What Sizes do Twin and Earth Cables Come in?

  Рет қаралды 19,015

GSH Electrical

GSH Electrical

Күн бұрын

Student training aid for all the different sizes in mm2 of twin and earth cables (PVC/PVC twin and CPC cable). This video includes the size of both live conductors line and neutral as well as the size of the often smaller CPC conductor (earth). It is very important that we understand the sizes of the live conductors in relationship to the CPC (earth) within this type of flat profile cable.
🔵Note that solid conductors are Class 1 conductors and solid stranded are Class 2 conductors. Video Link - Class 5 Flexible Cables - Construction, Number of Conductors - BS 1363 Plug Tops and BS 1362 Fuses • Class 5 Flexible Cable...
Construction of twin and earth cables and what size do they come in.
== 🕐 Time Stamps - Cut to the action 🕕 ==
00:00 - Sizes of twin and earth cable
00:08 - What do the regulations call them
00:21 - Live conductors
01:35 - 1 mm2 twin and CPC cable
01:51 - 1.5 mm2 twin and CPC cable
03:38 - 2.5 mm2 twin and CPC cable
04:23 - 4.0 mm2 twin and CPC cable
05:15 - 6.0 mm2 twin and CPC cable
06:05 - 10.0 mm2 twin and CPC cable
06:47 - 16.0 mm2 twin and CPC cable
07:21 - Cable colours
07:39 - Pre 2004 cable colours
08:13 - Full run through of sizes
08:44 - Full run through of CPC sizes
Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.
You can follow me day by day on Facebook, Instagram, Twitter and TikTok lookout for "GSH Electrical”.
▶️ FACEBOOK / gshelectrical
▶️ INSTAGRAM / brihzmraygdtmjmdb9lunq...
▶️ TWITTER / gsh_electrical
▶️ TikTok vm.tiktok.com/ZMRBLFdhe/
#GSHElectrical #Electricaltrainingvideos #cable #cables #conductor

