come out, pump will come out with it still in place, may save you a bit of time 😂👍
@TARSoda
@TARSoda 11 ай бұрын
Sometimes you need to remove the condi trap this way so it can be pick your poison
@anetaneykova1
@anetaneykova1 Жыл бұрын
Please, tell me what are the indications that require changing the water pump? Thank you.
@waseemkhaliq933
@waseemkhaliq933 3 жыл бұрын
I'd just like to say you can remove the pump without taking the bracket out you just have to be a bit aggressive and wiggle it out saves you taking the divertor out too!
@cputilitysolutions
@cputilitysolutions 3 жыл бұрын
Yeah I've tried that method as well, but I prefer this method personally. At the end of the day you gotta use whatever works best for you 👍🏽
@illuminate06
@illuminate06 5 ай бұрын
Great video, with the pump that you changed it for, can you just change the head for that one?
@cputilitysolutions
@cputilitysolutions 5 ай бұрын
Thanks 👍🏾 if it's Grundfos for Grundfos then yes
@feriak1975
@feriak1975 3 жыл бұрын
Thanks for the video man, did you need special tool to disconnect the Prv pipe cause i see it’s in a weird position and I don’t think normal spanner can unscrew it
@cputilitysolutions
@cputilitysolutions 3 жыл бұрын
Not really mate, the PRV nut is usually only hand tight as it's got a rubber washer sealing it so I've always been able to undo it by hand 👍🏽
@feriak1975
@feriak1975 3 жыл бұрын
@@cputilitysolutions ohhh that’s great mate, thanks for the tip, much appreciate
@xclusive463
@xclusive463 3 жыл бұрын
Do you work for yourself or a company ? Love the videos mate
@cputilitysolutions
@cputilitysolutions 3 жыл бұрын
Bit of both mate 😉 thank you, glad you're enjoying them!
@xclusive463
@xclusive463 3 жыл бұрын
@@cputilitysolutions top man work for yourself eventually cause ur a good engineer yu don’t need to make companies more richer than they already are 👍🏼🌟
@cputilitysolutions
@cputilitysolutions 3 жыл бұрын
@@xclusive463 let's see what opportunities the future brings eh 😉 thanks for your support man 👊🏽
@keithaldis8533
@keithaldis8533 3 жыл бұрын
Can yo change the he'd for another head which is the same? That is a silver head for another silver head? Great vid by the way. Really helpful
@cputilitysolutions
@cputilitysolutions 3 жыл бұрын
Yes you can change it for another Wilo head, but I don't think you'll get any new ones as Vaillant changed them to Grundfos. You can most probably get reconditioned ones or similar where you can just swap the heads over
@suheilhanna873
@suheilhanna873 3 жыл бұрын
👍👍
@adamsala9291
@adamsala9291 2 жыл бұрын
I like your channel 🤫 what's the orange drain hose called.
@alivarol4700
@alivarol4700 3 жыл бұрын
Good work mate It would be good if you could explain why you are changing the parts and why they could go wrong
@cputilitysolutions
@cputilitysolutions 3 жыл бұрын
Thanks mate, boiler was giving F75 fault code, changed pressure sensor first and was still doing it. Pump was making a grinding noise when running so suspected it was weak and changed it out. Problem solved 👍🏽
@bcr551
@bcr551 2 жыл бұрын
@@cputilitysolutions i have code f 6 and its a new for me what does it mean plz
@MikeeyThomson
@MikeeyThomson Жыл бұрын
Watched this the other day as I was doing one, great video. So it came out and new one went in no bother at all, however, the expansion vessel pipe from the pump housing to the expansion vessel, on the housing side it just would not seal. Leaked every time and that was with new washers. I just can't understand why. I'm going back tomorrow with a new pipe but if that doesn't work then I'm stumped. Any idea?
@cputilitysolutions
@cputilitysolutions Жыл бұрын
The only thing I can think of is a hairline crack on either the housing or the connection piece. How did you get on when you went back?
@MikeeyThomson
@MikeeyThomson Жыл бұрын
@@cputilitysolutions Not gonna lie I was shitting myself going back with the new pipe and the adapter for the gauge that goes in to the housing. But they worked and they sealed, thankfully. Still confused why the original didn't seal but when I put the new parts in, they felt a lot tighter to go in. It worked thankfully 👌
@cputilitysolutions
@cputilitysolutions Жыл бұрын
@@MikeeyThomson nice work mate 👍🏽
@chriscook7828
@chriscook7828 2 жыл бұрын
I noticed the new pump runs in the opposite direction to the old pump. Will this cause problems eg boiler getting to hot as the thermostat see the water temperature on the return?
@stephenjnolan
@stephenjnolan 2 жыл бұрын
I ALSO wanted to know if the rotation of the pump caused any issues. I’m about to swap a silver clockwise with the black Grundfoss anti-clockwise. Anything we need to know ? Thanks
@franktinnion5436
@franktinnion5436 3 жыл бұрын
videos are awesome must invest in some dust sheets mate had customers trying to claim for damage to stainless sinks & work tops in the past cover everything and cover your ass.
@martinasbury8889
@martinasbury8889 Жыл бұрын
Good video but I always leave the diverter in place and just remove the pump to replace.
@cputilitysolutions
@cputilitysolutions Жыл бұрын
Yeah I used to do that as well, but I just find this way a bit easier. Normally if it's a grundfos for grundfos I just swap the heads over
@raul835
@raul835 11 ай бұрын
Why can't you just change head on these?
@raymondwong2159
@raymondwong2159 Жыл бұрын
ok so its confirmed then, tools are going away and im calling a professional lol
@cputilitysolutions
@cputilitysolutions Жыл бұрын
Always the best way mate
Vaillant EcoTec Diverter Valve Replacement | FULL
27:33
Plumbing Doctors
Рет қаралды 82 М.
Русалка
01:00
История одного вокалиста
Рет қаралды 4,9 МЛН
Who has won ?? 😀 #shortvideo #lizzyisaeva
00:24
Lizzy Isaeva
Рет қаралды 41 МЛН
Always be more smart #shorts
00:32
Jin and Hattie
Рет қаралды 49 МЛН
He sees meat everywhere 😄🥩
00:11
AngLova
Рет қаралды 11 МЛН
Vaillant Ecotec Pro - How To Change The Canoe Filter
7:31
Advanced Boiler Training
Рет қаралды 20 М.
Vaillant Ecotec Hydro Assembly Explained. Dr pipe
10:34
Dr Pipe
Рет қаралды 51 М.
Vaillant EcoTec Pro - Changing The Pump Body
17:55
Advanced Boiler Training
Рет қаралды 20 М.
Vaillant Ecotec Diverter valve change
14:15
CP Utility Solutions
Рет қаралды 30 М.
Vaillant EcoTec Plus. New diverter valve
13:07
North West Gas Certificates
Рет қаралды 2 М.
Vaillant Eco Tec Plus- Grundfos pump change
4:03
Fellowship Heating, Plumbing & Gas
Рет қаралды 1,4 М.
Plumbers from hell left this behind
14:56
Urban Plumbers
Рет қаралды 75 М.
Vaillant Ecotec Boiler Pump Problems: Grundfos Wilo
3:45
Mark Ray
Рет қаралды 126 М.
Русалка
01:00
История одного вокалиста
Рет қаралды 4,9 МЛН