Пікірлер: 60
@sergiofernandez3725
@sergiofernandez3725 Жыл бұрын
This popped up today and I remembered the great April fools joke when they said there was a new cable size. 0.5mm squared Twin and Earth. Well people started asking around at wholesalers, people looked it up on the internet and then even the IET got involved and got funny about it as well. It was a great wind up. Really worth a watch. Moving forward. Gaz always refers to this kind of cable as PVC/PVC twin and CPC cable. Examiners want to see it that way and do not like the term earth cable the rest of us call it Twin&Earth or T&E as it has been know for donkeys years.
@GSHElectrical
@GSHElectrical Жыл бұрын
Thanks for the great comment Sergio 👍🏻
@tilidie5272
@tilidie5272 Жыл бұрын
this guys been invaluable along my journey to become an electrician
@GSHElectrical
@GSHElectrical Жыл бұрын
Massive thanks for the comment 👍🏻
@gabeerlazem7798
@gabeerlazem7798 3 жыл бұрын
Excellent video as always. Thank you 🙏
@Lainge86
@Lainge86 Жыл бұрын
He was a fantastic tutor in college
@GSHElectrical
@GSHElectrical Жыл бұрын
Thanks for the 👍🏻👍🏻
@olly7673
@olly7673 Жыл бұрын
Good info Gaz thankyou, though I am surprisedto hear, knowing how you like to be exact in your teaching, to hear you say millimetre squared rather than square millimetre😉Keep up the good work.
@berkotropia
@berkotropia 9 ай бұрын
GREAT VIDEO!!!!
@GSHElectrical
@GSHElectrical 9 ай бұрын
Thanks
@desmcdowell2469
@desmcdowell2469 3 жыл бұрын
In Ireland, and most of Europe T&E is basically just a flat 3 core cable (all conductors insulated, all same cross sectional area). New regs here in Ireland which we refer to as IS10101 also call for a minimum fire rating on cable
@nsoper19
@nsoper19 Жыл бұрын
Doesn't that just end up being very wasteful?
@Marcel_Germann
@Marcel_Germann Жыл бұрын
@@nsoper19 Here in Germany the CPC is fully insulated within the cable since it must be marked green/yellow over the whole length of the cable run. Exception from that are cables with a concentric CPC. Up to 16mm² the CPC must be the same size as the line. Is the line between 16 and 35mm² the CPC must be at least 16mm², from 35mm² on the CPC must be at least half the size of the line conductor. And the 1mm² isn't permitted. Smalltest copper conductor size for fixed installation is 1.5mm², for aluminium it's 16mm². The aluminium size is since 1973 in West-Germany and 1990 in East Germany. In East Germany they used a lot of aluminium conductors. It's not only about current carrying capacity, this is due to mechanical stability, bending radius, damaging the conductor while stripping and such stuff. And here the conductors are solid up to 10mm², so the stranded versions are starting from 16mm² here.
@Marcel_Germann
@Marcel_Germann Жыл бұрын
In Germany most cables are round shaped, not flat. Only type that is flat is NYIF, but no one here uses it anymore. Back in the old days it was a cheap alternative, but you can only use it in dry rooms, only below plaster, must be nailed to the brickwork and then plastered over, no contact to combustible construction materials. The wires are PVC insulated, but the cable sheath is made of rubber. And now these days it's almost more expensive than the more flexible in its application NYM cable. In some countries like France, these cable types aren't permitted at all. They want conduits with single wires in there. That is one of the three cable types that use the old German cable designation system from pre-European harmonisation: NYIF, NYM and NYY. The old NYA for example was replaced by H07V-U.
@lawrencer25
@lawrencer25 Жыл бұрын
Nice video 👍👍👍
@GSHElectrical
@GSHElectrical Жыл бұрын
Thank you 👍
@tcpnetworks
@tcpnetworks Жыл бұрын
The terms used to describe the cable - remembered until 1.5 microseconds after license acquired...
@billalhossain3134
@billalhossain3134 Жыл бұрын
Should we not be using the low smoke zero halogen as the standard?
@GSHElectrical
@GSHElectrical Жыл бұрын
Great question 👍🏻. Thanks for watching. Gaz
@yordanyordanov4466
@yordanyordanov4466 Жыл бұрын
Can we get the size by looking at the cable for somebody who is not experienced? Are there any markings on the cable showing the size?
@michaeltb1358
@michaeltb1358 Жыл бұрын
It is marked on the sheath.
@CompuWhizz
@CompuWhizz 3 жыл бұрын
Weird, UK still allows bare CPC??? We in europe no longer allow bare cpc since 2017, plus the cross section of the cpc must match the live conductor cross section
@aryehelectricalltd7247
@aryehelectricalltd7247 3 жыл бұрын
you can buy all double insulated but the point of it is the earth in between the Land N and if any insulation from L or N break will create a short and not arc L to E/N the mob will trip N to E rcd will trip
@billalhossain3134
@billalhossain3134 Жыл бұрын
Interesting that !
@andysims4906
@andysims4906 Жыл бұрын
I don’t know where the CPC comes from. Even the manufacturers call their cable Twin and Earth .
@stuartandrews4344
@stuartandrews4344 Жыл бұрын
Circuit Protective Conductor,aka earth conductor..
@MrEdrftgyuji
@MrEdrftgyuji Жыл бұрын
Government busybodies
@garypautard1069
@garypautard1069 Жыл бұрын
I recall in the 60s when I was doing my apprenticeship there was a copper shortage and our contracting company were installing on a new housing estate . We were given solid core aluminium cable instead of 7/029 for ring circuits and all the electricians were moaning about how difficult it was to push solid core cables into a wall box. The shortage ended after about 4 months. Seems amusing now in todays modern 2.5mm use. I wonder if any of you modern day sparks have seen this cable in domestic homes.
@GSHElectrical
@GSHElectrical Жыл бұрын
Thanks for the information Gary 👍🏻
@peterweeds4682
@peterweeds4682 Жыл бұрын
Sorry to be a pedant, but it is not 1mm squared, it is one square mm. One mm squared is technically the same but only for one mm squared and one square mm. For 2.5mm squared (for example) this would actually be 5.5 square mm. That is why it is important to distinguish between 'mm squared' and 'square mm'. If we said 2mm cubed what would that mean? It could only really mean 2x2x2mm, being 8 cubic mm. So why would you say 2.5mm squared when you clearly mean 2.5 square mm?
@paulprescott7913
@paulprescott7913 Жыл бұрын
My personal opinion is that all cable should be LSF.
@GSHElectrical
@GSHElectrical Жыл бұрын
Thanks for your opinion 👍🏻
@andysims4906
@andysims4906 Жыл бұрын
Well for the last 3 years ish I been using LSF in multi occupied premises even though it’s not specified
@paulprescott7913
@paulprescott7913 Жыл бұрын
@@andysims4906 pretty much so have we.
@johnwarwick4105
@johnwarwick4105 Жыл бұрын
Never understood how the earth can be less than half the line conductor and comply with even the old regs 14 th when I started.
@TheEulerID
@TheEulerID 9 ай бұрын
The reason is explained in the video. The CPC does not normally carry load current, and if it does, it's under fault conditions and will be for no more than 5 seconds. There simply isn't enough time for 5 seconds of fault current to generate enough heat to damage the cable. As long as the conductor has a low enough resistance to carry enough fault current to trip the breaker (or blow a fuse) on a line to CPC fault within the defined period. With RCDs and RCBOs it's even less likely that there will be a significant fault current as a fault to CPC of more than 30ma will cause those to trip immediately. Whilst it's possible to construct elaborate failure scenarios such that the CPC is carrying a high current, but not enough to trip an over-current breaker, those are extremely unlikely and, as mentioned, will always trip where there's an RCBO/RCD involved, so that would have to fail as well.
@johnwarwick4105
@johnwarwick4105 9 ай бұрын
@@TheEulerID yes appreciate that but why does it only apply to conductors up to 16mm. Armoured and other industrial cables, Flexes all have equal size earths. ( too old to call them Cpc's) this anomaly only applies to t&e cable. I expect it dates back to the end of the war when materials were short!
@TheEulerID
@TheEulerID 9 ай бұрын
@@johnwarwick4105 I don't understand why we would want to make the CPC larger than it needs to be. As for industrial uses, then the parameters are going to be different. SWA doesn't come in the same colour codes as twin and earth, and doesn't have a dedicated CPC as such. It it is often used in three phase installations, sometimes as start, sometimes as delta. Sometimes the armour is used as the CPC. There are simply too many variables and usage patterns. In contrast, twin an earth is used in many domestics and commercial premises where the parameters of the requirements are well known, so it makes sense to make the most economical cable which suits those needs. If you really want to, you could wire up a domestic property using conduits and singles; there's nothing in the regulations to stop you doing so.
@Tryingtimes007
@Tryingtimes007 Жыл бұрын
3 x class 1, 4 x class 2, 😁👍
@GSHElectrical
@GSHElectrical Жыл бұрын
100% - see description plus a link at the end of the video to class 5 cables 👍🏻
@Roverturbo
@Roverturbo Жыл бұрын
Ok… without watching the video…. Cable sizes in the thumbnail.. 1.0mm , 1.5mm, 2.5mm, 4mm, 6mm, 10mm, 16mm. Do I win a prize? 😁
@GSHElectrical
@GSHElectrical Жыл бұрын
CPC sizes?
@GSHElectrical
@GSHElectrical Жыл бұрын
PS mm2
@Roverturbo
@Roverturbo Жыл бұрын
@@GSHElectrical lol couldn’t be arsed to put the 2 on the end of them all..
@Roverturbo
@Roverturbo Жыл бұрын
@@GSHElectrical off the top of my head,.. no you got me there.. I’ll watch the video lol.
@EdthePlumber
@EdthePlumber Жыл бұрын
Where’s the new 0.5mm?? 😜
@GSHElectrical
@GSHElectrical Жыл бұрын
😂😂😂👍🏻
@GaryAppledale
@GaryAppledale Жыл бұрын
Blimey, I’m not even a spark and calling the earth CPC annoys me - why use one word when you can use three 🤔
@therealdojj
@therealdojj Жыл бұрын
Beacause that's what it's called It's been shortened to earth over the years
@leer9951
@leer9951 Жыл бұрын
CPC was most probably coined by a government bod whose job it was one day to check all the electrical terms were prim and proper. You can’t fault Gary because he’s teaching apprentices to pass the exams and you have to use CPC to get the full marks.
@GSHElectrical
@GSHElectrical Жыл бұрын
Thanks Lee 👍🏻
@andysims4906
@andysims4906 Жыл бұрын
I’m a Sparky and I don’t ever call it a CPC . As far as I’m concerned it’s a Earth wire and always will be.
@Dog-whisperer7494
@Dog-whisperer7494 Жыл бұрын
Even the manufacturers label on the drum has it as flat twin and earth PVC insulated cable . The some of the tables in BS7671 also have as flat twin and earth
@peterweeds4682
@peterweeds4682 Жыл бұрын
Please don't confuse listeners by saying "one millimeter squared", which is incorrect. The error is better shown with a number higher than 1, for example 4. If I were to say "four millimeters squared" it would actually mean 4mm x 4mm = 16 square millimeters. So please say "one square millimeter", or "4 square millimeters" for clarity instead of "one millimeter squared" .
@harveygibbons1113
@harveygibbons1113 Жыл бұрын
Good video but just repeating the same thing 20 times
What electrical work are you allowed to do in your own home?
10:39
100❤️
00:20
Nonomen ノノメン
Рет қаралды 64 МЛН
Backstage 🤫 tutorial #elsarca #tiktok
00:13
Elsa Arca
Рет қаралды 28 МЛН
DELETE TOXICITY = 5 LEGENDARY STARR DROPS!
02:20
Brawl Stars
Рет қаралды 10 МЛН
СНЕЖКИ ЛЕТОМ?? #shorts
00:30
Паша Осадчий
Рет қаралды 2,4 МЛН
Cou fin VS cou musclé 📈
0:10
MATOS
Рет қаралды 69 М.
Electricians' Guide: Cable Rating Factors
12:45
eFIXX
Рет қаралды 19 М.
Testing Circuit Polarity
4:31
Master Electricians New Zealand
Рет қаралды 12 М.
The Best 3 Way Switch Explanation Ever!
11:49
Terry Peterman
Рет қаралды 4,1 МЛН
Twin & Earth Cables
20:27
John Ward
Рет қаралды 92 М.
100❤️
00:20
Nonomen ノノメン
Рет қаралды 64 МЛН